RFL 107460-5 Instruction Data

Type
Instruction Data
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL Electronics Inc.
I N S T R U C T I O N D A T A
RFL (C37.94) Fiber Service Unit
Multimode
107460-1 RS-449
107460-2
V.35
107460-3 G.703
1
07460-4
X.21
1
07460-5 E1
Single Mode
108015-1 RS-449
108015-2 V.35
108015-3 G.703
108015-4
X.21
108
015-5 E1
Multi and Single mode mounted in 1U chassis
107460-1-1 RS-449 (Multimode)
107460-1-2 RS-449 (Single Mode)
107460-2-2 V.35 (Single Mode)
107460-3-1 G.703 (Multimode)
107460-5-1 E1 (Multimode)
RFL Electronics Inc. Boonton, New Jersey USA
RFL FSU 107460-1
RS - 449
R
X
TX
DATA
SYNC
YEL
PWR
Figure 1. Typical RFL Fiber Service Unit, Front Panel view
DESCRIPTION
The RFL Fiber Service Unit (FSU) provides an interface between synchronous electrical signals and
optical fiber. It can be used with the RFL 9300, RFL 9745, RFL IMUX 2000 or other types of
multiplexers. It can also be used with any other C37.94 compliant, end device. There are a total of five
varieties of FSUs using both single and multimode fiber heads. They use RS-449, V.35, G.703, X.21
and E1 as inputs and outputs on the non-fiber side of the connection. Note that there is a modification
allowing the unit to be mounted into a 1U Chassis. The FSU is a stand-alone device, which is
essentially a translator to and from data sent using these five interface standards in accordance with the
IEEE C37.94 fiber protocol. The G.703 is 64,000 bps only and thus it has N fixed at 1. The other four
versions use a DIP switch to set the value of N. The characteristics of each of the five types of Fiber
Service Units, is shown in Tables 1, 2 and 3. Mounting dimensions are shown in Figure 12, except for
the 1U version of the unit which is shown in Figure 6 and 9.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
1 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
2 (973) 334-3100
Table 1. Fiber Service Unit General Information
Assy. Num. Multimode Assy. Num. Single Mode Interface
Type
Interface Cable Connector Pinouts
107460-1
107460-1-1
107460-2
-
107460-3
107460-3-1
107460-4
107460-5
107460-5-1
108015-1
107460-1-2
108015-2
107460-2-2
108015-3
-
108015-4
108015-5
-
RS-449
RS-449
V.35
V.35
G.703
G.703
X.21
E1
E1
37-pin female
37-pin female
37-pin female
37-pin female
15-pin female
15-pin female
15-pin female
15-pin female or two BNCs
15-pin female or two BNCs
See Table 7
See Table 7
See Table 7
See Table 7
See Table 8
See Table 8
See Table 8
See Tables 9 & 10
See Tables 9 & 10
Table 2. Multimode Fiber Service Unit Characteristics at 25º C
Assembly
Number
Type
Wavelength/
Mode
Connector
Type
Receiver
Sensitivity
(av
e
rage)
TX Power
(average)
Typical
Distance
(3dB margin)
107460-1
107460-1-1
107460-2
107460-3
107460-3-1
107460-4
107460-5
107460-5-1
LED
Emitter/
Detector
830 (+/- 40 nm)
multimode
ST
-11 dBm to
-32dBm
-11dBm to -23dBm
into 50μm fiber
-11dBm to -19dBm
into 62.5μm fiber
Up to 2km
(1.2 mi.)
Table 3. Single mode Fiber Service Unit Characteristics at 25º C
Assembly
Number
Type
Wavelength/
Mode
Connector
Type
Receiver
Sensitivity
(average)
TX Power (average)
Typical
Distance
(3dB margin)
108015-1
107460-1-2
107460-2-2
108015-2
108015-3
108015-4
108015-5
LED
Emitter/
Detector
1300 (+/- 30 nm)
single mode
ST -35dBm
-20dBm to -22dBm
into 9
μ
m fiber
Up to 10km
(6.2mi.)
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 3 (973) 334-3100
SPECIFICATIONS
As of the date this Instruction Data Sheet was published, the following specifications apply to the RFL
Fiber Service Unit. Because all RFL products undergo constant refinement and improvement, these
specifications are subject to change without notice.
IEEE Standard: C37.94 for N times 64 kilobit per second optical fiber interfaces between
teleprotection and multiplexer equipment.
Signal Connector Type:
15-pin male type D subminiature for G.703 and X.21
37-pin male type D subminiature for RS-449 and V.35
15-pin male type D subminiature or dual BNCs for E1
Data Rate: Programmable from 64 kb/s to 768 kb/s in accordance with Table 6.
Input Power Requirements:
38 to 150 Vdc @ 3Watts
Operating Temperature:
-30
O
C to +60
O
C (-22
O
F to +140
O
F)
Relative Humidity: 95 percent @ 40
o
C, non-condensing.
Dimensions for standard units:
Width: 5.13 inches (13 cm)
Height: 1.77 inches (4.5 cm)
Depth: 8.51 inches (21.6 cm)
Mounting Dimensions: In accordance with Figure 12 except for 1U chassis mounting.
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
INSTALLATION
Installation involves mounting the FSU module in its desired location, connecting all signal, coaxial and
power cables, and programming the module data rate and other configuration settings.
Note 1: Instructions for the 107460-1 thru -4 FSU units also apply to the following units.
108015-1 thru -4, 107460-1-1, 107460-1-2, 107460-2-2 and 107460-3-1
Note 2: Instructions for the 107460-5 FSU also apply to the 108015-5 and 107460-5-1 units.
To install the module, proceed as follows:
1. Carefully inspect the module for any signs of shipping damage. If you suspect damage to the
m
odule, immediately call RFL Customer Service at the number given at the bottom
of this page.
2. Check the assembly number on the front panel of the module to make sure the unit is compatible
with y
our interface requireme
nt as shown in Table 1.
3. Use Table 7 as a wiring guide for the D subminiature connector if your interface is RS-449 or
V.35. Use Table 8 as a wiring guide for the D subm
iniature connector if y
our interface is X.21 or
G.703. Use Table 9 as a wiring guide for the D subm
iniature connector if your interface is 120 ohm
E1. Use Table 10 as a wiring guide for the BNC connectors if your interface is 75 ohm
E1. When
fastening the D subm
iniature connector, make sure that the screws on both ends of the ma
ting
connector are tightened to secure the connector to the FSU front panel.
NOTE
ALL CABLING TO AND FROM THE FIBER SERVICE UNIT INTERFACE CONNECTOR
MUST UTILIZE SHIELDED TWISTED PAIR OR COAXIAL CABLE TO MINIMIZE
CROSSTALK AND INTERFERENCE FROM EXTERNAL SOURCES.
CAUTION
BEFORE ATTEMPTING TO MAKE POWER CONNECTIONS TO THE FIBER SERVICE
UNIT, MAKE SURE THAT YOUR POWER SOURCE IS COMPATIBLE WITH THE FSU. IF
THE IMPROPER VOLTAGE IS CONNECTED TO THE FSU, COMPONENT DAMAGE MAY
RESULT.
A suitably rated power disconnect device and over current protection device (e.g. fuse or circuit
breaker) must be installed between the station battery supply and the FSU power input. The
over current protective device should be rated at 0.5 to 1.5 Amps.
4. Connect input power to the following terminals on the rear-panel terminal block connector TB1, as
shown in Figure 5, see Figure 6 and 9 for 1U chassis installation.
Station battery positive TB1-1
Station battery negative TB1-2
Ground TB1-3
5. Fiber optic cables with type ST series bayonet fiber optic connectors must be connected to the fiber
optic heads on the front panel of the FSU m
odule a
nd to the far end chassis. When connecting fiber
optic cables, m
ake sure the connectors are properly aligned before tightening, and then fully
tighten
them
. This will help minim
ize losses in the connector.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
4 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 5 (973) 334-3100
6. For 107460-1 to -5, select the FSU data rate using DIP switches SW1-1 through SW1-4 in accordance with
Table 6. The FSU data rate must be set to the same data rate as the unit at the other end of the fiber. The
settings of SW1-1 through SW1-4 are ignored by the (107460-3) G.703 module since its data rate is fixed at
64 kb/s. For an RFL 9745 the data rate is 64 kb/s. For an RFL 9300 the data rate is 64 kb/s.
7a. For 107460-1, -2, -4, select a normal or inverted transmit data clock by using DIP switch SW1-5.
Place SW1-5 to the DOWN position to select normal transmit data clock.
Place SW1-5 to the UP position to select inverted transmit data clock.
For 107460-3, set SW1-5 to the UP position.
7b. For 107460-5, enable or disable CRC4 generation by
using DIP switch SW1-5.
Place SW1-5 to the DOWN position to enable CRC4.
Place SW1-5 to the UP position to disable CRC4.
8a. For 107460-1, -2 and -4, select a normal or inverted receive data clock by using DIP switch SW1-6.
Place SW1-6 to the DOWN position to select normal receive data clock.
Place SW1-6 to the UP position to select inverted receive data clock.
For 107460-3, set SW1-6 to the DOWN position.
8b. For 107460-5, select AMI or HDB3 encoding by using DIP switch SW1-6.
Place SW1-6 to the DOWN position to select HDB3 encoding.
Place SW1-6 to the UP position to select AMI encoding.
9a. For 107460-1, -2 & -4, select a normal or inverted data by using DIP switch SW1-7.
This switch is ignored by 107460-3.
Place SW1-7 to the DOWN position to select inverted data.
Place SW1-7 to the UP position to select normal data.
9b. For 107460-5, enable or disable Fiber Loopback by using DIP switch SW1-7.
Place SW1-7 to the DOWN position to enable Fiber Loopback.
Place SW1-7 to the UP position to disable Fiber Loopback.
10a. For 107460-3, enable or disable octet timing on the G.703 module by using DIP switch SW1-8. This
switch is ignored by 107460-1, -2 and -4.
Place SW1-8 to the UP position to enable octet timing.
Place SW1-8 to the DOWN position to disable octet timing.
10b. For 107460-5, enable or disable E1 Loopback by using DIP switch SW1-8.
Place SW1-8 to the UP position to enable octet timing.
Place SW1-8 to the DOWN position to disable octet timing.
11. For 107460-5, set switches and jumpers on Board B in accordance with Table 5.
12. The FSU is now installed and is ready to be placed in service. For more information consult the
Instruction Manual for the RFL 9745, RFL 9300 or the RFL IMUX 2000 as applicable.
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL 9300 Chassis
(Top View)
Type ST bayonet
connector ( 4 places)
Up To 2km for multimode
Up to 10km for single mode
RS-449
V.35
G.703
X.21
or E1
as
applicable
Tx fibe
r
Rx fiber
38 to 150 Vdc
Input Power
Fiber Service Unit
107500
Short haul fiber
interface module
Front
panel of
9300
Rear panel
of 9300
Motherboard
15-pin, 37-pin,
or BNC
connectors as
applicable
Tx
Rx
Rx
Tx
107460-X
Or
108015-X
Figure 2. Connecting the FSU to an RFL 9300
Note: The FSU unit is orientated differently in a 1U chassis; the connections are the same (See Fig. 6 and 9)
RFL 9745 Chassis
(Top View)
Type ST bayonet
connector ( 4 places)
RS-449
V.35
G.703
X.21
or E1
as
applicable
Tx fibe
r
Rx fiber
38 to 150 Vdc
Input Power
Fiber Service Unit
107310
Short haul fiber
interface module
Front panel
of 9745
Rear panel
of 9745
107460-X
Or
108015-X
15-pin, 37-pin,
or BNC
connectors as
applicable
Tx
Rx
Rx
Tx
Up To 2km for multimode
Up to 10km for single mode
Figure 3. Connecting the FSU to an RFL 9745
Note: The FSU unit is orientated differently in a 1U chassis; the connections are the same (See Fig. 6 and 9)
RFL C37.94FSU RFL Electronics Inc.
M
ay 20, 2013 6 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
Type ST bayonet
connector ( 4 places)
RS-449
V.35
G.703
X.21
or E1
as applicable
Tx fibe
r
Rx fiber
38 to 150Vdc
Input Power
Fiber Service Unit
15-pin, 37-pin,
or BNC
connectors as
applicable
Tx
Rx
Rx
Tx
Non-C37.94
compliant
multiplexer
9745, 9300 or
any other C37.94
compliant device
107460-X
Or
108015-X
Up To 2km for multimode
Up to 10km for single mode
Figure 4. Connecting the FSU to a non-C37.94 compliant multiplexer
Note: The FSU unit is orientated differently in a 1U chassis; the connections are the same (See Fig. 6 and 9)
RFL C37.94FSU RFL Electronics Inc.
M
ay 20, 2013 7 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
CONTROLS AND INDICATORS (107460-1 to 107460-4)
The RFL FSU (107460-1 to 107460-4) has user controls and indicators as shown in Figures 5 and 7.
Figure 5 shows the location of all controls, indicators and connectors on the front and rear panels of
the FSU module. Figure 7 shows the location of controls and indicators on ECB number 107463. The
function of all controls and indicators are described in Table 4.
CAUTION
+SB
-SB
38 - 150 VDC
0.25 A
20 W MAX
TB1
Ground Lug
RFL Electronics Inc. Boonton, New Jersey USA
RFL FSU 107460-1
RS - 449
RX
TX
DATA
SYNC
YEL
PWR
SW1
DS5
DS1
DS2
DS3
DS4
UP
DOWN
P1 or P2
SW1-8
SW1-1
U8
a. Front Panel
b. R
ear Panel
See Figure 6 for 1U
chassis installation
TB1-1
TB1-3
Figure 5. Fiber Service Unit, front and rear panel controls and indicators (107460-1 to 107460-4)
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
8 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
CONTROLS AND INDICATORS (107460-1-1, 107460-1-2, 107460-2-2,
107460-3-1)
The RFL FSU units 107460-1-1, 107460-1-2, 107460-3-1 are identical to the previous assemblies,
however they have been modified to fit into a 1U Chassis. As shown below, the unit mounts from the
rear with all controls, indicators and connections on the rear panel. Figure 7 shows the location of
controls and indicators on the ECB number 107463. The function of all controls and indicators are
described in Table 4.
1.718
REF.
1.25
REF.
.234 REF.
18.312 REF.
19.00 REF.
WT
12345656 34 2 1
Wiring Diagram for Two FSU's
mounted in a 1U Chassis
Front View of 107460-1-1, 107460-2-2, 107470-1-2,
107460-3-1 mounted in a 1U Chassis
+SB
-SB
RED
BLK
GRN
RED
RED
BLK
BLK
GRN
GRN
RFL ELECTRONICS
BOONTON, NEW JERSEY,USA
WT
WT
WT WT
Rear View of 107460-1-1, 107470-1-2, 107460-2-2, 107460-3-1
mounted in a 1U Chassis
G.703
RS 449
or V.35
RX
RX
TX
TX
GROUND
-SB
+SB
Ass'y 107460-1-1, 107460-1-2, 107460-2-2Ass'y 107460-3-1
DATA
DATA
SYNC
SYNC
YEL
YEL
PWR
PWR
DS5
DS1
DS2
DS3
SW1
SW1
81
U8 DS4
P2
P1
All other designations as Ass'y
107460-3-1
81
8
UP
DOWN
Figure 6. Fiber Service Unit, mounted in a 1U Chassis (107460-1-1, 107460-1-2, 107460-1-3)
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 9 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
U8
SW1
DS5 DS1 DS2 DS3
DS4
TB1 F1
Figure 7. Fiber Service Unit ECB No. 107463 (Board A), controls and indicators (107460-1 to 107460-4, 107460-1-1,
107460-1-2, 107460-3-1)
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 10 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
11 (973) 334-3100
Table 4. Controls and indicators, Fiber Service Unit (107460-1 to 107460-4, 107460-1-1,107460-1-2, 107460-2-2,
107460-3-1)
Location
Reference
Designation Function
Front Panel U8 Fiber optic detector
SW1 8-position DIP switch used to set FSU operating parameters as follows:
SW1-1 through SW1-4: Selects Data Rate in accordance with Table 6.
SW1-5: For 107460-1, -2 and -4,
Selects NORMAL or INVERTED Xmit Data Clock
as follows:
Down = Normal Clock
Up = Inverted Clock
For 107460-3, SW1-5 must be UP
SW1-6: For 107460-1, -2 and -4 selects NORMAL or INVERTED
Receive Data Clock as follows:
Down = Normal Clock
Up = Inverted Clock
For 107460-3, SW1-6 must be DOWN
SW1-7: On 107460-1, -2 and –4 selects normal or inverted data as follows
Down = Inverted Data
Up = Normal Data
SW1-8: (This switch applies to G.703 only and is ignored by all other FSU
modules) Selects octet timing as follows:
Up = Octet Timing Enabled
Down = Octet Timing Disabled
DS4 Fiber optic emitter
DS5 DATA LED (green), illuminated when data is present on the electrical interface.
DS1 SYNC LED (green), illuminated when the optical signal is in sync.
DS2 YEL LED (yellow), Yellow Alarm Indication, illuminated when the remote fiber
receiver has failed and the remote transmitter is sending a yellow code by
the
local fiber receive channel.
DS3 PWR LED (green), illuminated when power is ON.
P1 or P2 Connector
Rear Panel TB1 Power connector
Ground Lug Ground lug
On ECB
No. 107463
Board A
F1 FSU power supply fuse (see note below)
Note: F1 is a 0.25 Amp, 250 Volt SLO-BLO, 5x20 mm fuse.
Littlefuse part number is: 239.250
BUS part number is: GMD-.25A
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
CONTROLS AND INDICATORS (107460-5)
The RFL FSU (107460-5) has user controls and indicators as shown in Figures 8, 10 and 11. Figure 8
shows the location of all controls, indicators and connectors on the front and rear panels of the FSU
module. Figures 10 and 11 show the location of controls and indicators on Board A and Board B. The
function of all controls and indicators are described in Table 5.
CAUTIO
N
+SB
-SB
38 - 150 VDC
0.25 A
20 W MAX
TB1
Ground Lug
b. Rear Panel
See Figure 9 for 1U
chassis installation
TB1-1
TB1-3
RFL Electronics Inc. Boonton, New Jersey USA
E1
D
E1
Y
FO D
FO
Y
PWR
J206
RFL FSU E1 107460 -5
75 OHM
75 OHM
U8
SW1-8
SW1-1
J204
TX
RX
J207
UP
DOWN
SW1
RX
TX
DS7
DS6
DS1
DS2
DS3
DS4
a. Front Panel
Figure 8. Fiber Service Unit, front and rear panel controls and indicators (107460-5)
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 12 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
CONTROLS AND INDICATORS (107460-5-1)
The RFL FSU (107460-5-1) is identical to the 107460-5 unit shown on the previous page; however it
has been modified to fit into a 1U Chassis. As shown below, the unit mounts from the rear with all
controls, indicators and connections on the rear panel. Figure 10 and 11 show the location of controls
and indicators on Board A and Board B. The function of all controls and indicators are described in
Table 5.
1.718
REF.
1.25
REF.
.234 REF.
18.312 REF.
19.00 REF.
RFL ELECTRONICS
INC.
BOONTON, NEW JERSEY,
USA
2000
CCM
FS
U
WT
12345656 34 2 1
Wiring Diagram for Two FSU's
mounted in a 1U Chassis
Front View of 107460-5-1 mounted in a 1U Chassis
WT
TX
120 OHM75 OHM
RX
81
SW1
RX
FO Y
E1
D
E1 Y
FO D
PW
R
75 OHM
TX
WT
107460-5-
1
TX
75
OHM
RX
81
SW1
RX
TX
107460-5-1
WT
Rear View of 107460-5-1 mounted in a 1U Chassis
J206
U8
J204
DS7
DS6
DS1
DS2
DS3
DS4
J207
8
UP
DOWN
120 OHM
75 OHM
+SB
-SB
GROUND
+SB
-SB
RED
BLK
GRN
RED
RED
BLK
BLK
GRN
GRN
PWR
FOY
FOD
E1Y
E1D
Figure 9. Fiber Service Unit, mounted in a 1U Chassis (107460-5-1)
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 13 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
TB1 F1
U8
SW1
DS7 DS6 DS1 DS2 DS3
DS4
Figure 10. Fiber Service Unit ECB No. 107463-5 (Board A), controls and indicators (107460-5, 107460-5-1)
RFL C37.94FSU RFL Electronics Inc.
Ma
y 20, 2013
14 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
ON
1 2 3 4 5 6
TX RX
U G G U
12
0
75
J203
J207
J205
SW201
SW203
J206 J204
Figure 11. Fiber Service Unit ECB No. 107463-5 Board B (107460-5, 107460-5-1)
RFL C37.94FSU RFL Electronics Inc.
M
a
y 20, 2013
15 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
16 (973) 334-3100
Table 5. Controls and indicators, Fiber Service Unit (107460-5 and 107460-5-1)
Location
Reference
Designation Function
Front Panel U8 Fiber optic detector
SW1 8-position DIP switch used to set FSU operating parameters as follows:
SW1-1 through SW1-4: Selects Data Rate in accordance with Table 6.
SW1-5: Selects CRC generation as follows:
Down = Generate CRC4
Up = Do not generate CRC4
SW1-6: Selects AMI or HDB3 encoding as follows:
Down = Selects HDB3 encoding
Up = Selects AMI encoding
SW1-7: Enables or disables fiber Loopback as follows:
Up = Loopback enabled
Down = Loopback disabled
SW1-8: Enables or disables E1Loopback as follows:
Up = Loopback Enabled
Down = Loopback Disabled
DS1 FO D LED (green) Lights green when fiber optic data is being received.
DS2 FO Y LED (yellow) Lights yellow when remote fiber unit is not receiving data.
DS3 PWR LED (green) Lights green when power is applied to input terminals.
DS4 Fiber Optic Emitter
DS6 E1 Y LED (yellow) Lights yellow when the remote E1 unit is not receiving data.
DS7 E1 D LED (green) Lights green when E1 data is being received.
J204 DB-15 120 ohm E1 Connector
J206 75 ohm E1 TX Connector
J207 75 ohm E1 RX Connector
Rear Panel TB1 Input power connector (Connect +dc supply to +SB, connect –dc supply to –
SB)
Ground Lug Ground lug (Connect to earth ground)
On ECB
No. 107463-5
Board A
F1 FSU power supply fuse (see note below)
Note: F1 is a 0.25 Amp, 250 Volt SLO-BLO, 5x20 mm fuse.
Littlefuse part number is: 239.250
BUS part number is: GMD-.25A
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013
17 (973) 334-3100
Table 5. continued - Controls and indicators, Fiber Service Unit (107460-5 and 107460-5-1)
Location
Reference
Designation Function
On ECB
No. 107463-5
Board B
J203, J205 Used to ground the outer conductor of the BNC connectors when necessary.
Both jumpers should be set to “U” when using the DB-15 E1 port.
J203 is set to “G” and J205 is set to “U” when using the BNC E1 ports
J204
120 ohm E1 port (DB-15 male connector) Refer to Table 8 for interface
connections
J206
75 ohm E1 TX port (BNC connector)
J207
75 ohm E1 RX port (BNC connector)
SW201 Selects impedance of E1 port as follows:
Set to 75 when using 75-ohm BNC ports
Set to 120 when using 120-ohm DB-15 port
SW203 Used to set E1 operating parameters as follows:
SW203-1 Selects Timing Mode
ON = Thru timing
OFF = Internal timing
SW203-2 For factory use only (Switch must be set to ON position)
SW203-3 Selects Normal operation or Transmit all ones, on E1 port.
ON = Normal operation (default setting)
OFF = Transmit all ones
SW203-4 Enables or disables jitter attenuator
ON = Disable jitter attenuator
OFF = Enable jitter attenuator (default setting)
SW203-5 Jitter attenuator selection
ON = Receiver (default setting)
OFF = Transmitter
SW203-6 Selects inverted data
ON = Inverted data
OFF = Normal operation (default setting)
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
Table 6. Data Rate Selection
Data Rate (KB/s) N SW1-1 SW1-2 SW1-3 SW1-4
64 1 Down Down Down Down
128 2 Down Down Up Up
192 3 Down Down Up Down
256 4 Down Up Down Up
320 5 Down Up Down Down
384 6 Down Up Up Up
448 7 Down Up Up Down
512 8 Up Down Down Up
576 9 Up Down Down Down
640 10 Up Down Up Up
704 11 Up Down Up Down
768 12 Up Up Down Up
Note 1. G.703 is 64 kb/s only and has N fixed at 1.
Note 2. Down = OPEN, Up = CLOSED.
Table 7. RS-449 and V.35 Interface Connections Table 8. X.21 and G.703 Interface Connections
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 18 (973) 334-3100
RS-449 and V.35 X.21 and G.703
Signal Pin Number Signal Pin Number
RD(A) 6 RXD_A 4
RD(B) 24 RXD_B 11
RT(A) 8 RT(A5) 6
RT(B) 26 RT(B5) 13
ST(A) 5 TXD_A 2
ST(B) 23 TXD_B 9
SD(A) 4 Ground 1, 8
SD(B) 22
Ground 1, 19
Table 9. E1 120 Ohm Interface Connections Table 10. E1 75 Ohm Interface Connections
Signal Pin Number Signal Connector
TX Data + 9 TX J206
TX Data - 1 RX J205
RX Data + 11
RX Data - 3
Chassis 7
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL Electronics Inc. Boonton, New Jersey USA
RFL FSU 107460-1
RS - 449
R
X
TX
DATA
SYNC
YEL
PWR
0.59 in.
(1.5 cm)
1.77 in.
(
4.5 cm
)
a. Fiber Service Unit
front view
5.13 in. (13 cm)
4.73 in. (12 cm)
4.13 in. (10.49 cm)
0.31 in. ( 0.80 cm)
diameter typical
8.51 in.
(21.61 cm)
7.34 in.
(18.54 cm)
b. Fiber Service Unit
top view
Figure 12. Mounting Dimensions, RFL 93 FSU Fiber Service Unit (107460-1 to 107460-5 and 108015-1 to 108015-5) Figure 12. Mounting Dimensions, RFL 93 FSU Fiber Service Unit (107460-1 to 107460-5 and 108015-1 to 108015-5)
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 19 (973) 334-3100
Notice
The information in this publication is proprietary
and confidential to RFL Electronics Inc. No part of this
publication may be reproduced or transmitted, in any form or by any means
(electronic, mechanical, photocopy,
recording, or otherwise), or stored in any retrieval system of any nature, unless written permission is given by
RFL Electronics Inc.
This publication has been compiled and checked for
accuracy. The information in this publication does not
constitute a warranty of performance. RFL Electronics Inc. reserves
the right to revise this publication and make
changes to its contents from time to time.
We assume no liability for losses incurred as a result of out-of-date or
incorrect information contained in this publication.
Disposal
When disposing of the equipment, it should be done in strict accordance with all local and national regulations
for the disposal of electrical and electronic equipment. The printed circuit boards should be separated for
recy
cling.
Em
for information on other innovative RFL product
RFL Electronics Inc.
353 Powerville Road Boonton Twp., NJ 07005-9151 USA
Tel: 973.334.3100 Fax: 973.334.3863
www.rflelect.com
Publication No. ID C37.94FSU
Printed in U.S.A.
Revised May 20, 2013
RFL C37.94FSU RFL Electronics Inc.
May 20, 2013 20 (973) 334-3100
Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

RFL 107460-5 Instruction Data

Type
Instruction Data

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI