AXIS A1001 installation with
24 volt lock
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for Relay
2. Depending on your lock type, congure
Lock 1 Relay for
Relay open = Locked for a fail-secure lock
Relay open = Unlocked for a fail-safe lock
3. Wire the RELAY|PWR connector according
to the drawing
>One-door solution with 24 V lock
Lock 1:
12 V
Relay
Relay Relay open = Locked
Relay open = Locked
Relay open = Unlocked
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
-
+
AXIS T8127 60 W Splitter
12/24 V DC
High PoE Switch (802.3at)
24 volt lock
Lock 1
AXIS A1001 installation with
dual electric strikes
Voltage is determined by the power supply voltage out.
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, congure
Lock 2 Relay for
Relay open = Locked for a fail-secure lock
Relay open = Unlocked for a fail-safe lock
4. Wire the LOCK connector and the
RELAY|PWR connector according to
the drawing
2. Congure Lock 2 for Relay
>Simple two-door solution with one door
using external power
Lock 1:
12 V
Relay Relay open = Locked
Relay open = Locked
Relay open = Unlocked
Fail-secure
Lock 2:
12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
Lock 1 Lock 2
12 volt DC
Electric Strike 12/24 volt DC
Electric Strike
PoE Switch
Door Power Supply
12/24+12/24-
AXIS A1001 installation with dual
locks and external power supply
The AXIS A1001 lock output connects to the separate auxiliary
relay power input. 12/24 volts DC+ from a separate door power
supply connects to the C terminal of the slave relay. This transfers
to the NO terminal, pushing power to the lock.
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, congure
Lock 2 Relay for
Relay open = Locked for a fail-secure lock
Relay open = Unlocked for a fail-safe lock
4. Wire the LOCK connector and the
RELAY|PWR connector according to
the drawing
2. Congure Lock 2 for Relay
>Two-door solution with high current locks
>Suggested for use with existing power and
relay
Lock 1:
12 V
Relay Relay open = Locked
Relay open = Locked
Relay open = Unlocked
Fail-secure
Lock 2:
12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
Relay
Lock 1 Lock 2
Electric Strike 12/24 volt DC12/24 volt DC Electric Strike
Door Power Supply
12/24+12/24-
12/24+12/24-
POS+
C
NC
NO
NEG-
C
NC
NO
PoE Switch
AXIS A1001 installation with
dual magnetic locks and
external power supply
The AXIS A1001 lock output connects to the separate auxiliary
relay power input. 12/24 volts DC+ from a separate door power
supply connects to the C terminal of the slave relay. This transfers
to the NO terminal, pushing power to the lock.
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, congure
Lock 2 Relay for
Relay open = Locked for a fail-secure lock
Relay open = Unlocked for a fail-safe lock
4. Wire the LOCK connector and the
RELAY|PWR connector according to
the drawing
2. Congure Lock 2 for Relay
>Two-door solution with high current locks
>Suggested for use with existing power and
relay
Lock 1:
12 V
Relay Relay open = Locked
Relay open = Locked
Relay open = Unlocked
Fail-secure
Lock 2:
12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
12/24 volt
Magnetic Lock
Lock 1
12/24 volt
Magnetic Lock
Lock 2
Door Power Supply
12/24+12/24-
12/24+12/24-
PoE Switch
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
AXIS A1001 installation with
dual integrated locksets
The AXIS A1001 lock output connects to the separate auxiliary
relay power input. 12/24 volts DC+ from a separate door power
supply connects to the C terminal of the slave relay. This transfers
to the NO terminal, pushing power to the lock.
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
> AXIS T8127 60 W Splitter 12/24 V DC
High PoE Splitter
> AXIS T81B22 DC 30 W Midspan 1-port
> AXIS T8133 Midspan 30 W 1-port
> AXIS T8123-E Outdoor Midspan 30 W 1-port
30 Watt Midspan options
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for 12 V and Fail-secure
3. Depending on your lock type, congure
Lock 2 Relay for
Relay open = Locked for a fail-secure lock
Relay open = Unlocked for a fail-safe lock
4.
2. Congure Lock 2 for Relay
Wire the LOCK connector and the
RELAY|PWR connector according to
the drawing
>Two-door solution with high current locks
Lock 1:
12 V
Relay Relay open = Locked
Relay open = Locked
Relay open = Unlocked
Fail-secure
Lock 2:
12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
Integrated
Lockset
Lock 1
Integrated
Lockset
Lock 2
Data + Power Data
30 W Midspan
PoE IN
Splitter
12/24-12/24+
Data OUT
Switch
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
AXIS A1001 installation with
dual external auxiliary devices
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
> AXIS T8127 60 W Splitter 12/24 V DC
High PoE Splitter
> AXIS T81B22 DC 30 W Midspan 1-port
> AXIS T8133 Midspan 30 W 1-port
> AXIS T8123-E Outdoor Midspan 30 W 1-port
30 Watt Midspan options
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for 12 V and Fail-secure
2. Congure Lock 2 for 12 V and Fail-secure
4. Wire the LOCK connector according to
the drawing
>Solution for using relays to control devices
such as HVAC, gates, and other auxiliary
devices
Lock 1:
12 V
Relay
Fail-secure
Lock 2:
12 V
Relay
Fail-secure
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
Data + Power Data
30 W Midspan
PoE IN Data OUT
Splitter
12/24-12/24+
Energy Management
(add this wire for wet contact)
Switch
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
Relay
POS+
C
NC
NO
NEG-
C
NC
NO
AXIS A1001 installation with
dual magnetic locks
Voltage is determined by the POE splitter voltage out.
Adhere to local life safety code in all installations.
Ensure that your power supplies and relays are rated for the intended purposes.
Illustration does not depict cabling for reader, REX, Door monitor, battery backup and UPS.
> AXIS T8127 60 W Splitter 12/24 V DC
High PoE Splitter
> AXIS T81B22 DC 30 W Midspan 1-port
> AXIS T8133 Midspan 30 W 1-port
> AXIS T8123-E Outdoor Midspan 30 W 1-port
30 Watt Midspan options
AXIS Entry Manager
Programming
Application
1. Congure Lock 1 for 12 V and Fail-safe
2. Congure Lock 2 for Relay
3. Congure Lock 2 Relay for
Relay open = Unlocked (fail-safe lock)
4. Wire the LOCK connector and the
RELAY|PWR connector according to
the drawing
>Two-door solution with one 12 V lock and
one 12 or 24 V lock
Lock 1:
12 V
Relay Relay open = Unlocked
Relay open = Locked
Relay open = Unlocked
Fail-safe
Lock 2:
12 V
Relay
READER I/O 1
DOOR IN 1 DOOR IN 2 LOCK
+MIC- +SPK-
AUDIO AUX
A- B+ A- B+ D0 D1 A- B+ A- B+ D0 D1
-12
VIO
3IO
4IO
5IO
6
READER DATA 1 READER DATA 2
DC IN
RELAY | PWR
*REL*- - 12
V24
V
- H1 - H2
- IN1 - IN2 - IN3 - IN4
- +
- 3V IO
1IO
2
READER I/O 2
-12
VIO
7IO
8IO
9IO
10
Data + Power Data
30 W Midspan
PoE IN Data OUT
Splitter
12/24 volt
Magnetic Lock
Lock 2
12 volt
Magnetic Lock
Lock 1
12/24-12/24+
Switch
/