Trove2SS2

Altronix Trove2SS2 Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Altronix Trove2SS2 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
SIGNALING
Trove2SS2
- Trove2 enclosure with Altronix/Lenel-S2 (S2 Security Platform) backplane (TSS2)
TSS2
- Altronix/Lenel-S2 (S2 Security Platform) backplane only
Trove3SS3
- Trove3 enclosure with Altronix/Lenel-S2 (S2 Security Platform) backplane (TSS3)
TSS3
- Altronix/Lenel-S2 (S2 Security Platform) backplane only
Rev. TSS080620
Installing Company: _________________________ Service Rep. Name: __________________________________________
Address: _________________________________________________________ Phone #: _________________________
All registered trademarks are property of their respective owners. More than just power.™
Installation Guide
Access & Power Integration
- 2 - TroveSS Installation Guide
Agency Listings:
UL 294 - 6th edition: Line Security I, Destructive Attack I, Endurance IV, Stand-by Power II*.
*Stand-by Power Level I if no battery is supplied.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme á la norme NMB-003 du Canada.
CE European Conformity.
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having juris-
diction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws; level and secure.
Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install
the three fasteners. Place the enclosure’s upper keyholes over the three upper screws.
Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch(es) (Altronix Model TS112 or equivalent)
in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the
enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch
wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount Altronix/Lenel-S2 (S2 Security Platform) S2-INST mounting kit boards to backplane,
refer to Page 3, 4.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Trove2SS2
Trove2 enclosure with
TSS2 Altronix/Lenel-S2 (S2 Security Platform) backplane.
Includes: tamper switch, cam lock and mounting hardware.
Enclosure Dimensions (H x W x D): 27.25” x 21.75” x 6.5”
(692.2mm x 552.5mm x 165.1mm).
TSS2
Altronix/Lenel-S2 (S2 Security Platform) backplane only
Includes mounting hardware.
Dimensions (H x W x D): 25.375” x 19.375” x 0.3125”
(644.6mm x 492.1mm x 7.9mm).
TSS2 accommodates a combination of the following:
Altronix Modules:
Up to two (2) AL400ULXB2, AL400XB2V, AL600ULXB, AL600XB220,
AL1012ULXB, AL1012XB220, AL1024ULXB2, AL1024XB2V,
eFlow4NB, eFlow4NBV, eFlow6NB, eFlow6NBV, eFlow102NB,
eFlow102NBV, eFlow104NB, eFlow104NBV.
Up to two (2) ACM8(CB), ACMS8(CB), LINQ8ACM(CB).
Up to six (6) ACM4(CB), MOM5, PD4UL(CB), PD8UL(CB),
PDS8(CB), or VR6.
S2:
One (1) S2-INST mounting kit.
Trove3SS3
Trove3 enclosure with
TSS3 Altronix/Lenel-S2 (S2 Security Platform) backplane
Includes: two (2) tamper switches, cam lock and mounting hardware.
Enclosure Dimensions (H x W x D): 36.12” x 30.125” x 7.06”
(917.5mm x 768.1mm x 179.3mm).
TSS3
Altronix/Lenel-S2 (S2 Security Platform) backplane only
Includes mounting hardware.
Dimensions (H x W x D): 34” x 28” x 0.3125”
(863.6mm x 711.2mm x 7.9mm).
TSS3 accommodates a combination of the following:
Altronix Modules:
Up to two (2) AL400ULXB2, AL400XB2V, AL600ULXB, AL600XB220,
AL1012ULXB, AL1012XB220, AL1024ULXB2, AL1024XB2V,
eFlow4NB, eFlow4NBV, eFlow6NB, eFlow6NBV, eFlow102NB,
eFlow102NBV, eFlow104NB, eFlow104NBV.
Up to four (4) ACM8(CB), ACMS8(CB), LINQ8ACM(CB).
Up to eight (8) ACM4(CB), MOM5, PD4UL(CB), PD8UL(CB),
PDS8(CB), or VR6.
S2:
Up to two (2) S2-INST mounting kit.
Overview:
Trove2SS2 and Trove3SS3 accommodate Lenel-S2 (S2 Security Platform) S2-INST bracket(s) supporting Lenel-S2 (S2 Security Platform) controllers
with Altronix power and sub-assemblies for access systems.
Specifications:
16 Gauge backplane and enclosure with ample knockouts for convenient access.
TroveSS Installation Guide - 3 -
Installation Instructions for Altronix Power Supplies and Sub-Assemblies to TSS2:
1. Fasten spacers (provided) into pem configuration (A), (B) or (C) of backplane (Fig. 2, pg. 3).
2. Mount boards to spacers utilizing 5/16” pan head screws (provided) (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Altronix Board Pem Mounting
AL400ULXB2, AL400XB2V, AL600ULXB, AL600XB220, AL1012ULXB, AL1012XB220, AL1024ULXB2, AL1024XB2V,
eFlow4NB, eFlow4NBV, eFlow6NB, eFlow6NBV, eFlow102NB, eFlow102NBV, eFlow104NB, eFlow104NBV A
ACM8, ACM8CB, ACMS8, ACMS8CB, LINQ8ACM, LINQ8ACMCB B
ACM4, ACM4CB, LINQ8PD, LINQ8PDCB, MOM5, PD4UL, PD4ULCB, PD8UL, PD8ULCB, PDS8, PDS8CB, VR6 C
Installation Instructions for S2-INST Bracket to TSS2:
1. Align S2-INST mounting holes with pems on TSS2 (Fig. 2, pg. 3).
2. Attach S2-INST to backplane with lock nuts (provided) (Fig. 2b, pg. 3).
3. Mount backplane to enclosure with hardware.
Pem
Spacer
Altronix
Power Supply or
Sub-Assembly
Backplane
Pan Head
Screw
Pem
Lock nut
S2-INST Bracket
Backplane
S2-INST
Installation Kit for
S2 Network Node
Metal Spacer Placement
A
C
Metal Spacer Placement
A
C
B
C
B
C
CC
Fig. 2a
Fig. 2b
Fig. 2
- 4 - TroveSS Installation Guide
Installation Instructions for Altronix Power Supplies and Sub-Assemblies to TSS3:
1. Fasten spacers (provided) into pem configuration (A), (B) or (C) of backplane (Fig. 3, pg. 4).
2. Mount boards to spacers utilizing 5/16” pan head screws (provided) (Fig. 3a, pg. 4).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Altronix Board Pem Mounting
AL400ULXB2, AL400XB2V, AL600ULXB, AL600XB220, AL1012ULXB, AL1012XB220, AL1024ULXB2, AL1024XB2V,
eFlow4NB, eFlow4NBV, eFlow6NB, eFlow6NBV, eFlow102NB, eFlow102NBV, eFlow104NB, eFlow104NBV A
ACM8, ACM8CB, ACMS8, ACMS8CB, LINQ8ACM, LINQ8ACMCB B
ACM4, ACM4CB, LINQ8PD, LINQ8PDCB, MOM5, PD4UL, PD4ULCB, PD8UL, PD8ULCB, PDS8, PDS8CB, VR6 C
Installation Instructions for S2-INST Bracket to SS3:
1. Align S2-INST mounting holes with pems on TSS3 (Fig. 3, pg. 4).
2. Attach S2-INST to backplane with lock nuts (provided) (Fig. 3b, pg. 4).
3. Mount backplane to enclosure with hardware.
Pem
Spacer
Altronix
Power Supply or
Sub-Assembly
Backplane
Pan Head
Screw
Pem
Lock nut
S2-INST Bracket
Backplane
D
D
S2-INST
Installation Kit For
S2 Network Node
S2-INST
Installation Kit For
S2 Network Node
Metal Spacer Placement
A
Metal Spacer Placement
A
B
C
B
C
B
C
B
C
CC
CC
Fig. 3a
Fig. 3b
Fig. 3
TroveSS Installation Guide - 5 -
2.2” (55.9mm) 2.2” (55.9mm)
19.375” (492.1mm)
12.625” (320.7mm)
8.5” (215.9mm)
16.25” (412.8mm)
1.0” (25.4mm)
1.0” (25.4mm)
9.2” (233.7mm) 9.2” (233.7mm)
7.5” (190.5mm) 7.5” (190.5mm)
25.375” (644.6mm)
0.45” (11.4mm)0.45” (11.4mm)
0.156”
( 3.96mm)
TSS2 Dimensions (H x W x D):
25.375” x 19.375” x 0.3125” (644.6mm x 492.1mm x 7.9mm)
- 6 - TroveSS Installation Guide
Trove2SS2 Enclosure Dimensions (H x W x D approximate):
27.25” x 21.75” x 6.5” (692.2mm x 552.5mm x 165.1mm)
6.75” (171.5mm)8.25” (209.5mm)
8.00” (203.2mm)
2.00” (50.8mm)
2.00” (50.8mm)
1.25” (31.8mm)
1.25” (31.8mm)
5.25” (133.4mm) 5.25” (133.4mm)7.00” (177.8mm)
1.25” (31.8mm)
6.25” (158.8mm) 19.80” (502.9mm)
1.00” (25.4mm)
27” (685.8mm)
1.5”
(38.1mm)
2.00” (50.8mm) 2.00” (50.8mm)
3.5”(88.9mm) 3.5”(88.9mm)
21.50” (546.1mm)
5.25” (133.35mm) 5.25” (133.35mm)
6.25” (158.8mm)
1.25”
(31.8mm)
0.85” (21.6mm)
0.5625” (14.3mm)
2.415” (61.3mm)
0.685” (17.4mm)
1.77”
(45mm)
0.885” (22.5mm)
1.125” (28.3mm)
Knockouts
2.00” (50.8mm) 2.00” (50.8mm)
TroveSS Installation Guide - 7 -
0.45” (11.4mm)
2.5” (63.5mm)
2” (50.8mm)
13.5”
(342.9mm)
13.5”
(342.9mm)
13.5” (342.9mm)
25” (635mm)
0.156”
( 3.96mm)
1.0” (25.4mm)
1.0” (25.4mm)
34” (863.6mm)
28” (711.2mm)
TSS3 Dimensions (H x W x D):
34” x 28” x 0.3125” (863.6mm x 711.2mm x 7.9mm)
- 8 - TroveSS Installation Guide
Trove3SS3 Enclosure Dimensions (H x W x D approximate):
36.12” x 30.125” x 7.06” (917.5mm x 768.1mm x 179.3mm)
G
G
2”
(50.8mm)
8.75” (222.3mm) 8.75” (222.3mm)
8.62” (219mm)
7.06” (179.3mm)
1.25” (31.8mm)
1.25” (31.8mm)
2.00” (50.8mm) 7.12” (222.3mm) 9.5” (241.3mm) 9.5” (241.3mm)
30.12” (768.1mm)
14.01” (355.9mm) 14.01” (355.9mm)
1.25” (31.8mm) 1.55” (39.4mm)
1.78” (45.2mm)
1.25” (31.8mm)
1.07”
(27.2mm)
1.10” (27.9mm)
2” (50.8mm)
10.75” (273.1mm)10.75” (273.1mm) 10.62” (269.8mm)
2.00” (50.8mm)10.75” (273.1mm)10.75” (273.1mm) 10.62” (269.8mm)
36.12” (917.5mm)
33.63” (854.2mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––