FläktGroup CAIRpool Controls Quick start guide

Category
Above ground pool accessories
Type
Quick start guide
CAIR
®
pool – DDC Controller
QUICKGUIDE
Table of Contents CAIRpool – DDC Controller
2FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications
1 Unit function.......................................................................... 3
2 Operation ............................................................................... 4
2.1 Login/authorization levels ................................................................. 4
2.2 Basic operation ................................................................................. 4
2.3 System User Interface ...................................................................... 5
2.3.1 Contact Us ............................................................................ 5
2.3.2 Language .............................................................................. 6
2.3.3 Info ........................................................................................ 6
2.4 Plant ................................................................................................. 7
2.4.1 Flow chart ............................................................................. 7
2.4.2 Refrigeration circuit (if integrated in unit) .............................. 7
2.5 Activate plant ................................................................................... 8
2.6 Setpoints ........................................................................................... 9
2.7 Messages.......................................................................................... 9
2.7.1 Alarms ................................................................................. 10
2.7.2 Archive Alarms .................................................................... 10
2.7.3 Maintenance list .................................................................. 10
CAIRpool – DDC Controller Unit function
FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications3
1 Unit function
CAIRpool units are designed as dehumidifier units for swimming pools.
The different unit models are based on the strategy of dehumidification with outdoor
air. Depending on the swimming pool humidity, different quantities of fresh air are sup-
plied to the swimming pool for dehumidification.
P_X Design The basic model of CAIRpool dehumidifiers for swimming pools comprises a unit
series with highly efficient heat recovery of the P_X series.
P_I Design The units with an inverter-controlled heat pump P_I are based on this model. The heat
pump enables an additional stage of heat recovery for the swimming pool.
Units with a heat pump can contain a pool or fresh-water condenser as an option. In
this case, a part of the heat pump capacity can be released directly to the pool water
or to a water treatment plant (please consider water quality)
P_R Design The P_R series is available to the user as premium solution. The swimming pool is
heated via the inverter-controlled heat pump and can be cooled to nominal tempera-
ture in summer or in case of high external temperatures through a changeover switch.
When the plants are equipped with a heat pump, the heat pump provides the residual
ventilation heat for heating the swimming pool. In winter or at commissioning, a down-
stream heater bank provides a sufficient supply of heat. Furthermore, the reheater coil
regulates the heat function when the heat pump is not in operation or disabled by the
controller because of insufficient quantities of outdoor air.
Units with a heat pump can contain a pool or fresh-water condenser as an option. In
this case, a part of the heat pump capacity can be released directly to the pool water
or to a water treatment plant (please consider water quality)
Operation CAIRpool – DDC Controller
4FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications
2Operation
2.1 Login/authorization levels
Use the startup screen to log into the system.
There are the following authorization levels:
Guest Access to almost all monitors (without change rights)
No password is required
Operator Change rights of relevant setpoints
Manual operation of the drives
Switch unit ON and OFF
Acknowledge faults
Export archive
Default password: "1234"
Enter login password (operator) in the textbox and confirm
by pressing OK (PC: Return key) .
After successful login, press to switch over to the PLANT
operator screen.
With logout or after 15 minutes inactivity, access is reset to
GUEST.
Press without entering a password.
2.2 Basic operation
The fundamental sceen design is explained on the basis of a
monitor screen from the PLANT group.
CAIRpool – DDC Controller Operation
FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications5
Top line: Headline, current time and current date, as well as plant signal lights with the following
assignment:
LED left: display Plant ON (green)
LED middle: plant malfunction (red)
LED right: service request (yellow)
Primary area: Operation and observation of the functional characteristics in accordance with the
selected subsection
Bottom line: Navigation in the main groups with buttons and pictographs. The current group is high-
lighted with a yellow border on the button.
2.3 System User Interface
Press the System User Interface button
The screen System User Interface appears.
All important functions and values are consolidated on the
System User Interface screen.
2.3.1 Contact Us
Press the Contact button.
The CONTACT screen appears.
At need, you can access the data at all times in the Contact
screen.
NOTICE!
During commissioning, fill in the Contact screen
with all important contact data!
Filling out the contact form is possible with "Ser-
vice" access rights.
Operation CAIRpool – DDC Controller
6FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications
2.3.2 Language
Press the Language button.
In the Language screen you can select the desired langu-
age by tapping the appropriate national flag.
2.3.3 Info
Press the Info button.
The INFO screen appears
It shows an overview of the symbols and pictograms used in
the system, along with a short description.
The system itself can be operated intuitively.
CAIRpool – DDC Controller Operation
FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications7
2.4 Plant
2.4.1 Flow chart
Press the Continue button on the startup screen .
The flowchart appears on this central screen.
The plant representation as flowchart contains the following dis-
plays:
Switching state and position of the actuator
Manual mode of individual drives or groups
All measured values and sensor states
State of the filter monitoring
A few calculated values, such as the display of the calcu-
lated enthalpy
The setpoint and actual values of the temperature and air
volume-flow control
Here you can (with the operator authorization level):
Acknowledge faults
Operate manual mode of all drives.
This screen is dynamically structured. Only the units or plant components are shown
that are available in the respective plant (in accordance with the plant configuration).
2.4.2 Refrigeration circuit (if integrated in unit)
Press the Cooling Circuit button in the Plant screen .
The Cooling Circuit screen appears.
The integrated cooling circuit is displayed here. Only the indivi-
dual measured values of the integrated cooling are displayed
here, according to the sensor installation site.
Operation CAIRpool – DDC Controller
8FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications
2.5 Activate plant
In the navigation line, press the button Activate Plant.
The main operating screen of the plant appears for the activation.
Here you can switch the plant ON and OFF in several ways.
Plant
Plant OFF Direct switch-off
Plant IDLE MODE Direct switch-on in idle mode
In the idle mode, the following values are set as default.
* Outdoor-air quantity based on dehumidification demand.
** Lowering the volume flow in the idle mode max. 25% of the nominal air volume
must be approved by the operator or a qualified expert!
Plant POOL MODE Direct switch-on in pool mode
In pool mode, the following values are set as default.
Plant AUTO Plant ON/OFF with internal clock
Designation Default value Unit
Extract-air/room temperature 28 °C
Extract-air room humidity 60 % r.h.
Minimum amount of outside air* 5 %
Supply-air volume flow** 4000 m3/h
Extract air volume flow** 4000 m3/h
Designation Default value Unit
Extract-air/room temperature 30 °C
Extract-air room humidity 55 % r.h.
Minimum amount of outside air* 30 %
Supply-air volume flow** 5000 m3/h
Extract air volume flow** 5000 m3/h
CAIRpool – DDC Controller Operation
FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications9
Short pool mode ON
In short mode, the unit runs with the same settings as in pool mode, but the operating
time is limited by the time setting. When the set time expires, the plant automatically
returns to idle mode.
Plant status
Apart from the plant traffic light (see „Basic operation“ auf Seite 4) the plant status in
the middle of the screen is displayed. The plant status gives information about pool or
idle modes, faults, or maintenance requests.
External switches
The "external switches" function provides a digital ON/OFF switch contact and a free
clock channel. You can activate lights, damper blades, or attractions without any addi-
tional control elements. The contacts can be easily inscribed in the menu.
Please consider the maximum contact load rating of the outputs in the wiring diagram!
2.6 Setpoints
Standard values with reference to VDI 2089 guideline
Air temperature 30°C
Water temperature 28 °C
With relative room air humidity 54 %
2.7 Messages
In the navigation line, press the Messages button.
The Messages screen appears
This group provides the display and confirmation of:
Alarm signals ("alarms")
Operation messages ("events")
maintenance messages ("maintenance list")
Operation CAIRpool – DDC Controller
10 FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications
2.7.1 Alarms
In the Messages screen, press the Alarms button.
The Alarms screen appears
The alarm signals are displayed in a list in this screen. The term
"current" means in this case either still pending or not yet ack-
nowledged.
With the ACKN button, you can acknowledge faults in the plant.
2.7.2 Archive alarms
In the MESSAGES screen, press the Archive AL button.
The screen Archive AL (Alarms) appears.
In this screen, the last 250 alarm signals are displayed in a
list.
2.7.3 Maintenance list
In the Messages screen, select the Maintenance List button.
The Maintenance List screen appears
The maintenance messages are listed in this screen.
CAIRpool – DDC Controller
FläktGroup DC-2015-0116-GB 2020-01/R1 • Subject to modifications11
FläktGroup DC-2015-0116-GB 2020-01/R1 © Copyright 2018 FläktGroup
CAIR
®
POOL DDC CONTROLLER
WWW.FLAKTGROUP.COM
FläktGroup is the European market leader for smart and energy efficient Indoor Air
and Critical Air solutions to support every application area. We offer our customers
innovative technologies, high quality and outstanding performance supported by more
than a century of accumulated industry experience. The widest product range in the
market, and strong market presence in 65 countries worldwide, guarantee that we
are always by your side, ready to deliver Excellence in Solutions.
PRODUCT FUNCTIONS BY FLÄKTGROUP
Air Treatment | Air Movement | Air Diffusion | Air Distribution | Air Filtration
Air Management | Air Conditioning & Heating | Controls | Service
» Learn more on www.flaktgroup.com
or contact one of our office
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

FläktGroup CAIRpool Controls Quick start guide

Category
Above ground pool accessories
Type
Quick start guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI