  • Hello! I am an AI chatbot trained to assist you with the allgood Size 3-6 Concealed Cam Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the minimum power size required for fire/smoke door assemblies as per Approved Document B?
    Can mechanical hold open devices be installed on fire/smoke door assemblies?
    What is the maximum opening angle for the device?
    How often should periodic checks be carried out on the device once it's been correctly fitted?
    What maintenance tasks should be performed on the device?
QUALITY SINCE 1948
T: 020 7387 9951 www.allgood.co.uk1
Recycle responsibly
Allgood size 3-6 concealed cam closer fitting instructions excluding intumescent for non-fire rated doors
9134N
issue 01:03/22
max.120°
max.1400
max.120°
max.1400
Installation and Maintenance Instructions:
Maintenance
1.Once the unit has been correctly fitted it is recommended
that periodic checks (every six months) are carried out to
ensure all fixings are tight and the door closes freely and
positively into the frame, without slamming.
2.A light oil lubricant (non-graphite) should be applied to
the moving joints and exposed pivot points. Hinges
should be maintained in accordance with the
manufacturer’s instructions.
After Installation
1.When the closer operates to close the door from its maximum
opening position, it should ensure the lock latchbolt and any
seals are overcome and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt resting against
the strike, release the door to ensure the leaf fully closes into its
frame.
3.It is recommended to fit door stops to prevent the door opening
beyond its limits.
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as
required by Approved Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid
damage through over adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled
under high load, therefore, tampering with the mechanism is to be strictly avoided.
2
9
1
4
3
120
°-0°
7
3
10°-0°
8
1
3
3
3
2
3
5
5
max. 10Nm
5
max. 8Nm
8
1400mm
Max
120Kg
EN6
1250mm
Max
100Kg
EN5
1100mm
Max
80Kg
EN4
950mm
Max
60Kg
EN3
6
≥EN3
EN4EN3
3
EN6EN5
8 13
0
*Factory Preset
175
70
9
20
352
9
334
300X40
3
440
145
(464)
(133)
96
165
(133)
145
(464)
200 200
440
70 500
352
9334
20
==
175
145 440
12
3
96
12
300X40
(133) (464)
165 200
(133)
145
(464)
200
440
31
max.16
20
55
12
40
12
40
min. 5
52
3
29
min. 3
20
31
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
1
1
2
2
2
4
4
End Cap
4
3
3
3
max.120°
max.1400
max.120°
max.1400
Installation and Maintenance Instructions:
Maintenance
1.Once the unit has been correctly fitted it is recommended
that periodic checks (every six months) are carried out to
ensure all fixings are tight and the door closes freely and
positively into the frame, without slamming.
2.A light oil lubricant (non-graphite) should be applied to
the moving joints and exposed pivot points. Hinges
should be maintained in accordance with the
manufacturer’s instructions.
After Installation
1.When the closer operates to close the door from its maximum
opening position, it should ensure the lock latchbolt and any
seals are overcome and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt resting against
the strike, release the door to ensure the leaf fully closes into its
frame.
3.It is recommended to fit door stops to prevent the door opening
beyond its limits.
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as
required by Approved Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid
damage through over adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled
under high load, therefore, tampering with the mechanism is to be strictly avoided.
2
9
1
4
3
120°-0°
7
3
10°-0°
8
1
3
3
3
2
3
5
5
max. 10Nm
5
max. 8Nm
8
1400mm
Max
120Kg
EN6
1250mm
Max
100Kg
EN5
1100mm
Max
80Kg
EN4
950mm
Max
60Kg
EN3
6
≥EN3
EN4EN3
3
EN6EN5
8 13
0
*Factory Preset
175
70
9
20
352
9
334
300X40
3
440
145
(464)
(133)
96
165
(133)
145
(464)
200 200
440
70 500
352
9 334
20
==
175
145 440
12
3
96
12
300X40
(133) (464)
165 200
(133)
145
(464)
200
440
31
max.16
20
55
12
40
12
40
min. 5
523
29
min. 3
20
31
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
1
1
2
2
2
4
4
End Cap
4
3
3
3
QUALITY SINCE 1948
T: 020 7387 9951 www.allgood.co.uk2
Recycle responsibly
Allgood size 3-6 concealed cam closer fitting instructions including intumescent for fire rated doors
9134N
issue 02:02/22
Installation and Maintenance Instructions:
Maintenance
1.Once the unit has been correctly fitted it is recommended
that periodic checks (every six months) are carried out to
ensure all fixings are tight and the door closes freely and
positively into the frame, without slamming.
2.A light oil lubricant (non-graphite) should be applied to
the moving joints and exposed pivot points. Hinges
should be maintained in accordance with the
manufacturer’s instructions.
After Installation
1.When the closer operates to close the door from its maximum
opening position, it should ensure the lock latchbolt and any
seals are overcome and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt resting against
the strike, release the door to ensure the leaf fully closes into its
frame.
3.It is recommended to fit door stops to prevent the door opening
beyond its limits.
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as
required by Approved Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid
damage through over adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled
under high load, therefore, tampering with the mechanism is to be strictly avoided.
2
9
4
3
120
°-0°
7
3
10°-0°
8
1
3
3
3
2
3
5
5
max. 10Nm
5
max. 8Nm
8
1400mm
Max
120Kg
EN6
1250mm
Max
100Kg
EN5
1100mm
Max
80Kg
EN4
950mm
Max
60Kg
EN3
6
≥EN3
EN4EN3
3
EN6EN5
8 13
0
*Factory Preset
max.1400
max.120°
max.1100
max.120°
143 444
12
5
96
12
300X45
(133) (464)
70
9
352
334
175
20
9
300
165 200
(133)
143
(464)
200
444
300X45
3
5
444
143
(464)
(133)
96
165
(133)
143
(464)
200 200
444
70 500
352
9334
20
==
175
300
22
12
36
max.16
57
45
31
45
3
12
54
min. 5
min. 3
22
36
5
444 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
444 &143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
1
1
2
2
2
4
4
End Cap
4
3
3
3
Installation and Maintenance Instructions:
Maintenance
1.Once the unit has been correctly fitted it is recommended
that periodic checks (every six months) are carried out to
ensure all fixings are tight and the door closes freely and
positively into the frame, without slamming.
2.A light oil lubricant (non-graphite) should be applied to
the moving joints and exposed pivot points. Hinges
should be maintained in accordance with the
manufacturer’s instructions.
After Installation
1.When the closer operates to close the door from its maximum
opening position, it should ensure the lock latchbolt and any
seals are overcome and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt resting against
the strike, release the door to ensure the leaf fully closes into its
frame.
3.It is recommended to fit door stops to prevent the door opening
beyond its limits.
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as
required by Approved Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid
damage through over adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled
under high load, therefore, tampering with the mechanism is to be strictly avoided.
2
9
1
4
3
120°-0°
7
3
10°-0°
8
1
3
3
3
2
3
5
5
max. 10Nm
5
max. 8Nm
8
1400mm
Max
120Kg
EN6
1250mm
Max
100Kg
EN5
1100mm
Max
80Kg
EN4
950mm
Max
60Kg
EN3
6
≥EN3
EN4EN3
3
EN6EN5
8 13
0
*Factory Preset
max.1400
max.120°
max.1100
max.120°
143 444
12
5
96
12
300X45
(133) (464)
70
9
352
334
175
20
9
300
165 200
(133)
143
(464)
200
444
300X45
3
5
444
143
(464)
(133)
96
165
(133)
143
(464)
200 200
444
70 500
352
9 334
20
==
175
300
22
12
36
max.16
57
45
31
45
3
12
54
min. 5
min. 3
22
36
5
444 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
444 &143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
1
1
2
2
2
4
4
End Cap
4
3
3
3
6-3
3 8 11 3
2812-CPR-AD7895
APPROVED
PRODUCT
CF 6022
ALLGOOD PLC
63-83 BREARLEY STREET
BIRMINGHAM
B19 3NT
EN 1154: 1996/A1:2002/AC:2006
/