Allgood size 2-4 concealed cam closer fitting instructions excluding intumescent for non-fire doors
9133N
issue 01:03/22
After Installation
1.When the closer operates to close the door from
its maximum opening position, it should ensure
the lock latchbolt and any seals are overcome
and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt
resting against the strike, release the door to
ensure the leaf fully closes into its frame.
3.It is recommended to fit door stops to prevent the
door opening beyond its limits.
Maintenance
1.Once the unit has been correctly fitted it is
recommended that periodic checks (every six
months) are carried out to ensure all fixings are
tight and the door closes freely and positively into
the frame, without slamming.
2.A light oil lubricant (non-graphite) should be
applied to the moving joints and exposed pivot
points. Hinges should be maintained in
accordance with the manufacturer’s instructions.
Installation and Maintenance Instructions:
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as required by Approved
Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid damage through over
adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled under high load, therefore,
tampering with the mechanism is to be strictly avoided.
max.120°
max.1100
73 500
338
9 320
20
175
153 424
145 440
(133) (464)
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap. R8
286x3399
3
8.5
440
145
(464)
(133)
17
3
8.5
33
Ø31
42
4
23
max.16
153 424
145 440
(133) (464)
73 500
338
9320
20
==
175
max.120°
max.1100
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
R8
(133) (464)
145 440
8.5
3
99 286x33
8.5
2.5
42
46
42
46
33
Ø31
max.16
8.5
42 4
23
17
3
20
2
3
3
4
4
1
1
1
2
2
90°
1
4
With end cap
4
120°-7°
7
7°-0°
8
5
5
5
max. 10Nm
max. 8Nm
8
6
≥EN3
Factory preset
EN3 EN4EN2
x0 x5x5
850mm
Max
40Kg
950mm
Max
60Kg
1100mm
Max
80Kg
3
3
2
1
3
3
3
2
30°
After Installation
1.When the closer operates to close the door from
its maximum opening position, it should ensure
the lock latchbolt and any seals are overcome
and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt
resting against the strike, release the door to
ensure the leaf fully closes into its frame.
3.It is recommended to fit door stops to prevent the
door opening beyond its limits.
Maintenance
1.Once the unit has been correctly fitted it is
recommended that periodic checks (every six
months) are carried out to ensure all fixings are
tight and the door closes freely and positively into
the frame, without slamming.
2.A light oil lubricant (non-graphite) should be
applied to the moving joints and exposed pivot
points. Hinges should be maintained in
accordance with the manufacturer’s instructions.
Installation and Maintenance Instructions:
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as required by Approved
Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid damage through over
adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled under high load, therefore,
tampering with the mechanism is to be strictly avoided.
max.120°
max.1100
73 500
338
9 320
20
175
153 424
145 440
(133) (464)
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap. R8
286x3399
3
8.5
440
145
(464)
(133)
17
3
8.5
33
Ø31
42
4
23
max.16
153 424
145 440
(133) (464)
73 500
338
9 320
20
==
175
max.120°
max.1100
440 & 145
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
R8
(133) (464)
145 440
8.5
3
99 286x33
8.5
2.5
42
46
42
46
33
Ø31
max.16
8.5
42 4
23
17
3
20
2
3
3
4
4
1
1
1
2
2
90°
1
4
With end cap
4
120°-7°
7
7°-0°
8
5
5
5
max. 10Nm
max. 8Nm
8
6
≥EN3
Factory preset
EN3 EN4EN2
x0 x5x5
850mm
Max
40Kg
950mm
Max
60Kg
1100mm
Max
80Kg
3
3
2
1
3
3
3
2
30°
QUALITY SINCE 1948
T: 020 7387 9951 www.allgood.co.uk2
Recycle responsibly
Allgood size 2-4 concealed cam closer fitting instructions including intumescent for fire rated doors
9133N
issue 01:03/22
42
44
max.120°
max.1100
440 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
444
143
(464)
(133)
8.5
5
28
153 424
444
(133) (464)
143
R8
38
338
9320
175
20
73 500
= =
286x3399
Ø31
max.16
8.5
3
38
44 2
28
19
22.5
max.120°
max.1100
440 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
28
153 424
R8
444
(133) (464)
338
9320
175
282
38
20
==
73 500
(133)
143
(464)
444
286x38
8.5
10.5
99
42
44
19
143
8.5
38
28
19
442 3
max.16
Ø31
After Installation
1.When the closer operates to close the door from
its maximum opening position, it should ensure
the lock latchbolt and any seals are overcome
and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt
resting against the strike, release the door to
ensure the leaf fully closes into its frame.
3.It is recommended to fit door stops to prevent the
door opening beyond its limits.
Maintenance
1.Once the unit has been correctly fitted it is
recommended that periodic checks (every six
months) are carried out to ensure all fixings are
tight and the door closes freely and positively into
the frame, without slamming.
2.A light oil lubricant (non-graphite) should be
applied to the moving joints and exposed pivot
points. Hinges should be maintained in
accordance with the manufacturer’s instructions.
Installation and Maintenance Instructions:
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as required by Approved
Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid damage through over
adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled under high load, therefore,
tampering with the mechanism is to be strictly avoided.
2
3
3
4
4
1
1
1
2
2
90°
1
4
With end cap
4
120°-7°
7
7°-0°
8
5
5
5
max. 10Nm
max. 8Nm
8
6
≥EN3
Factory preset
EN3 EN4EN2
x0 x5x5
850mm
Max
40Kg
950mm
Max
60Kg
1100mm
Max
80Kg
3
3
2
1
3
3
3
2
30°
42
44
max.120°
max.1100
440 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
444
143
(464)
(133)
8.5
5
28
153 424
444
(133) (464)
143
R8
38
338
9 320
175
20
73 500
= =
286x3399
Ø31
max.16
8.5
3
38
44 2
28
19
22.5
max.120°
max.1100
440 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
28
153 424
R8
444
(133) (464)
338
9 320
175
282
38
20
==
73 500
(133)
143
(464)
444
286x38
8.5
10.5
99
42
44
19
143
8.5
38
28
19
442 3
max.16
Ø31
After Installation
1.When the closer operates to close the door from
its maximum opening position, it should ensure
the lock latchbolt and any seals are overcome
and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt
resting against the strike, release the door to
ensure the leaf fully closes into its frame.
3.It is recommended to fit door stops to prevent the
door opening beyond its limits.
Maintenance
1.Once the unit has been correctly fitted it is
recommended that periodic checks (every six
months) are carried out to ensure all fixings are
tight and the door closes freely and positively into
the frame, without slamming.
2.A light oil lubricant (non-graphite) should be
applied to the moving joints and exposed pivot
points. Hinges should be maintained in
accordance with the manufacturer’s instructions.
Installation and Maintenance Instructions:
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as required by Approved
Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid damage through over
adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled under high load, therefore,
tampering with the mechanism is to be strictly avoided.
2
3
3
4
4
1
1
1
2
2
90°
4
With end cap
4
120°-7°
7
7°-0°
8
5
5
5
max. 10Nm
max. 8Nm
8
6
≥EN3
Factory preset
EN3 EN4EN2
x0 x5x5
850mm
Max
40Kg
950mm
Max
60Kg
1100mm
Max
80Kg
3
3
2
1
3
3
3
2
30°
42
44
max.120°
max.1100
440 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
444
143
(464)
(133)
8.5
5
28
153 424
444
(133) (464)
143
R8
38
338
9 320
175
20
73 500
= =
286x3399
Ø31
max.16
8.5
3
38
44 2
28
19
22.5
max.120°
max.1100
440 & 143
Illustration shows without end cap.
(464)&(133)
Illustration shows with end cap.
28
153 424
R8
444
(133) (464)
338
9 320
175
282
38
20
==
73 500
(133)
143
(464)
444
286x38
8.5
10.5
99
42
44
19
143
8.5
38
28
19
442 3
max.16
Ø31
After Installation
1.When the closer operates to close the door from
its maximum opening position, it should ensure
the lock latchbolt and any seals are overcome
and the leaf returned into its frame.
2.When the door is slightly open and the latch bolt
resting against the strike, release the door to
ensure the leaf fully closes into its frame.
3.It is recommended to fit door stops to prevent the
door opening beyond its limits.
Maintenance
1.Once the unit has been correctly fitted it is
recommended that periodic checks (every six
months) are carried out to ensure all fixings are
tight and the door closes freely and positively into
the frame, without slamming.
2.A light oil lubricant (non-graphite) should be
applied to the moving joints and exposed pivot
points. Hinges should be maintained in
accordance with the manufacturer’s instructions.
Installation and Maintenance Instructions:
Warning
1.Please note the minimum power size requirement for fire / smoke door assemblies is 3 as required by Approved
Document B.
2.Do not install mechanical hold open devices on fire / smoke door assemblies.
3.Take care not to exceed the maximum opening angle as detailed above.
4.Care and attention must be taken when adjusting any of the units control valves to avoid damage through over
adjustment.
5.All Allgood Door Closer units are sealed for life and the internal components assembled under high load, therefore,
tampering with the mechanism is to be strictly avoided.
2
3
3
4
4
1
1
1
2
2
90°
4
With end cap
4
120°-7°
7
7°-0°
8
5
5
5
max. 10Nm
max. 8Nm
8
6
≥EN3
Factory preset
EN3 EN4EN2
x0 x5x5
850mm
Max
40Kg
950mm
Max
60Kg
1100mm
Max
80Kg
3
3
2
1
3
3
3
2
30°
4-2
3 8 11 3
2812-CPR-AD7894
APPROVED
PRODUCT
CF 6022
ALLGOOD PLC
63-83 BREARLEY STREET
BIRMINGHAM
B19 3NT
EN 1154: 1996/A1:2002/AC:2006
/