Fujitsu AUXB24LALH Installation guide

Category
Split-system air conditioners
Type
Installation guide

This manual is also suitable for

PART NO. 9371022192-04
English
INSTALLATION MANUAL
VRF SYSTEM
INDOOR UNIT
Compact Cassette Type
For authorized service personnel only.
Contents
1. SAFETY PRECAUTIONS ............................................. 2
2. ABOUT THE UNIT
2.1. Precautions for using the R410A refrigerant .......... 2
2.2. Special tool for R410A ............................................ 2
2.3. Accessories ............................................................ 2
2.4. Optional parts ......................................................... 3
3. INSTALLATION WORK
3.1. Selecting an installation location ............................ 3
3.2. Installation dimensions ........................................... 4
3.3. Discharge direction setting ..................................... 4
3.4. Installing the unit .................................................... 5
4.
PIPE INSTALLATION
4.1. Selecting the pipe material ..................................... 6
4.2. Pipe requirement .................................................... 6
4.3. Flare connection (pipe connection) ........................ 6
4.4. Installing heat insulation ......................................... 7
5. INSTALLING DRAIN PIPES .......................................... 7
6. ELECTRICAL WIRING
6.1. Electrical requirement ............................................ 9
6.2. Wiring method ...................................................... 10
6.3. Unit wiring ............................................................ 10
6.4. Connection of wiring ............................................. 12
6.5. External input and external output
(Optional parts) .................................................... 13
7. FIELD SETTING
7.1. Setting the address .............................................. 15
7.2. Custom code setting ............................................ 16
7.3. Function setting .................................................... 17
8. DECORATION PANEL INSTALLATION
8.1. Remove the intake grille ....................................... 18
8.2. Install panel to indoor unit .................................... 19
8.3. Attach the intake grille .......................................... 19
9. TEST OPERATION
9.1.
Test operation using PCB (Outdoor unit) ....................19
9.2.
Test operation using Remote Controller ......................19
10. CHECK LIST ............................................................... 20
11. ERROR CODES ......................................................... 20
En-2
1. SAFETY PRECAUTIONS
Be sure to read this Manual thoroughly before installation.
The warnings and precautions indicated in this Manual
contain important information pertaining to your safety. Be
sure to observe them.
Hand this Manual, together with the Operating Manual to
the customer.
Request the customer to keep them on hand for future
use, such as for relocating or repairing the unit.
WARNING!
This mark indicates procedures which,
if improperly performed, might lead to
the death or serious injury of the user.
• Request your dealer or a professional installer to install
the unit in accordance with this Manual.
An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or re.
If the unit is instruction in disregard of the instructions
in the Installation Manual, it will void the manufacturers
warranty.
Do not turn ON the power until all work has been
completed.
Turning ON the power before the work is completed can
cause serious accidents such as electric shock or re.
If refrigerant leaks while work is being carried out, ventilate
the area.
If the refrigerant comes in contact with a ame, it produces
a toxic gas.
• Installation work must be performed in accordance with
national wiring standards by authorized personnel only.
Except for EMERGENCY, never turn off main as well as
sub breaker of the indoor units during operation. It will
cause compressor failure as well as water leakage. First,
stop the indoor unit by operating the control unit, converter
or external input device and then cut the breaker.
Make sure to operate through the control unit, converter
or external input device.
When the breaker is designed, locate it at a place where
the users cannot start and stop in the daily work.
CAUTION!
This mark indicates procedures which,
if improperly performed, might possibly
result in personal harm to the user, or
damage to property.
2. ABOUT THE UNIT
2.1. Precautions for using the R410A
refrigerant
WARNING
Do not introduce any substance other than the prescribed
refrigerant into the refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the
refrigeration cycle will become abnormally high and cause the
piping to rupture.
• If there is a refrigerant leakage, make sure that it does not
exceed the concentration limit.
If a refrigerant leakage exceeds the concentration limit, it can
lead to accidents such as oxygen starvation.
• Do not touch refrigerant that has leaked from the refrigerant
pipe connections or other area. Touching the refrigerant directly
can cause frostbite.
If a refrigerant leakage occurs during operation, immediately
vacate the premises and thoroughly ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic
gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses the R410A refrigerant, use dedicated
tools and piping materials that have been manufactured
speci cally for R410A use.
Because the pressure of the R410A refrigerant is approximately
1.6 times higher than the R22, failure to use dedicated piping
material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water
leakage, electric shock, or re.
Tool name Contents of change
Gauge
manifold
Pressure is huge and cannot be
measured with a conventional gauge.
To prevent erroneous mixing of other
refrigerants, the diameter of each port
has been changed.
It is recommended to use a gauge
manifold with a high pressure display
range –0.1 to 5.3 MPa and a low
pressure display range –0.1 to 3.8 MPa.
Charging hose
To increase pressure resistance, the
hose material and base size were
changed.
Vacuum pump
A conventional vacuum pump can be
used by installing a vacuum pump
adapter.
Be sure that the pump oil does not
backflow into the system. Use one
capable for vacuum suction of
–100.7 kPa (5 Torr, –755 mmHg).
Gas leakage
detector
Special gas leakage detector for HFC
refrigerant R410A.
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by
the manufacturer or other prescribed parts.
The use of non-prescribed parts can cause serious accidents
such as the unit to fall, water leakage, electric shock, or re.
• The following installation parts are furnished. Use them as
required.
• Keep the Installation Manual in a safe place and do not discard
any other accessories until the installation work has been
completed.
En-3
Do not discard any accessories needed for installation
until the installation work has been completed.
Name and Shape Q’ty Application
Operating Manual
1
Installation Manual
1
(This book)
Binder (Large)
4
For fixing the
connection pipe (Large
and Small)
Binder (Medium)
3
For transmission and
remote controller cable
binding.
Coupler heat
insulation
(Small)
1
For indoor side pipe
joint (Small)
Coupler heat
insulation
(Large)
1
For indoor side pipe
joint (Large)
Special nut A
(Large flange)
4
For installing indoor unit
Special nut B
(Small flange)
4
For installing indoor unit
Template
(Carton top)
1
For cealing openings
cutting
Also used as packing
Drain hose
1
For installing drain pipe
VP25 (O.D.32, I.D.25)
Hose Band
1
For installing drain hose
Drain hose insulation
1
For installing drain pipe
DECORATION PANEL ACCESSORIES
Name and Shape Q’ty Application
Connector cover
1
For covering connector
Tapping screw
(M5 × 12mm)
4
For mounting decoration
panel
Tapping screw
(M4 × 12mm)
1
For mounting connector
cover
2.4. Optional parts
The following options are available.
• External output wire (P/N 9379529006)
• External input (voltage) wire (P/N 9368779016)
• External input (no voltage) wire (P/N 9368779009)
• Insulation kit for high humidity (UTZ-KXGC)
Install when the condition under the roof is over 80% in
humidity and over 30°C in temperature.
3. INSTALLATION WORK
Especially, the installation place is very important for the split type
air conditioner because it is very dif cult to move from place to
place after the rst installation.
3.1. Selecting an installation location
WARNING
Select installation locations that can properly support the weight
of the indoor. Install the units securely so that they do not topple
or fall.
En-4
CAUTION
Do not install the unit in the following areas:
Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fall or the
unit to leak water.
• Area lled with mineral oil or containing a large amount of
splashed oil or steam, such as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or the
unit to leak water.
Area that generates substances that adversely affect the
equipment, such as sulfuric gas, chlorine gas, acid, or
alkali.
It will cause the copper pipes and brazed joints to corrode,
which can cause refrigerant leakage.
Area that can cause combustible gas to leak, contains
suspended carbon fibers or flammable dust, or volatile
in ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a re.
Area where animals may urinate on the unit or ammonia may
be generated.
Do not use the unit for special purposes, such as storing food,
raising animals, growing plants, or preserving precision devices
or art objects.
It can degrade the quality of the preserved or stored objects.
• Do not install where there is the danger of combustible gas
leakage.
• Do not install the unit near a source of heat, steam, or ammable
gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, outdoor unit, power supply cable,
transmission cable, and remote controller cable at least 1 m
away from a television or radio receivers. The purpose of this
is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still
receive noise under some signal conditions.)
• If children under 10 years old may approach the unit, take
preventive measures so that they cannot reach the unit.
• Use the “Insulation kit for high humidity” (option), when the
condition under the roof is over 80% in humidity and over 30°C
in temperature. Otherwise, there is a risk of condensation on
the ceiling.
• Decide the mounting position with the customer as
follows:
(1) Install the indoor unit on a place having a suf cient strength
so that it withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air
should be able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly
throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the connection pipe can be easily
installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not ampli ed.
(9) Take servicing, etc., into consideration and leave the spaces.
Also install the unit where the lter can be removed.
3.2. Installation dimensions
Leave the space speci ed in Fig. A so that the air from the
blower will cover the entire room.
Install the indoor unit on a place having a suf cient strength so
that it withstands against the weight of the indoor unit.
A place from where drainage can be extracted outdoors easily.
WARNING
Never install in a room where there is the potential of leaking
ammable gas. A spark could ignite the gas and cause an
explosion or re.
Avoid installing in a location with high temperature.
The blower direction can be set for 2 directions or 3 directions.
When using 2-direction or 3-direction blower, follow Fig. B for
the blower direction and space.
This product can be installed at a height of up to 3.0 m.
Perform the Function Setting on the remote controller in
accordance with the installed height.
Fig. A
Obstruction
H
1,800mm or more
1,000 mm
or more
1,000 mm
or more
Floor
Strong and durable ceiling
262 mm
or more
H(The maximum height from floor to ceiling)(mm)
Model name
AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24
Standard
mode
2,700 2,700 2,700 2,700 2,700 2,700
High Ceiling
mode
- - 3,000 3,000 3,000 3,000
3.3. Discharge direction setting
The discharge direction can be selected as shown below.
Fig. B
(4 directions)
(3 directions)
100 mm or more
Piping position
En-5
* Select the most appropriate air ow direction from 3 or
4 directions according to the shape of the room and the
installation position.
* When changing the number of outlets, we recommend using
the optional AIR OUTLET SHUTTER PLATE KIT to close the
outlet.
* For the speci c closing pattern, please refer to the attached
AIR OUTLET SHUTTER PLATE KIT’S MANUAL. (Do so
before installing the decorative panel as it will be installed on
the body.)
3.4. Installing the unit
Install the air conditioner as follows.
INDOOR UNIT INSTALLATION
(1) Make the holes for installing in the ceiling (Fig. D).
(2)
Install the hanging bolts (M10), refer to the position in Fig. C.
(3) Install special nut A, then special nut B onto the hanging bolt
(Fig. D).
(4) Raise the body and mount its hooks onto the hanging bolt
between the special nuts.
(5) Turn special nut B to adjust the height of the body.
(6) Be sure to leave service access for future service at the
designated position.
Fig. C
530 mm (Hanging bolt position)
540 mm (Hanging bolt position)
570 mm (Indoor unit)
580 – 660 mm (Cealing openings)
700 mm (Decoration Panel)
135 mm 250 mm
150 ~ 200 mm
Min. 450 mm
Service access
75 mm
Min. 450 mm
Fig. D
Drain pipe (O.D. ø25.4)
40 mm 99 mm
102 mm
146 mm
245 mm
30 mm
262 mm
30 mm
58 mm
123 mm
Ceiling
Control box
Liquid pipe
Gas pipe
40 mm
Special nut A
Special nut B
Hook
Hanging bolt
30 mm
or more
After
installing the
body, tighten
the nuts.
19 mm
Ceiling
Leveling
Using a level, or vinyl hose lled with water, ne adjust so that
the body is level.
Inclined installation so as the drain pipe side is higher may
cause a malfunction of the oat switch, and may cause water
leakage.
Vinyl hoses
Drain pipe
WARNING
Install the air conditioner in a location which can withstand a
load do at least 5 times the weight of the main unit and which will
not amplify sound or vibration. If the installation location is not
strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that
the unit will come loose. Please take care.
When fastening the hangers, make the bolt positions
uniform.
• Perform nal tightening by tightening the double nut rmly. The
product may fall if not installed properly.
Using a level, or vinyl hose lled with water, ne adjust so that
the body is level.
En-6
4. PIPE INSTALLATION
CAUTION
• Be more careful that foreign matter (oil, water, etc.) does
not enter the piping than with refrigerant R410A models.
Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
• While welding the pipes, be sure to blow dry nitrogen gas
through them.
4.1. Selecting the pipe material
CAUTION
Do not use existing pipes.
Use pipes that have clean external and internal sides without
any contamination which may cause trouble during use, such
as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than
40 mg/10 m.
• Do not use copper pipes that have a collapsed, deformed,
or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become
blocked with contaminants.
Improper pipe selection will degrade performance. As an air
conditioner using R410A incurs pressure higher than when
using conventional refrigerant, it is necessary to choose
adequate materials.
Thicknesses of copper pipes used with R410A are as
shown in the table.
Never use copper pipes thinner than those indicated in the
table even if they are available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in.)] Thickness [mm]
6.35 (1/4) 0.80
9.52 (3/8) 0.80
12.70 (1/2) 0.80
15.88 (5/8) 1.00
19.05 (3/4) 1.20
4.2. Pipe requirement
CAUTION
Refer to the Installation Manual of the outdoor unit for
description of the length of connecting pipe or for difference
of its elevation.
Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C.
(Reverse cycle model only)
In addition, if the humidity level at the installation location
of the refrigerant piping is expected to exceed 70 %, install
heat insulation around the refrigerant piping. If the expected
humidity level is 70-80 %, use heat insulation that is 15 mm or
thicker and if the expected humidity exceeds 80 %, use heat
insulation that is 20 mm or thicker. If heat insulation is used
that is not as thick as speci ed, condensation may form on
the surface of the insulation. In addition, use heat insulation
with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
4.3. Flare connection (pipe connection)
WARNING
• Tighten the are nuts with a torque wrench using the speci ed
tightening method. Otherwise, the are nuts could break after
a prolonged period, causing refrigerant to leak and generate
a hazardous gas if the refrigerant comes into contact with a
ame.
4.3.1. Flaring
Use special pipe cutter and are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe
cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe
and remove any burrs.
(3) Insert the are nut (always use the are nut attached to the
indoor and outdoor units respectively) onto the pipe and
perform the are processing with a are tool. Use the special
R410A are tool, or the conventional are tool. Leakage of
refrigerant may result if other are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust,
dirt, or water from entering the pipes.
Pipe outside
diameter
[mm (in.)]
Dimension A [mm]
Dimension B
-
0
0.4
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional are tools to are R410A pipes, the
dimension A should be approximately 0.5 mm more than indicated
in the table (for aring with R410A are tools) to achieve the
speci ed aring. Use a thickness gauge to measure the dimension
A.
En-7
Width across
flats
Pipe outside
diameter [mm (in.)]
Width across flats
of Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
4.3.2. Bending pipes
If pipes are shaped by hand, be careful not to collapse them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bend or stretched, the material will
harden, making it dif cult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
4.3.3. Pipe connection
When the are nut is tightened properly by your hand, hold the
body side coupling with a separate spanner, then tighten with a
torque wrench. (See the table below for the are nut tightening
torques.)
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle
with the pipe, in order to tighten the are nut correctly.
• Tighten the are nuts with a torque wrench using the speci ed
tightening method. Otherwise, the are nuts could break after
a prolonged period, causing refrigerant to leak and generate
a hazardous gas if the refrigerant comes into contact with a
ame.
Flare nut [mm (in.)]
Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
4.4. Installing heat insulation
Install the heat insulation material after performing a refrigerant
leak check (see the Installation Manual for the outdoor unit for
details).
COUPLER HEAT INSULATION
Insulate by the coupler heat insulation (Accessories) around
the gas pipe and liquid pipe of indoor side.
After installing the coupler heat insulation, wrap both end with
vinyl tape so that there is no gap.
• After af xing the coupler heat insulation, secure it with 2 bin-
ders (large), one on each end of the insulation.
Make sure that the binders overlap the heat insulation pipe.
Coupler heat
insulation
(Accessories)
Binder (Large)
(Accessories)
Heat insulation
Cover this portion with
heat insulation.
CAUTION
After checking for gas leaks (refer to the Installation Manual
of the outdoor unit), perform this section.
Install heat insulation around both the large (gas) and small
(liquid) pipes. Failure to do so may cause water leaks.
5. INSTALLING DRAIN PIPES
Install the drain pipe with downward gradient (1/100 to 1/50)
and so there are no rises or traps in the pipe. Unsmooth
draining caused by accumulated water ow in the pipe may
cause clogged drain.
Use general hard polyvinyl chloride pipe (VP25) [outside
diameter 32 mm].
When the pipe is long, install supporters.
Do not perform air bleeding. Drainage may be blown out.
Always heat insulate the indoor side of the drain pipe.
If it is impossible to have suf cient gradient of pipe, perform
drain lift-up.
Pipe size
Drain pipe VP25 (O.D. 32 mm)
Hanging ttings
VP25 (O.D. 32 mm)
Downward gradient 1/100 to 1/50
1.5 to 2 m
Rise
PROHIBITED:
Trap Air bleeding
When lifting up drain:
Height of inclined pipe should be less than 700 mm from the
ceiling. A rise dimension over this range will cause leakage.
Lift up the pipe vertically at the position of 300 mm or less from
the unit.
En-8
VP25 (O.D. 32 mm)
local arrangement
VP30 (O.D. 38 mm) or more
Downward gradient 1/100 to 1/50
Downward gradient
1/100 to 1/50
300 mm or less
700 mm or less
700 mm or less
Horizontal or
upward gradient
WARNING
• Do not insert the drain piping into the sewer where sulfurous
gas occurs. (Heat exchange erosion may occur)
Insulate the parts properly so that water will not drip from the
connection parts.
Check for proper drainage after the construction by using the
visible portion of transparent drain port and the drain piping
nal outlet on the body.
CAUTION
Do not apply adhesive agent on the drain port of the body.
(Use the attached drain hose and connect the drain piping)
Working procedure
(1) Install the attached drain hose to the drain port of the body.
Install the hose band from the top of the hose within the
graphic display area.
(2) Use vinyl adhesive agent to glue the drain piping (PVC pipe
VP25) which is prepared on site or elbow socket.
(Apply color adhesive agent evenly until the gauge line and
seal)
(3) Check the drainage. (See separate diagram)
(4) Install the heat insulation.
(5) Use the attached heat insulation to insulate the drain port
and band parts of the body.
Install the knob faces
upward (Accessories)
Attached
hose band
Attached
heatinsulation
Attached drain hose
(Accessories)
Locally
arrangedviny
pipe
(a) Top view
Drain hose
Hose band
20mm
20mm
Transparent
visible portion
5~10mm
(b) Side view
Applying area
of adhesive
VP25
Gauge line
4 mm or less
35 mm
(c) Hose opening view
Wind the attached heat insulation
around the hose band
Make sure the
alignment is on top
(d) Top view
Make sure there
are no gaps
Note: Check for drainage
Pour about 1 liter of water from the position shown in the diagram or
from the air ow outlet to the dew tray. Check for any abnormalities
such as strange noises and whether the drain pump functions
normally.
En-9
Watering pot
Drain pipe
Wire cover
Screw
6. ELECTRICAL WIRING
WARNING
Electrical work must be performed in accordance with this
Manual by a person certi ed under the national or regional
regulations. Be sure to use a dedicated circuit for the unit.
An insuf cient power supply circuit or improperly performed
electrical work can cause serious accidents such as electric
shock or re.
Before starting work, check that power is not being supplied to
the indoor unit and outdoor unit.
• For wiring, use the prescribed type of cables, connect them
securely, making sure that there are no external forces of the
cables applied to the terminal connections.
Improperly connected or secured cables can cause serious
accidents such as overheating the terminals, electric shock,
or re.
Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious
accidents such as electric shock or re through exposure to
dust or water.
• Install sleeves into any holes made in the walls for wiring.
Otherwise, a short circuit could result.
Use the included connection cables and power cables or
ones speci ed by the manufacturer. Improper connections,
insuf cient insulation, or exceeding the allowable current can
cause electric shock or re.
Do not modify the power cables, use extension cables, or use
any branches in the wiring. Improper connections, insuf cient
insulation, or exceeding the allowable current can cause electric
shock or re.
• Match the terminal block numbers and connection cable colors
with those of the outdoor unit. Erroneous wiring may cause
burning of the electric parts.
Securely connect the connection cables to the terminal board.
In addition, secure the cables with wiring holders. Improper
connections, either in the wiring or at the ends of the wiring,
can cause a malfunction, electric shock, or re.
• Always fasten the outside covering of the connection cable with
the cable clamp. (If the insulator is chafed, electric leakage may
occur.)
Install a ground leakage breaker. In addition, install the ground
leakage breaker so that the entire AC main power supply is
cut off at the same time. Otherwise, electric shock or re could
result.
Always connect the ground cable.
Improper grounding work can cause electric shocks.
• Install the remote controller cables so as not to be direct touched
with your hand.
Perform wiring work in accordance with standards so that the
air conditioner can be operated safely and positively.
Connect the connection cable rmly to the terminal board.
Imperfect installation may cause a re.
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly quali ed persons
in order to avoid a hazard.
CAUTION
Ground the unit.
Do not connect the ground cable to a gas pipe, water pipe,
lightning rod, or a telephone ground cable.
Improper grounding may cause electric shock.
Do not connect power supply cables to the transmission
or remote controller terminals, as this will damage the
product.
Never bundle the power supply cable and transmission
cable, remote control cable together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or
breakdown.
• When handling PCB, static electricity charged in the body may
cause malfunction of the PCB. Follow the cautions below:
• Establish a ground for the indoor and outdoor units and
peripheral devices.
Cut power (breaker) off.
Touch metal part of the indoor and outdoor units for more
than 10 seconds to discharge static electricity charged in
the body.
Do not touch terminals of parts and patterns implemented
on PCB.
6.1. Electrical requirement
Voltage rating
230 V
Operating range
198 to 264 V
Select the power cable type and size in accordance with
relevant local and national regulations.
• Speci cations for local wiring power cord and branch wiring are
in compliance with local code.
Max. wire length: Set a length so that the voltage drop is less
than 2%. Increase the wire diameter when the wire length is
long.
Refer to the table for the breaker speci cations of each
installation condition. Perform the power crossover wiring within
the range of the same refrigerant system. When the crossover
wiring is done, make a connection for indoor units to satisfy
conditions A and B below.
En-10
A. Current breaker requirements
Model MCA MFA
AUXB07LALH
0.20 A
20 A
AUXB09LALH
0.20 A
AUXB12LALH
0.24 A
AUXB14LALH
0.29 A
AUXB18LALH
0.30 A
AUXB24LALH
0.75 A
MCA: Minimum Circuit Ampacity
MFA: Maximum Fuse Ampacity
When the power crossover wiring is done, make it so that the
total of the MCA of the connected indoor units does not exceed
the 15 A.
If the capacity of connected indoor units exceeds the upper limit,
either add breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Breaker capacity
The number of connectable indoor
units
30 mA, 0.1 sec or less 12 or less*
100 mA, 0.1 sec or less 13 to 40
200 mA, 0.1 sec or less 41 to 48
*:
If the total number of units connected to the breaker exceeds
12, either add a 30mA breaker, or use breakers with a greater
capacity.
Recommended
cable size
(mm
2
)
Cable type Remark
Power
supply cable
2.5
Type60245
IEC57 or
equivalent
1ø 50 Hz
198–264 V
2 Cable +
ground
Transmission
c
able
0.33
LONWORKS
compatible
cable
22 AWG LEVEL
4 (NEMA)
non-polar 2
core, twisted
pair solid core
diameter 0.65
mm
Remote
controller
cable
0.33
Sheathed
PVC cable*
Polar 3 core
Twisted pair
*: Use shielded cable in accordance with local rules for remote
controller cable.
6.2. Wiring method
(EXAMPLE)
POWER SUPPLY
OUTDOOR UNIT
TRANSMISSION
TRANSMISSION TRANSMISSION
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
POWER SUPPLY
REMOTE
CONTROLLER
(MASTER)
REMOTE
CONTROLLER
(SLAVE)
REMOTE
CONTROLLER
REMOTE CONTROL
INDOOR UNIT
INDOOR UNIT
INDOOR UNIT
BREAKER
BREAKER
POWER SUPPLY REMOTE CONTROL POWER SUPPLY REMOTE CONTROL
BREAKER BREAKER
TRANSMISSION
[Crossover wiring of power supply]
Indoor unit
Indoor unit Indoor unit
Power supply
Power supply
Power supply
Pull box
Pull box
Breaker
Power supply
6.3. Unit wiring
Before attaching the cable to terminal block.
6.3.1. Power supply cable
Adjust the length of power supply cable to avoid excessive
tension with referring gure below.
20 mm
30 mm
Power supply cable
Earth cable
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram
and connect after looping it around the end of the cable.
(2) Use the speci ed cables, connect them securely, and fasten
them so that there is no stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal
screws.
Do not use a screwdriver that is too small, otherwise, the
screw heads may be damaged and prevent the screws from
being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the
screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not x 2 power supply cables with 1 screw.
En-11
Strip 25 mm
Loop
Screw with spe-
cial washer
Screw with
special washer
Cable end
(Loop)
Cable end
(Loop)
Cable
Cable
Terminal block
WARNING
When using solid core cables, do not use the ring terminal. If
you use the solid core cables with the ring terminal, the ring
terminal's pressure bonding may malfunction and cause the
cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the
gure below to connect to the terminal block.
(2) Securely clamp the ring terminals to the cables using an
appropriate tool so that the cables do not come loose.
(3) Use the speci ed cables, connect them securely, and fasten
them so that there is no stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw
heads may be damaged and prevent the screws from being
properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the
screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not x 2 power supply cables with 1 screw.
Strip 10 mm
Sleeve
Screw with spe-
cial washer
Screw with
special washer
Ring terminal
Cable
Cable
Terminal block
Ring terminal
Ring
terminal
WARNING
Use ring terminals and tighten the terminal screws to the
speci ed torques, otherwise, abnormal overheating may be
produced and possibly cause heavy damage inside the unit.
Tightening torque
M4 screw
(Power supply /L, N, GND)
1.2 to 1.8N
m
(12 to 18 kgfcm)
6.3.2. Transmission and Remote controller cable
30 mm
40 mm
Transmission cable
Shielded
cable (no lm)
30 mm
Remote controller cable
Connect remote controller and transmission cables as
shown in Fig. C.
Fig. C
OK NO GOOD NO GOOD
Different
diameter
Connect to
1 side
WARNING
• Tighten the terminal screws to the speci ed torques, otherwise,
abnormal overheating may be produced and possibly cause
heavy damage inside the unit.
Tightening torque
M3 screw
(Transmission /X1, X2)
(Remote controller /Y1, Y2, Y3)
0.5 to 0.6Nm
(5 to 6 kgf
cm)
CAUTION
To peel the lm from the lead cable, use a dedicated tool that
will not damage the conductor cable.
• When installing a screw on the terminal block, do not cut
the wire by overtightening the screw. On the other hand, an
undertightened screw can cause faulty contact, which will
lead to a communication failure.
En-12
6.4. Connection of wiring
Remove the control box cover and install the connection cable.
(1) Remove the control box cover and install each connection cable.
Screw
Control box cover
(2) Connect the connection cable, with the binder.
Cable clamp L, N: Power supply cable
Remote controller cable
Y1: Red
Y2: White
Y3: Black
Binder
(Accessories)
X1, X2:
Transmission cable
(3) Install control box cover.
CAUTION
Do not bundle the remote controller cable, or wire the remote controller cable in parallel, with the indoor unit connection cable (to the
outdoor unit) and the power supply cable. It may cause erroneous operation.
En-13
6.5. External input and external output
(Optional parts)
Controller PCB
Input No Voltage
terminal (CN17)
Input Voltage terminal (CN6)
Output terminal (CN16)
(1) External input terminals
• Indoor unit can be Start/Stop or Emergency stop, Forced
stop by using indoor unit PCB CN6 or CN17.
Wiring methods and speci cations
• A twisted pair cable (22AWG) should be used. Maximum
length of cable is 150 m.
* Use an external input and output cable with appropriate
external dimension, depending on the number of cables to
be installed.
• The wire connection should be separate from the power
cable line.
• Input selection
Use either one of these types of terminal according to the
application. (Both types of terminals cannot be used
simultaneously.)
• Voltage terminal ([CN6])
When a power supply must be provided at the input device
you want to connect, use the voltage terminal ([CN6]).
1
2
3
+
+
-
-
-
Input device 1Input device 2
Load
resistance
Load
resistance
*1
DC power supply
12 - 24V
connected unit
*a
*a
P.C . B
CN6
*b
*1
Make the power supply DC12 to 24V. Select a power supply
capacity with an ample surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and
1-3.
*a The allowable current is DC5~10mA. (Recommended:
DC5mA)
Provide a load resistance such that the current becomes
DC10mA or less.
Select very low current use contacts (usable at DC12V,
DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3.
Connect correctly.
When connected to voltage terminals of multiple indoor units
with a connected unit, be sure to make a branch outside the
indoor unit using a pull box, etc. as shown on below example.
DC power
supply 12-24V
connected unit
Load
resistance
P.C . B
P.C . B
CN6
CN6
CN6
P.C . B
Input device 1Input device 2
Indoor unitIndoor unitIndoor unit
Load
resistance
• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device
you want to connect, use the no voltage terminal ([CN17]).
1
2
3
P.C . B
GND
Ch 1
*c
*c
*d
Ch 2
CN17
connected unit
*c Select very low current use contacts (usable at DC12V,
DC1mA or less).
*d The wiring is different from voltage terminals. Be suf ciently
careful when wiring.
When connected to no voltage terminals of multiple indoor units
with a connected unit, insulate each indoor unit with relay, etc.
as shown on below example.
When connected to multiple indoor units directly, it will cause
breakdown.
Power supply for relay
Indoor unit Indoor unit Indoor unit
Input device 2
Input device 1
K1~K6: Relay
(Device for DC Current)
P.C . B
K1
P.C . B
P.C . B
CN17
CN17
CN17
K2
K3
K4
K5
K6
En-14
• Selection method of functions
“Start/Stop” mode or “Emergency stop” mode, “Forced stop”
mode can be selected with function setting of indoor unit.
(2) External output terminals
• When picking up output signals for operating status,
abnormal conditions or indoor unit status.
Wiring methods and speci cations
• A twisted pair cable (22AWG) should be used. Maximum
length of cable is 150 m.
• Use an external input and output cable with appropriate
external dimension, depending on the number of cables to
be installed.
• The wire connection should be separate from the power
cable line.
1
2
3
4
P.C . B
CN16
*4
+
+
-
-
-
-
DC power supply
12 - 24V *2
Connected load
*3
connected unit
Connected load
*3
Connected load
*3
*2 Provide a DC12 to 24V power supply. Select a power
supply capacity with an ample surplus for the connected
load.
*3 The allowable current is 30mA or less. Provide a load
resistance such that the current becomes 30mA or less.
*4
Polarity is [+] for pin 1 and [-] for pins 2-4. Connect correctly.
Do not impress a voltage exceeding 24V across pins 1-2, 1-3,
and 1-4.
Operation behavior
Connector Output voltage Status
CN16
External
output1
Pins 1-2
0V Stop
DC 12-24 V *2 Operation
External
output2
Pins 1-3
0V Normal
DC 12-24 V *2 Error
External
output3
Pins 1-4
0V Indoor unit fan stop
DC 12-24 V *2
Indoor unit fan
operation
Operation behavior
• Input signal type
The input signal type can be selected.
It is switched by Dip-sw on the indoor
unit PCB.
Dip-sw [Set 2-2] Input signal type
OFF Edge
ON Pulse
• When function setting is “Start/Stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of
CN6 or CN17
OFF ON Operation
ON OFF Stop
[In the case of “Pulse” input]
Connector Input signal Command
CN6 or CN17
Ch1 OFF ON Operation
Ch2 OFF ON Stop
* The last command has priority.
* The indoor units within the same remote controller group
operates in the same mode.
• When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of
CN6 or CN17
OFF ON Emergency stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CN6 or CN17
Ch1 OFF ON
Emergency
stop
Ch2 OFF ON Normal
* All indoor units of same refrigerant system stops when
Emergency stop operates.
• When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of
CN6 or CN17
OFF ON Forced stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CN6 or CN17
Ch1 OFF ON Forced stop
Ch2 OFF ON Normal
* When the forced stop is triggered, indoor unit stops and
Start/Stop operation by a remote controller is restricted.
*
When forced stop function is used with forming a
remote controller group, connect the same equipment
to each indoor unit within the group.
Pulse
The width of pulse
must be longer
than 200msec.
Edge
En-15
(3) Connection methods
• Wire modi cation
Use a tool to cut off the terminal on the end of the
wire, and then remove the insulation from the cut end
of the wire.
Connect the wire with connecting wire with solder.
Important: Be sure to insulate the connection between the wires.
Option parts
External input /output wire
Insulated connection
Field supply
Input Voltage
terminal (CN6)
Controller PCB
Input No Voltage
terminal (CN17)
Output terminal
(CN16)
Binder (Field supply)
:Bind to the transmission cable
Transmission cable
7. FIELD SETTING
There are 3 methods for address setting by FIELD
SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD
, REF AD SW settings
... This section (7.1. Setting the
address)
(2) Remote controller settings ....
Refer to the wired or wireless
remote controller manual for
detailed setting information.
(Set IU AD, REF AD SW to 0)
(3) Automatic address settings ...
Refer to the outdoor unit
manual for detailed setting
information. (Set IU AD, REF
AD SW to 0)
CAUTION
Be sure to turn OFF the power before performing the eld
setting.
7.1. Setting the address
CAUTION
Use an insulated screwdriver to set the dip switches.
Rotary switch
Example: “0”
Rotary switch
Example: “0”
Setting
Setting
range
Type of switch
Indoor unit
address
0–63
Setting
example
2
IU AD×10 IU AD×1
Refrigerant
circuit
address
0–99
Setting
example
63
REF AD×10 REF
AD×1
(1) Indoor unit address
Rotary switch (IU AD ×1)...Factory setting “0”
Rotary switch (IU AD ×10)...Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system,
set the address at IU AD SW as shown in the Table A
.
En-16
Example If 4 indoor units are connected.
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
Indoor unit
Remote
controller
Indoor unit Indoor unit Indoor unit
RC AD SW
01234567
Address
01234567
RC AD SW
89ABCDEF
Address
8 9 10 11 12 13 14 15
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote
controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP SW SET 3 SW1 , SW2, referring to the Table B.
SW
1
SW
2
SW
3
SW
4
Dip switch “SET3”
Table B
Custom code
A (Factory setting) B C D
DIP SW
SET 3 SW1
OFF ON OFF ON
DIP SW
SET 3 SW2
OFF OFF ON ON
CAUTION
Do not operate any switches other than prescribed, as it can
cause the unit to operate improperly or malfunction.
(2) Refrigerant circuit address
Rotary switch (REF AD ×1)...Factory setting “0”
Rotary switch (REF AD ×10)...Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW
as shown in the Table A for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor
unit.
If working in an environment where the wireless remote
controller can be used, the addresses can also be set
using the remote controller.
If setting the addresses using the wireless remote
controller, set the indoor unit address and refrigerant circuit
address to “00”.
(For information on setting using the wireless remote
controller.)
Table A
Address
Rotary
Switch
Setting
Address
Rotary
Switch
Setting
Refrigerant
circuit
REF AD SW
Indoor
unit
IU AD SW
× 10 × 1 × 10 × 1
0
00 0 00
101101
202202
303303
404404
505505
606606
707707
808808
909909
10 1 0 10 0 0
11 1 1 11 1 1
12 1 2 12 1 2
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
99 9 9 63 6 3
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result failure.
(3) Remote controller address
Rotary switch (RC AD SW)...Factory setting “0”
When connecting multiple indoor units to 1 standard
wired remote controller, set the address at RC AD SW in
sequence from 0.
Setting
Setting
range
Type of switch
Remote
controller
address
0–15
Setting
example
0
RC AD
En-17
7.3. Function setting
FUNCTION SETTING can be performed with the wired or
wireless remote controller.
(The remote controller is optional equipment)
Refer to the wired or wireless remote controller manual for
detailed setting information. (Set IU AD ,REF AD SW to 0)
Refer to “7.1. Setting the address.” for indoor unit address
and refrigerant circuit address settings.
Turn the power of the indoor unit ON before starting the
setting.
* Turning on the power indoor units initializes EEV, so make
sure the piping air tight test and vacuuming have been
conducted before turning on the power.
* Also check again to make sure no wiring mistakes were
made before turning on the power.
Function details
Function
Function
number
Setting
number
Default Details
Filter
indicator
interval
11
00 Default
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation
is too early, change to setting
01. If the notifi cation is too late,
change to setting 02.
01 Longer
02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the fi lter
indicator. Setting 02 is for use
with a central remote controller.
01 Disable
02
Display
only on
central
remote
controller
Ceiling
air ow
20
00 Default
Regulate the airfl ow according
to the needs of the installation
location. When set to 01, the air
ow will be stronger.
01
High
Ceiling
Vertical
air ow
direction
23
00 Default
Adjust the vertical airfl ow
direction. All airfl ow direction
louvers are adjusted together.
(Cassette type only)
01 Raise
Cool air
tem-
perature
trigger
30
00 Default
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
01 Adjust (1)
02 Adjust (2)
Hot air
tem-
perature
trigger
31
00 Default
Adjust the hot air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto
restart
40
00 Enable
Enable or disable automatic
system restart after a power
outage.
01 Disable
External
control
46
00 Start/Stop
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to
the external input terminals,
and Start/Stop by a remote
controller is restricted.
01
Emergency
stop
02
Forced
stop
Error
report
target
47
00 All
Change the target for reporting
errors. Errors can either be
reported in all locations, or only
on the wired remote.
01
Display
only on
central
remote
controller
7.3.1. Button name and function
OPERATION indicator lamp (Green)
FILTER indicator lamp (Red)
TIMER indicator lamp (Orange)
MANUAL AUTO button
7.3.2. Checking the function settings
Press and hold the “MANUAL AUTO” button on the indoor
unit for 3 seconds to check the function settings. It is
necessary to disconnect the power in order to return to
normal operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indication pattern
Indoor unit
address
Refrigerant address
OPERATION indicator
lamp (Green)
ON
Flash
(1.0s ON/1.0s OFF)
TIMER indicator
lamp (Orange)
Address: tens place
(0.5s ON/0.5s OFF)
FILTER indicator
lamp (Red)
Address: ones place
(0.5s ON/0.5s OFF)
En-18
Indoor unit address example
(Example) ADDRESS : 24
OPERATION
indicator
lamp (Green)
TIMER
indicator lamp
(Orange)
FILTER
indicator lamp
(Red)
10 sec
1 cycle 12 sec
8 sec
ON
OFF
0.5s
0.5s 0.5s 0.5s
0.5s
0.5s
0.5s 0.5s
0.5s
0.5s
0.5s 0.5s
ON
OFF
ON
OFF
ON
Refrigerant address example
(Example) ADDRESS : 30
OPERATION
indicator lamp
(Green)
TIMER
indicator lamp
(Orange)
FILTER
indicator lamp
(Red)
9 sec
1 cycle 12 sec
ON
OFF
1.0s 1.0s 1.0s
1.0s 1.0s 1.0s 1.0s
0.5s
0.5s
0.5s 0.5s 0.5s 0.5s
ON
OFF
ON
OFF
OFF
• Setting details
Function
number
Item Setting number
01 Indoor unit address 00~63
02 Refrigeration address 00~99
For use with a remote controller, set all rotary switches to
0, and refer to “7.1. Setting the address” for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name Indication pattern
OPERATION indicator
lamp (Green)
Function number; tens place
(0.5s ON/0.5s OFF)
TIMER indicator lamp
(Orange)
Function number; ones place
(0.5s ON/0.5s OFF)
FILTER indicator lamp
(Red)
Setting number: (0 - 9) (0.5s
ON/0.5s OFF)
(Example) Function : 31, Setting number : 2
OPERATION
indicator lamp
(Green)
TIMER
indicator lamp
(Orange)
FILTER
indicator lamp
(Red)
11 sec
10 sec
9 sec
1 cycle 12 sec
ON
OFF
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
ON
OFF
ON
OFF
8. DECORATION PANEL INSTALLA-
TION
8.1. Remove the intake grille
(1) Slide the 2 grille hook
Grille hook
(2) Open the intake grille and remove.
En-19
8.2. Install panel to indoor unit
(1) Install the decoration panel on the indoor unit.
“DRAIN” mark
“PIPE” mark
* Align the stamped marks on the decoration panel against the pipe
and the drain of the indoor unit.
CAUTION
Use only the supplied screws to install the decoration panel.
Indoor unit
Cealing
No gap between cealing and
decoration panel around entire
periphery
5 ~ 7
Decoration panel
Sealant
(2) Connect the connector.
Cable (louver): WHITE
Cable (display): WHITE
Cable (louver): RED
Indoor unit side
Arrange the cables as illustrated below.
(3) Attach the connector cover.
Screw
Connector cover
8.3. Attach the intake grille
The installation is the reverse of “REMOVING THE INTAKE
GRILLE”.
The intake grille can be rotated and installed 4 ways to suit
the user’s preference.
CAUTION
The louver angle cannot be changed if the power is not on,
(If moved by hand, it may be damaged.)
• The grille assembly is directional relative to the air conditioner
body.
• Install so that there is no gap between the grille assembly
and the air conditioner body.
9. TEST OPERATION
9.1.
Test operation using PCB (Outdoor unit)
Refer to the Installation Manual for the outdoor unit if
the PCB for the outdoor unit is to be used for the test
operation.
9.2.
Test operation using Remote Controller
Refer to the Installation Manual for the remote controller
to perform the test operation using the wireless remote
controller.
When the air conditioner is being test run, the
OPERATION and TIMER indicator lamps ash slowly at
the same time.
En-20
10. CHECK LIST
Pay special attention to the check items below when installing
the indoor unit(s). After installation is complete, be sure to
check the following check items again.
CHECK ITEMS
If not performed
correctly
CHECK
BOX
Has the indoor unit been
installed correctly?
Vibration, noise,
indoor unit may drop
Has there been a check
for gas leaks (refrigerant
pipes)?
No cooling, No
heating
Has heat insulation work
been completed?
Water leakage
Does water drain easily
from the indoor units?
Water leakage
Is the voltage of the
power source the same
as that indicated on the
label on the indoor unit?
No operation, heat or
burn damage
Are the wires and
pipes all connected
completely?
No operation, heat or
burn damage
Is the indoor unit
grounded?
Short circuit
Is the connection cable
the specified thickness?
No operation, heat or
burn damage
Are the inlets and outlets
free of any obstacles?
No cooling, No
heating
Does start and stop air
conditioner operation by
remote control unit or
external device?
No operation
After installation is
completed, has the
proper operation and
handling been explained
to the user?
11. ERROR CODES
If you use a wired type remote controller, error codes will
appear on the remote controller display. If you use a wireless
remote controller, the lamp on the photodetector unit will output
error codes by way of blinking patterns. See the lamp blinking
patterns and error codes in the table below.
Error display
Wired
Remote
Controller
Error code
Error contents
OPERATION
lamp (green)
TIMER
lamp
(orange)
FILTER
lamp
(red)
(1) (2)
Remote controller
communication
error
(1) (4)
Anomalous
network
communications
(1) (6)
Parallel
communication
error
(3) (1)
Power frequency
error
(3) (2)
Model
information
error/EEPROM
accession error
(4) (1)
Room
temperature
thermistor error
(4) (2)
Indoor heat
exchanger
temperature
thermistor error
(5) (1)
Indoor fan motor
error
(5) (3)
Drainage error
(9) (15)
Outdoor unit
error
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of ashing
Wired Remote Controller Display
Error code
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Fujitsu AUXB24LALH Installation guide

Category
Split-system air conditioners
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI