Application Sheet
Lit. No.
VY7FB102
Date:
2000-02-04
ECL 2000/Comfort – LON Network Free Topology
Heat Meter
Heat Meter
Main station
ECL Comfort 200/300
ECL 2000
ECL Comfort 200/300
ECL 2000
ECL Comfort 200/300
Analog/Digital I/O
(Temp
., Flow, Contacts, etc.)
I/O Module
Terminator
ECL 2000
The FTT system (Free Type Topology) is
designed to support free topology wiring,
and will accommodate bus, star, loop or any
combination of these topologies. FTT-10
transceivers can be located at any point
along the network wiring. High capability
simplifies system installation and makes it
easy to add nodes to expand the system.
Limitations:
Maximum total cable length 500 m.
Requires 1 terminator, connected some-
where.
If the cable length exceeds 500 m, a physi-
cal repeater (maximum one) or a logical
router has to be connected for every 500
meters of the cable.
What do I need?
1 Network Terminator
If bindings between ECL 2000/Comfort, Heat Meter, etc. are desired or visualisation possibili-
ties of data from the network:
PC (Laptop)
Interface between LON network and the PC
Binding tool
Visualisation software incl. Drivers
/