Cooper Lighting OAWC-P-120W-R Installation guide

Category
Motion detectors
Type
Installation guide

This manual is also suitable for

Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
24’
(7.3 mm)
Minor Motion, IR
Major Motion, IR
20’
(6 mm)
8’
(2.4 mm)
8’
(2.4 mm)
24’
(7.3 mm)
20’
(6 mm)
0
10 ft
(3 mm)
12’
(3.7)
12’
(3.7)
6 ft
(1.7 mm)
15 ft
(4.6 mm)
24 ft
(7.3 mm)
50 ft
(15.3 mm)
Model # OAWC-P-120W
Model # OAWC-P-120W-R
Passive Infared Wall/Corner Mounted Low
Voltage Occupancy Sensor
• Readallinstructionsonbothsidesofthissheetrst
• Planallcomponentlocationscarefully
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
• ForUsewithGreengateSwitchpacks&SystemsOnly
• DonotrunanyGreengateLowVoltageWiringinthe
sameconduitaspowerconductors
General Information
Technology:PassiveInfrared(PIR)
Power Requirements:
Input:
• 10-30VDCfromGreengateSwitchpackorGreengate
system.Maximumcurrentneededis25mApersensor
Output:
• OpencollectoroutputtoswitchuptotenGreengate
Switchpacks.BASwithIsolatedFormCRelay(-Rmodel)
IsolatedFormCRelayRatings:1A30VDC/VAC
Time Delays:Self-Adjusting,15seconds/test(10minAuto),
orSelectable5,15,30minutes
Coverage:1200sq.ft.
Light Level Sensing:0to300foot-candles(-Rmodel)
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Housing:
• Mediumimpactinjectionmoldedhousing
PolycarbonateresincomplieswithUL94V0
Size:4.4"x3.4"x2"(112mmx86.4mmx50.8mm)
LED Indicators:RedindicatesPIRdetection
Specifications
Description
TheOAWC-PWall/CornerMountLowVoltageOccupancySensorisaPassiveInfrared(PIR)motion sensinglightingcontrol,used
forenergysavingsandconvenience.Whenmotionisdetected,thebluewireiselectronicallyconnectedtotheredwire,energizing
therelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,thebluewireisdisconnectedfromthered,causingtherelay
toopenturningOFFtheload.Theredleadis10to30VDCsupply,theblackleadiscommonandtheblueistherelaycontrol.
PIR Technology
Thesensor’ssegmentedlensdividestheeldofviewintosensorzonesanddetectsthechangesintemperaturethatarecreated
whenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtimedelayinreal-
time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergysavingsthatareavailablein
theparticularapplication.
TheDaylightingfeature(-Rmodelonly)preventslightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.Thesensor
willswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetectmotion30seconds
following theinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
InAutomaticOnMode,thelightsturnONwhenapersonenterstheroom.InManualONMode,thelightsareturnedONby
activatingamomentaryswitch(model#GMDS-*)thatisconnectedtothesensor.Whenusedwith2levellighting(-Rmodelonly),
bi-levelAutomaticONcanbeachievedwhichallowsZone1tocomeONautomaticallyuponoccupancy.Zone2doesnotcomeON
unlesstheoccupantpressestheoptionalmomentaryswitch.
Location
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthe
presenceofobstacles.Followthecoveragediagramconcerningmajorandminormotion
coverage.Thesensormusthaveaclearviewoftheareatobecontrolled.Thesensorwill
not“see”throughglass.Mountingheightshouldnotexceed12feet.Optimummounting
heightis10feet.Mountthesensorsothedevicefacestheopenportionoftheroom and
arefacinganearbywall,door,window,orotherobstructingobject.Avoidpointinginto
hallways.Topreventfalseactivation,thesensorshouldbemountedawayfromtheair
supplyductaminimumof4to6feet.Mountingatxtureheightismosteffective.For
typicalplacementrefertoLocationDiagram.
Installation
TheOAWC-P-120Wcanbemountedtothewall,ceiling,junctionboxorroundxturewithraceway.
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the
branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a
fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with
the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by
frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2. Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsforall
connections)CAPALLUNUSEDWIRELEADS.
3. Mountunittowall,ceiling,junctionbox,orroundxturewithraceway.
4. TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5. Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
Occupancy Sensor Mounted to Wallboard
Occupancy Sensor Mounted to Round Fixture with Raceway
Occupancy Sensor Mounted to Octagon Box
Occupancy Sensor Mounted to Drop Ceiling
Location Diagram
Coverage
Occupancy Sensor Mounted to Octagon Box with Mud Ring
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30 VDC)
Blue (Control)
Yellow (Control)
Brown (Switch-Blue Lead Control)
Brown/White (Switch-Yellow Lead Control)
Sensor’s Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally closed)
Yellow
Blue
Red
Black
Recommended Wire: 18-3 AWG stranded non-shielded
Brown/White
Brown
Gray
Purple
Orange
Optional Greengate GMDS Switch-
Blue Control Lead-Manual ON/OFF
To Additional Sensors.
Maximum of 5 sensors
per switchpack.
Switchpack
Blue
Load 1
White
**Hot
Blue
Hot
Neutral
Line
**Use Black Lead for 120 VAC
Use Orange Lead for 277 VAC
Cap Unused Lead
Black (Common)
Red (15 VDC)
Blue (Control)
One Sensor, One Switchpack
P/N 9850-000140-01
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Checkout and Adjustment
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
WallswitchOFF TurnwallswitchON
Iflowvoltageswitchoptionisused,lights
mayhavebeenturned-offmanually
Presslow-voltageswitch
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnONadjustDIP
Switch10and/ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled
IfalllightsarerequiredadjustDIP
Switch10and/ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalled4-6feetaway
fromanyairventandoutofheavyairow
Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5UP
Bypass
Checkwiringtomakesuresensor
orswitchpackarenotbypassed
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandPIRsensitivity.Inpreparationforthe
InstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the
unitwilltime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconrmedbywatching
theRed(PIR)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONforonesecondwitheachmotion.(IfLEDs
donotturnON,gotoInstallerAdjustments-SensitivityAdjustmentsSection)
2.Standstillsixtoeightfeetawayfromthesensorforveseconds.LEDsshouldnotturnON.(IfanyLEDturns
ON,noteLEDandgotoInstallerAdjustments–SensitivityAdjustmentsection)
3.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.
(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
5.TheunitwillremaininTestModefor5 minutesthenautomaticallyexitTestModeandgofor10min.Time
DelayUserModesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To
forceinto10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrent
position,wait3
seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillashonceper1/4second.
Installer Adjustments
Sensitivity Adjustments
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5U P.
Hot
Neutral
Line
Load 1
Black
Red
Blue
Purple
Gray
Orange
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Hot
Neutral
Line
Load 2
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Yellow
Brown
Brown/White
Optional Greengate GMDS Switch-
Blue Control Lead- Manual on/off
Red (15VDC)
Black(Common)
Blue (Control)
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30VDC)
Blue (Control)
Yellow (Control)
Brown (Switch-Blue Lead Control)
Brown/White(Switch-Yellow Lead Control)
Sensor's Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally Closed)
Red (15VDC)
Black(Common)
Blue (Control)
To Additional Switchpacks
10 switchpacks Maximum
Activation Activation
PIR Sensitivity
Daylighting Mode
Lighting SweepOverride
LEDs
10
9
8
7
50%
54
5 Minutes
15 Minutes
30 Minutes
Auto
Auto
Manual
Manual
DIP Switch
3
2
Power Pack One Power Pack Two
(-R model only)
(-R model only)
Full
Disable
Disable
Disable
Enable
Enable
Enable
Auto*
*Self-Adjusts to
10 min. user mode
Default =
Time Delay
1
Disable
Enable
6
Walk-Through Mode
Half
Full
12345678910
One Sensor, Multiple Switchpacks Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
Daylight Adjustments
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyCW).
TheDaylightingfeature(-Rmodelonly)preventsthelightsfromturningONwhentheroomisadequatelyilluminated
bynaturallight.Ifthereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsO F F.Ifthere
isnotenoughlightintheroom,thesensorwillallowthelightstoturnONwhenoccupied.
Full and Half Logic Modes(SeeDIPSwitchlegend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancy
activation,shouldtheambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtothe
yellowcontrolleadwillturnOF F.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,after
occupancyactivation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturn
thelights
OFFwhileoccupancyisbeingdetected.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoarticiallightisneeded.Inorderforthis
featuretofunction,theyellowcontrolleadmustbewired.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrent
position,wait3secondsandthenbackintoitsoriginalposition.
2.SetDIPSwitch10toFullorHalfLogicMode.
3.Setthelightleveltominimum(fullyCCW).
4.Leavetheroomandletthesensortime-outsolightsareOF F.EnterthespaceandlightsshouldremainOFF.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
incrementsuntilthelightsareON.(Pause5secondsbetweeneachadjustment)
6.OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethe
currentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10
minutes.AslongasAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,
byalternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbe
noneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2are
alreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Automatic Mode
InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltage
switchesareusedalongwithAutomaticONMode,activatingtheswitch(es)whiletheloadisONturnstheloadO F F.
WhentheloadisturnedOFFmanually,aslongasthesensorcontinuestodetectoccupancytheloadsstayO F F.After
thetimedelayexpires,thelightsstayOFFandthesensorgoesbacktoAutomaticONMode.Forwiringinformationfor
theoptionalmomentarylowvoltageswitch(es),pleaseseethewiringsectionoftheinstallationinstructions.
Manual Mode
InManualONMode,theoptionalmomentarylowvoltageswitch(es)isrequired
toturntheload(s)ON.Onceactivated
thesensorwillmaintainthelightsONuntilmotionceasesandthetimedelayexpires.Whiletheroomisoccupiedthe
BASrelayremainsactive.Afterthetimedelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)
mustbeusedtoturntheload(s)ONunlessthereismotiondetectedwithinthe10secondre-triggerperiod.
Lighting Sweep Option
Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayuponpower-up”topreventfalseactivationin
buildingswithcomputercontrolsystems.
1. MoveDIPSwitch9U P.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPSwitch8U P.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).