Cooper Lighting Vacancy Passive Infrared MicroSet Ceiling Sensor Installation guide

Category
Motion detectors
Type
Installation guide
Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Black
Blue
Brown
Yellow
Purple
Gray
Orange
Red
White/Brown
Load 1
Blue
Neutral
Hot
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Line
**Hot
White
Blue
SWITCH-
PACK
Black (Common)
Blue (Control)
Red (15 VDC)
Model GMDS - Load 1
(Normally Open
Momentary Switch)
Manual Mode Operation:
Switches are required to
turn corresponding loads ON.
Lights turn OFF when sensor
times out or with the
switch.
If daylight sensor is
enabled and light level is
above setpoint, switchpack
connected to yellow lead
will not turn ON.
Recommended Wire:
18-3 AWG Stranded Wire
non/shielded.
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30 VDC)
Blue (Control - Occupancy)
Yellow (Control - Occupancy and Daylight)
Brown (Switch-Blue Lead Control)
Brown/White (Switch-Yellow Lead Control)
Sensor's Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally Closed)
Coverage
Model # VAC-P-0500-R
Model # VAC-P-1500-R
Passive Infrared Ceiling Mounted Low
Voltage Vacancy Sensor
• Readallinstructionsonbothsidesofthis
sheetrst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
• ForUsewithGreengateSwitchpacks&
SystemsOnly
• DonotrunanyGreengateLowVoltageWiringin
thesameconduitaspowerconductors
General Information
Power Requirements:
Input:
• 10-30VDCfromGreengateSwitchpackor
Greengatesystem.Maximumcurrentneededis
25mApersensor
Output:
• Opencollectoroutputtoswitchuptoten
GreengateSwitchpacks.
• BASwithIsolatedFormCRelay(-Rmodel)
• IsolatedFormCRelayRatings:1A30VDC/VAC
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Specifications
Description
TheVAC-PCeilingMountLowVoltageVacancySensorisaPassiveInfrared(PIR)motionsensinglighting
control,usedforenergysavingsandconvenience.ThesensorproducesaPassiveInfrared(PIR)motionsensing
lightingcontrol,usedforenergysavingsandconvenience.WhenmanuallyturnedON,thebluewireiselectronically
connectedtotheredwire,energizingtherelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,theblue
wireisdisconnectedfromthered,causingtherelaytoopenturningOFFtheload.Theredleadis10-30VDCsupply,
theblackleadiscommon,andtheblueistherelaycontrol.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.
Location
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Follow
thecoveragediagramconcerningmajorandminormotioncoverage.Thesensormusthaveaclearviewoftheareato
becontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12feet.Optimummounting
heightis8to10feet.Avoidpointingintohallways.Mountingatxtureheightismosteffective.*Topreventfalse
activation,thesensorshouldbemountedawayfromtheairsupplyductaminimumof4to6feet.
Installation
TheVAC-Psensorcanbemountedtotheceiling,junctionbox,orroundxturewithraceway.
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used
as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All
installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor
allconnectionsCAPALLUNUSEDWIRELEADS.
3.Mountunittoceiling,junctionbox,orroundxturewithraceway.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
OAC-STEM Threaded Rod
(sold separately)
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Minor Motion, IR
Major Motion, IR
8.5 ft
(2.59 m)
10 ft
(3 m)
5 ft
(1.5 m)
0
0
5 ft
(1.5 m)
10 ft
(3 m)
DT1k
0
20 ft
(6.096m)
3 ft
(0.91)
15 ft
(4.57 m)
15 ft
(4.57 m)
20 ft
(6.096m)
20 ft
(6.096m)
20 ft
(6.096m)
10 ft
(3 m)
5 ft
(1.5 m)
10 ft
(3 m)
5 ft
(1.5 m)
15 ft
(4.57 m)
15 ft
(4.57 m)
VAC-P-1500-R Coverage Diagram
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Minor Motion, IR
Major Motion, IR
0
0
8.5 ft
(2.59 m)
0
3 ft
(0.91)
12 ft
(3.66 m)
12 ft
(3.66 m)
18 ft
(5.49 m)
18 ft
(5.49 m)
12 ft
(3.66 m)
12 ft
(3.66 m)
18 ft
(5.49 m)
18 ft
(5.49 m)
VAC-P-0500-R Coverage Diagram
Load 1
Blue
Neutral
Hot
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Line
**Hot
White
Blue
SWITCH-
PACK
Black
Blue
Brown
Yellow
Purple
Gray
Orange
Red
White/Brown
Load 2
Blue
Neutral
Hot
**Use black lead for 120 VAC
Use orange lead for 277 VAC
Cap unused lead.
Line
**Hot
White
Blue
SWITCH-
PACK
Black (Common)
Blue (Control)
Red (15 VDC)
Black (Common)
Blue (Control)
Red (15 VDC)
Model GMDS - Load 2
(Normally Open
Momentary Switch)
Model GMDS - Load 1
(Normally Open
Momentary Switch)
Manual Mode Operation:
Switches are required to
turn corresponding loads ON.
Lights turn OFF when sensor
times out or with the
switch.
If daylight sensor is
enabled and light level is
above setpoint, switchpack
connected to yellow lead
will not turn ON.
Recommended Wire:
18-3 AWG Stranded Wire
non/shielded.
Manual ON Control of
Two Standard Switchpacks
One Sensor, One Switchpack
30 ft
9.14 m
30 ft
9.14 m
15 ft
4.57 m
15 ft
4.57 m
VAC-P-1500 VAC-P-0500
P/N 9850-000195-01
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Warranties and Limitation of Liability
DIP Switch Settings Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled
IfalllightsarerequiredadjustDIPSwitch10
and/ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetaway
fromanyairventandoutofpathofheavyairow.
Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting.
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up
Bypass
Checkwiringtomakesuresensoror
switchpackarenotbypassed
Lights Will Not
Turn OFF
manually
Override
MakesuresensorisnotinOverrideMode
(DIPSwitch8up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Installer Adjustments
SweepOverride
LEDs
(-R model only)
(-R model only)
Full/Half Logic HVAC/Tracking
Zero Time Delay
Pot 1 - Blue (0-300 FC)
Ultrasonic
(-R model only)
Pot 2 - Green
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandPIRsensitivity.InpreparationfortheInstallerTest,
thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwilltime-out15seconds
afterthelastmotiondetected.CoverageandsensitivitycanbeconrmedbywatchingthePassiveInfrared(PIR)indicatorLEDson
thefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDsdonotturn
ON,gotoInstallerAdjustments–SensitivityAdjustmentsSection)
2. Standstillsixtoeightfeetawayfromthesensorforveseconds.LEDsshouldnotturnON.(IfanyLEDturnsON,noteLED
andgotoInstallerAdjustments–SensitivityAdjustmentsection)
3. Walkoutsidetheroomandwait15secondsforthelightstoturnOF F.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4. Re-entertheroomandmanuallyturnthelightsON.(IflightsdonotturnONgotoTroubleshootingSection)
5. TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgofor10min.TimeDelayUser
Modesetting.
Note: ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To
forceinto10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrent
position,wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillashonceper1/4second.
12345678910
11 12
ON
Daylight Sensor Adjustment
PIR Detector
Sensitivity Adjustments
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyonadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
Daylight Adjustments (-R Model Only 0 to 300 foot-candles)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOF F.Ifthereisnotenoughlightintheroom,the
sensorwillallowthelightstoturnONwhenoccupied.
Full and Half Logic Modes(SeeDIPSwitchlegend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancyactivation,should
theambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellowcontrol
leadwillturnO F F.ThelightswillremainOF F,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,afteroccupancy
activation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturnthelightsOFFwhile
occupancyisbeingdetected.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoarticiallightisneeded.Inorderforthisfeauretofunction,
theyellowcontrolleadmustbewired.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait
3secondsandthenbackintoitsoriginalposition.
2. SetDIPSwitch10toFullorHalfLogicMode.
3. Setthelightleveltominimum(fullyCCW).
4. Leavetheroomandletthesensortime-outsolightsareO F F.EnterthespaceandlightsshouldremainOF F.
5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrementsuntil
thelightsareON.(Pause5secondsbetweeneachadjustment)
6. OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.Aslong
asAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,byalternatelymakingslight
adjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedformanualadjustment.Ifmanual
adjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2arealreadydown,
toggleDIPSwitch10outofitscurrentposition,wait3secondsandthenbacktoitsoriginalposition)
Manual Mode
InManualONMode,theoptionalmomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivatedthesensor
willmaintainthelightsONuntilmotionceasesandthetimedelayexpires.WhiletheroomisoccupiedtheBASrelayremainsactive.
Afterthetimedelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)mustbeusedtoturntheload(s)ONunless
thereismotiondetectedwithinthe10secondre-triggerperiod.
Lighting Sweep Option
Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“power-uptopreventfalseactivationinbuildingswith
computercontrolsystems.
1. MoveDIPSwitch9up.Ifnotselected(DipSwitch9down),uponinitial“power-uporrestorationofpowerthesensorwillforce
thelightsONnomatterthestateofoccupancy.
HVAC/Tracking Mode (-R model only)
Ifselected,TrackingModeallowstheloadconnectiontotheFormCrelaytofollowthestateofthesensor’sbluelead.HVAC
ModeallowstheloadconnectedtotheFormCrelaytoremainONwhenthelightsareturnedOFFmanually.Applicationsmayinclude
keepingtheroomatadesiredtemperaturewhilegivingapresentationandthelightsareOF F.
Zero Time Delay Mode
InZeroTimeDelayMode,theoutputisactuatedforonesecondtosignalanotherdevicethatthespacebeingmonitoredis
occupied.Applicationsmayincludetheuseofalightingcontrolsystemtomanagethedelayofthelightingdeactivation.Pleaseseethe
wiringdiagramsectionforwiringdetails.
WheninZeroTimeDelayModeandTrackingModetheloadconnectedtotheFormCrelayshallfollowthestateofthesensor’s
bluelead(zeroTimeDelayfortheformCrelay).
WheninZeroTimeDelayModeandHVACMode,theloadconnectedtotheFormCrelayremainsONforthestandardtimedelay.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPSwitch8up.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).
LED Indicators Functionality
During Installer/Test Mode While in User Mode
LED Flashing Speed
LEDswillashonceper¼second LEDswillashoncepersecond
Duration
10minutes 10to30minutes
Checkout and Adjustment
  • Page 1 1
  • Page 2 2