turck TBIP-L4-4FDI-4FDX Operating instructions

Type
Operating instructions

This manual is also suitable for

Your Global Automation Partner
Instructions for Use
TBIP-Lā€¦-4FDI-4FDX
Safety Block I/O Module
2Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
V01.00 | 2020/07 3
Table of Contents
1 About These Instructions.................................................................................................................. ī€’5
1.1 Target groups................................................................................................................... ī€’5
1.2 Explanation of symbols used ........................................................................................ ī€’5
1.3 Additional documents.................................................................................................... ī€’5
1.4 Feedback about these instructions.............................................................................. ī€’5
2 Notes on the Product......................................................................................................................... ī€’6
2.1 Product identification..................................................................................................... ī€’6
2.2 Scope of delivery ............................................................................................................. ī€’6
2.3 Manufacturer and service.............................................................................................. ī€’6
3 For Your Safety.................................................................................................................................... ī€’7
3.1 Intended use..................................................................................................................... ī€’7
3.1.1 Reasonably foreseeable misuse.................................................................................................. ī€¬7
3.2 General safety notes ....................................................................................................... ī€’8
3.3 Residual risks (EN ISO 12100:2010).............................................................................. ī€’8
3.4 Warranty and liability ..................................................................................................... ī€’8
3.5 Directives and standards ...............................................................................................ī€’9
3.5.1 National and international directives and standards ......................................................... ī€¬9
3.5.2 Cited standards................................................................................................................................. ī€¬9
4 Product Description .........................................................................................................................ī€’10
4.1 Device overview ............................................................................................................ī€’10
4.1.1 Type label..........................................................................................................................................ī€¬10
4.2 Properties and features................................................................................................ī€’11
4.2.1 Switches and connectors............................................................................................................ī€¬11
4.2.2 Block diagram..................................................................................................................................ī€¬12
4.3 Functions and operating modes ................................................................................ī€’12
4.3.1 Safety Function...............................................................................................................................ī€¬12
4.3.2 Safety inputs (FDI)..........................................................................................................................ī€¬12
4.3.3 Safety outputs (FDO) ....................................................................................................................ī€¬13
4.3.4 Configuration memory ................................................................................................................ī€¬13
5 Mounting............................................................................................................................................ī€’14
5.1 Grounding the device...................................................................................................ī€’14
5.1.1 Equivalent wiring diagram and shielding concept ...........................................................ī€¬14
5.1.2 Shielding of the fieldbus and I/O level...................................................................................ī€¬15
5.1.3 Grounding the device ā€“ I/O level and fieldbus level.........................................................ī€¬15
6 Connecting ........................................................................................................................................ī€’17
6.1 Connecting the M12 connectors ................................................................................ī€’17
6.2 Connecting the device to Ethernet............................................................................ī€’18
6.3 Connecting the power supply ....................................................................................ī€’19
6.3.1 24 V Supply (SELV/PELV)..............................................................................................................ī€¬20
6.4 Connecting safe sensors and actuators ....................................................................ī€’21
6.5 Switching examples......................................................................................................ī€’23
6.5.1 Inputs..................................................................................................................................................ī€¬23
6.5.2 Outputs..............................................................................................................................................ī€¬24
7 Commissioning .................................................................................................................................ī€’25
7.1 Initial commissioning ...................................................................................................ī€’25
Table of Contents
4Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
7.1.1 Mounting and electrical installation.......................................................................................ī€¬25
7.1.2 Configuring in Turck Safety Configurator.............................................................................ī€¬25
7.1.3 Commissioning the device at the PLC....................................................................................ī€¬25
7.2 Safety planning..............................................................................................................ī€’26
7.2.1 Prerequisites ....................................................................................................................................ī€¬26
7.2.2 Reaction time ..................................................................................................................................ī€¬26
7.2.3 Safety characteristic data............................................................................................................ī€¬26
7.3 Setting the IP address...................................................................................................ī€’27
8 Configuring........................................................................................................................................ī€’29
8.1 Installing Turck Safety Configurator..........................................................................ī€’29
8.2 Licensing Turck Safety Configurator .........................................................................ī€’29
8.3 Creating a configuration with the TSC commissioning wizard ............................ī€’29
8.3.1 Creating a new workspace .........................................................................................................ī€¬29
8.3.2 Selecting a master and creating a basic configuration....................................................ī€¬30
8.3.3 Adapting the configuration of the safe channels ..............................................................ī€¬33
8.4 Loading the configuration with the TSC commissioning wizard.........................ī€’39
8.5 Application example ā€“ configuring a safety function in TSC................................ī€’45
8.5.1 Checking and loading the configuration ..............................................................................ī€¬51
8.6 Configuring single channel safety sensors...............................................................ī€’52
8.7 Configuring the device at EtherNet/IP in Rockwell Studio 5000..........................ī€’55
8.7.1 Used Hardware ...............................................................................................................................ī€¬55
8.7.2 Used Software.................................................................................................................................ī€¬55
8.7.3 Scanning the network in RSLinx...............................................................................................ī€¬56
8.7.4 Creating a new project in Studio 5000...................................................................................ī€¬57
8.7.5 Opening the catalog file..............................................................................................................ī€¬59
8.7.6 Configuring the device in Logix Designer ............................................................................ī€¬61
9 Operating ...........................................................................................................................................ī€’73
9.1 LED displays....................................................................................................................ī€’73
9.2 Status- and control word .............................................................................................ī€’74
9.3 Process input data.........................................................................................................ī€’75
9.4 Process output data......................................................................................................ī€’78
9.5 Using the configuration memory...............................................................................ī€’79
9.5.1 Storing a configuration................................................................................................................ī€¬79
9.5.2 Loading a configuration from the memory chip................................................................ī€¬79
9.5.3 Deleting the memory chip (Erase Memory) .........................................................................ī€¬79
9.5.4 Configuration transfer and module behavior .....................................................................ī€¬81
9.6 Reset the device to factory settings (factory reset) ................................................ī€’81
10 Restarting after Device Exchange or Modification ....................................................................ī€’82
10.1 Changing a device.........................................................................................................ī€’82
10.1.1 Prerequisites for device replacement.....................................................................................ī€¬82
10.1.2 Procedure for device replacement..........................................................................................ī€¬82
11 Maintenance......................................................................................................................................ī€’83
12 Decommissioning.............................................................................................................................ī€’84
13 Disposal ..............................................................................................................................................ī€’84
14 Technical Data...................................................................................................................................ī€’85
14.1 General technical data..................................................................................................ī€’85
14.2 Technical data ā€“ safety inputs.....................................................................................ī€’86
14.3 Technical data ā€“ safety outputs..................................................................................ī€’87
V01.00 | 2020/07 5
1 About These Instructions
These operating instructions describe the structure, functions and the use of the product and
will help you to operate the product as intended. These instructions contain rules for the use of
the devices in Safety Instrumented Systems (SIS). The assessment of the safety related values is
based on IECī€¬61508, ISOī€¬13849-1 and IECī€¬62061.
Read these instructions carefully before using the product. This is to avoid possible damage to
persons, property or the device. Retain the instructions for future use during the service life of
the product. If the product is passed on, pass on these instructions as well.
1.1 Target groups
These instructions are directed to qualified personnel or technically trained personnel (planer,
developer, design engineer, installer, electrical specialist, operator, maintenance personnel etc.)
and must be carefully read by anyone anyone who assembles, commissions, operates, main-
tains, dismantles or disposes of the device.
1.2 Explanation of symbols used
The following symbols are used in these instructions:
DANGER
DANGER indicates a dangerous situation with high risk of death or severe injury if
not avoided.
WARNING
WARNING indicates a dangerous situation with medium risk of death or severe in-
jury if not avoided.
CAUTION
CAUTION indicates a dangerous situation of medium risk which may result in minor
or moderate injury if not avoided.
NOTICE
NOTICE indicates a situation which may lead to property damage if not avoided.
NOTE
NOTE indicates tips, recommendations and useful information on specific actions
and facts. The notes simplify your work and help you to avoid additional work.
uCALL TO ACTION
This symbol denotes actions that the user must carry out.
aRESULTS OF ACTION
This symbol denotes relevant results of actions.
1.3 Additional documents
The following additional documents are available online at www.turck.com:
nData sheet
nEU Declaration of Conformity
1.4 Feedback about these instructions
We make every effort to ensure that these instructions are as informative and as clear as pos-
sible. If you have any suggestions for improving the design or if some information is missing in
the document, please send your suggestions to [email protected].
Notes on the Product
Manufacturer and service
6Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
2 Notes on the Product
2.1 Product identification
These instructions apply for the following full safety module with CIP Safety:
nTBIP-Lā€¦-4FDI-4FDX
2.2 Scope of delivery
The scope of delivery includes:
nTBIP-Lā€¦-4FDI-4FDX
nM12 closure caps
n7/8ā€™ā€™ blind caps (not suitable to guarantee IP67/IP69K)
2.3 Manufacturer and service
Hans Turck GmbH & Co. KG
WitzlebenstraƟe 7
45472 MĆ¼lheim an der Ruhr
Germany
Turck supports you with your projects, from initial analysis to the commissioning of your applic-
ation. The Turck product database contains software tools for programming, configuration or
commissioning, data sheets and CAD files in numerous export formats. You can access the
product database at the following address: www.turck.de/products
For further inquiries in Germany contact the Sales and Service Team on:
nSales: +49 208 4952-380
nTechnology: +49 208 4952-390
Outside Germany, please contact your local Turck representative.
V01.00 | 2020/07 7
3 For Your Safety
The product is designed according to state-of-the-art technology. However, residual risks still
exist. Observe the following warnings and safety notices to prevent damage to persons and
property. Turck accepts no liability for damage caused by failure to observe these warning and
safety notices.
3.1 Intended use
These devices are designed solely for use in industrial areas.
TBIP-Lā€¦-4FDI-4FDX is a decentralized safety module for CIP Safety. The module collects field
signals and forwards them safely to a CIP Safety master. Thanks to an extended temperature
range from -40ā€¦+70 Ā°C and IP67/IP69K protection, the module can be used directly on the ma-
chine.
The module serves for controlling signal devices as for example emergency stop buttons, posi-
tion switches or OSSDs which are used to ensure human, material or machine protection.
TBIP-Lā€¦-4FDI-4FDX can be used in the following applications:
napplications up to SIL 3 (according to IEC 61508)
napplications up to SIL CL3 (according to EN 62 061)
napplications up to Category 4 and Performance Level e (according to EN ISO 13 849-1)
The devices may only be used as described in these instructions. Any other use is not in accord-
ance with the intended use. Turck accepts no liability for any resulting damage.
3.1.1 Reasonably foreseeable misuse
The device is not suitable for:
nThe use in explosive areas
nOutdoor use
nThe permanent use in liquids
Modifications to the device
It is not permitted to modify the technical function or the construction of the device.
For Your Safety
Warranty and liability
8Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
3.2 General safety notes
nThe device may only be assembled, installed, operated, parameterized and maintained by
professionally-trained personnel.
nThe device may only be used in accordance with applicable national and international regu-
lations, standards and laws.
nThe device only meets the EMC requirements for industrial areas and is not suitable for use
in residential areas.
nThe Performance Level as well as the safety category according to EN ISO 13849-1 depend
on the external wiring, the application, the choice of the control devices as well as their ar-
rangement on the machine.
nThe user has to execute a risk assessment according to EN ISO 12100:2010.
nBased on the risk assessment a validation of the complete plant/machine has to be done in
accordance with the relevant standards.
nOperating the device beyond the specification can lead to malfunctions or to the destruction
of the device. The installation instructions must be observed.
nFor trouble-free operation, the device must be properly transported, stored, installed and
mounted.
nFor the release of safety circuits in accordance with EN IEC 60204-1, EN ISO 13850 only use
the output circuits of connectors C4ā€¦C7.
nChange the default password of the integrated web server after the first login. Turck recom-
mends using a secure password.
3.3 Residual risks (EN ISO 12100:2010)
The wiring proposals described in the following have been tested under operational conditions
with the greatest care. Together with the connected periphery of safety related equipment and
switching devices they fulfill relevant standards.
Residual risks remain, if
nthe proposed wiring concept is is changed and connected safety related devices or protect-
ive devices are possibly not or insufficiently included in the safety circuit.
nthe operator does not observe the relevant safety regulations specified for the operation, ad-
justment and maintenance of the machine. Here, the inspection and maintenance intervals
for the machine should be strictly observed.
Failure to follow these instructions can result in serious injury or equipment damage.
3.4 Warranty and liability
Any warranty and liability is excluded for:
nimproper application or not intended use of the product
nnon-observance of the user manual
nmounting, installation, configuration or commissioning by unqualified persons
V01.00 | 2020/07 9
3.5 Directives and standards
Manufacturers and operators of machines and plants in which the device is used are respons-
ible for observing all relevant directives and standards.
3.5.1 National and international directives and standards
The following guidelines and regulations must be observed:
n2006/42/EG (machine directive )
n2014/30/EU (electromagnetic compatibility)
n2011/65/EU (RoHS Directive)
n89/655/EWG (work equipment directive)
nAccident prevention regulation
nSafety rules and safety regulations according to the actual state of the art
3.5.2 Cited standards
Standard Title
DIN EN ISO 13849-1:2016-06 Safety-related parts of control systems
EN 62061:2005 + Cor.:2010 + A1:2013 + A2:2015
IEC 62061:2005 + A1:2012 + A2:2015
Safety of machinery - Functional safety of
safety-related electrical, electronic and
programmable electronic control systems
DIN EN 61508:2011
IEC 61508:2010
Functional safety of electrical/electronic/
programmable electronic safety-related
systems
DIN EN 61131-2:2008
IEC 61131-2:2007
Programmable controllers
EN ISO 12100:2010
DIN EN ISO 12100:211-03
Safety of machinery - General principles
for design - Risk assessment and risk re-
duction
Product Description
Device overview
10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
4 Product Description
TBIP-Lā€¦-4FDI-4FDX is a safety block I/O module for CIP Safety via EtherNet/IP. The device has
four 2-channel digital safety inputs (FDI) for the connection of different safety sensors as for ex-
ample light barriers or emergency stop buttons. Four further safety channels (FDX) can be
freely used as inputs (FDI) or outputs (FDO).
The configuration of the safe I/Os and their function is realized by means of a software tool the
Turck Safety Configurator.
4.1 Device overview
218 [8.58]
230.5 [9.08]
C4C5C6C7
6.3 [0.25]
38.8 [1.53]
60.4 [2.38]
C0C1C2C3
24 [0.95]
30.2 [1.19]
X2
X1
P2
P1
red
Fig.ī€¬1: TBIP-L4-4FDI-4FDX
218 [8.58]
230.5 [9.08]
C4C5C6C7
6.3 [0.25]
38.8 [1.53]
60.4 [2.38]
C0C1C2C3
24 [0.95]
30.2 [1.19]
X2
X1
P2
P1
red
Fig.ī€¬2: TBIP-L5-4FDI-4FDX
4.1.1 Type label
TBIP-L4-4FDI-4FDX
Ident-No.: 100001827
HW:
Charge code:
YoC:
Hans Turck GmbH & Co. KG
D-45466 MĆ¼lheim a. d. Ruhr
www.turck.com
Made in Germany
TBIP-L5-4FDI-4FDX
Ident-No.: 100001828
HW:
Charge code:
YoC:
Hans Turck GmbH & Co. KG
D-45466 MĆ¼lheim a. d. Ruhr
www.turck.com
Made in Germany
Fig.ī€¬3: Type label TBIP-L4-4FDI-4FDX Fig.ī€¬4: Type label TBIP-L5-4FDI-4FDX
V01.00 | 2020/07 11
4.2 Properties and features
nFour safety-related SIL3 inputs FDI
nFour safety-related SIL3 in-/outputs FDX
nSafe PP/PM-switching of the actuator power supply
nUsable in SIL CL3 according to EN 62061 or PLe according to DIN EN ISO 13849-1
n7/8ā€™ā€™ power supply connectors
nTwo 4-pole M12-connectors for Ethernet
nMultiple LEDs for status indication
nIntegrated Ethernet switch, allows line topology
nIntegrated web server
nTransmission rate 10 Mbps and 100 Mbps
nFiberglass reinforced housing
nShock and vibration tested
nFully potted module electronics
nProtection class IP65/IP67/IP69K
4.2.1 Switches and connectors
TBIP-Lā€¦-4FDI-4FDX
Meaning
C4
C5
C6
C7
C0
C1
C2
C3
X2X1
P2
P1
FE
IP Address
X1 Power IN
TBIP-L4-4FDI-4FDX: 4 pole
TBIP-L5-4FDI-4FDX 5-pole
X2 Power OUT
TBIP-L4-4FDI-4FDX: 4 pole
TBIP-L5-4FDI-4FDX 5-pole
C0 FDI0/1, safety-related input
C1 FDI2/3, safety-related input
C2 FDI4/5, safety-related input
C3 FDI6/7, safety-related input
C4 FDX8/9, safety-related in-/output
C5 FDX10/11, safety-related in-/output
C6 FDX12/13, safety-related in-/output
C7 FDX14/15, safety-related in-/output
IP address Rotary coding switch for address setting (last byte
of the IP address for the safe functional unit)
P1 Ethernet 1
P2 Ethernet 2
FE Functional earth
Product Description
Functions and operating modes
12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
4.2.2 Block diagram
4
2
C0
V1
4
2
C1
4
2
1
5
1
5
1
5
1
5
C2
4
2
4
2
4
2
4
2
1
5
1
5
1
5
1
5
4
2
C3
C4
C5
C6
C7
4
3
4
3
4
3
4
3
V2
Safety
FDI
0/1
Safety
FDX
8/9
Safety
FDI
2/3
Safety
FDX
10/11
Safety
FDI
4/5
Safety
FDX
12/13
Safety
FDX
14/15
Safety
FDI
6/7
Fig.ī€¬5: Block diagram TBIP-Lā€¦-4FDI-4FDX
4.3 Functions and operating modes
4.3.1 Safety Function
The TBIP-Lā€¦-4FDI-4FDX provides four safe digital SIL3 inputs (FDI) and four SIL3-connectors
(FDX), configurable as inputs or outputs.
The following devices can be connected to the safety inputs:
n1- and 2-channel safety switches and sensors
nContact based switches, e.g. emergency switches, protective door switches
nSensors with OSSD switching outputs
nAntivalently switching OSSD sensors
The four safe SIL3 outputs can be used PP- or PM-switching.
Safe status
In the safe state the device outputs are in LOW-state (0). The inputs report a LOW-state (0) to
the logic.
Fatal error
nIncorrect wiring at the output (i.e. capacitive load, energetic recovery)
nShort-circuit at the line control output T2
nIncorrect power supply
nStrong EMC disturbances
nInternal device error
4.3.2 Safety inputs (FDI)
The safe inputs are suitable for the connection of safety-related sensors:
nMax. eight 2-channel safety switches and sensors
nContact based switches, e.g. emergency switches, protective door switches
nSensors with OSSD switch outputs with test pulses
nSensors with OSSD switch outputs without test pulses
V01.00 | 2020/07 13
Error detection and diagnostics
Internal:
nDevice self test: Diagnosis of internal device errors
External:
nCross connection diagnosis: The device detects a cross connection between the sensor sup-
plies at the inputs or between one sensor supply to another potential (if the test pulses are
activated)
nDiscrepancy diagnosis: for 2-channel inputs
nShort-circuit diagnosis
Parameters
For each input the following types can be selected:
nSafe input for potential free contacts (NC/NC)
nSafe antivalent input for potential free contacts (NC/NO)
nSafe electronic input at OSSD-output with test pulses
4.3.3 Safety outputs (FDO)
The safe SIL3 outputs can be used PP- or PM-switching.
nMax. four 2-channel safety output (outputs are supplied via V1)
Error detection and diagnostics
Internal:
nDevice self test: Diagnosis if an output can not change to the safe state due to an internal er-
ror.
External:
nOverload diagnosis
nCross connection diagnosis
nShort-circuit diagnosis
Parameters
nSafe output PP-switching:
Safe output, the load is connected between P-terminal and Ground-terminal.
nSafe output PM-switching:
Safe output, the load is connected between P-terminal and M-terminal (mass), necessary for
special loads which need a separation from Ground.
4.3.4 Configuration memory
A pluggable memory stick is included in the scope of delivery of TBIP-Lā€¦-4FDI-4FDX. It serves
for storing the safety function configured via Turck Safety Configurator. It allows to transfer the
configuration of one device to another device, e. g. for device exchange.
Mounting
Grounding the device
14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
5 Mounting
NOTICE
Mounting on uneven surfaces
Device damage due to stresses in the housing
ī€ƒFix the device on a flat mounting surface.
ī€ƒUse two M6 screws to mount the device.
The device can be screwed onto a flat mounting plate.
ī€ƒAttach the module to the mounting surface with two M6 screws. The maximum tighten-
ing torque for the screws is 1.5 Nm.
ī€ƒAvoid mechanical stresses.
ī€ƒOptional: Ground the device.
218 [5.58]
M6 (2x)
max. 1.5 Nm
Fig.ī€¬6: Mounting the device onto a mounting plate
5.1 Grounding the device
5.1.1 Equivalent wiring diagram and shielding concept
1 nF
2,2 Mā„¦
X1
C0
C1
C2
C3
P1
X2
C4
C5
C6
C7
P2
4 x 15 nF
Fig.ī€¬7: Equivalent wiring diagram and shielding
concept
V01.00 | 2020/07 15
5.1.2 Shielding of the fieldbus and I/O level
The fieldbus and the I/O level of the modules can be grounded separately.
1
2
3
Fig.ī€¬8: Grounding clip (1), grounding ring (2) and metal screw (3)
The grounding ring (2) is the module grounding. The shielding of the I/O level is permanently
connected to the module grounding. The module grounding is only connected to the refer-
ence potential of the installation when the module is mounted.
Shielding concept of the I/O modules (I/O level)
In the case of direct mounting on a mounting plate, the module grounding is connected to the
reference potential of the system via the metal screw in the lower mounting hole (3). If module
grounding is not desired, the electrical connection to the reference potential must be interrup-
ted, e.g. by using a plastic screw.
Shielding concept of the fieldbus level
On delivery, a grounding clip is provided on the connectors for the fieldbus connection.
When mounted directly on a mounting plate, the shielding of the fieldbus cables is routed dir-
ectly to the module ground via the grounding clip and the metal screw in the lower mounting
hole.
If direct grounding of the fieldbus shield is not desired, the grounding clip must be removed. In
this case, the fieldbus shield is connected to the module ground via an RC element.
5.1.3 Grounding the device ā€“ I/O level and fieldbus level
The grounding of the fieldbus level can either be connected directly via the grounding clip (1)
or connected and routed indirectly via an RC element to the grounding of the I/O level. If the
grounding is to be routed via an RC element, the grounding clip must be removed.
1
2
3
Fig.ī€¬9: Grounding clamp (1)
Mounting
Grounding the device
16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Removing the grounding clip: Disconnect the direct grounding of the fieldbus level
ī€ƒUse a flat screwdriver to slide the grounding clamp forward and remove it.
Mounting the grounding clip: grounding the fieldbus level directly
ī€ƒPlace the grounding clamp between the fieldbus connectors by using a screwdriver in
such way that the clamp contacts the metal housing of the connectors.
ī€ƒThe shielding of the fieldbus cables is connected to the grounding clip.
Fig.ī€¬10: Mounting the grounding clip
Grounding the device ā€“ mounting on a mounting plate
ī€ƒFor mounting onto a mounting plate: Fix the Device with an M6 metal screw through the
lower mounting hole.
aThe shielding of the M12 flanges for the I/O level is connected to the reference potential
of the installation via the M6 metal screw.
aWith mounted grounding clip: The shielding of the fieldbus is connected to the reference
potential of the installation via the module grounding of the I/O level.
V01.00 | 2020/07 17
6 Connecting
WARNING
Intrusion of liquids or foreign bodies through leaking connections
Danger to life due to failure of the safety function
ī€ƒTighten M12 connectors with a tightening torque of 0.8 Nm.
ī€ƒAlways seal unused connectors with suitable screw caps or blind caps.
ī€ƒUse appropriate 7/8" sealing caps, e.g. type RKMV-CCC. The caps not part of the
scope of delivery.
6.1 Connecting the M12 connectors
ī€ƒWhen connecting the cables to the M12-connectors, use the torque screwdriver men-
tioned below.
Fig.ī€¬11: Torque screwdriver
Description Type Ident no.
Torque screwdriver,
torque range 0.4ā€¦1.0 Nm
nM8 (SW9)
nM12 for bus cables (SW13)
nM12 for sensor cables (SW14)
Torque-Wrench-Set
Turck Line + BUS
6936171
Connecting
Connecting the device to Ethernet
18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
6.2 Connecting the device to Ethernet
For the connection to Ethernet the device has an integrated auto-crossing switch with two 4-
pole, D-coded M12 x 1-Ethernet-connectors. The maximum tightening torque is 0.6 Nm.
Fig.ī€¬12: M12 Ethernet connector
ī€ƒConnect the device to Ethernet according to the pin assignment below.
v
4
13
2
P1, P2
1 = TX +
2 = RX +
3 = TX ā€“
4 = RX ā€“
ļ¬‚ange = FE
Fig.ī€¬13: Pin assignment Ethernet connectors
V01.00 | 2020/07 19
6.3 Connecting the power supply
For the connection to the power supply, the device has two 5-pin 7/8" connectors. The power
supply connectors are designed as 4-pole (TBIP-L4) or 5-pole (TBIP-L5) connectors. V1 and V2
are galvanically isolated. The maximum tightening torque is 0.8 Nm.
Fig.ī€¬14: TBIP-L4ā€¦ ā€“ 7/8ā€
connector for connecting the supply voltage
Fig.ī€¬15: TBIP-L5ā€¦ ā€“ 7/8ā€
connector for connecting the supply voltage
ī€ƒConnect the device to the power supply according to the pin assignment shown below.
w v
1
2
3
4
1 RD = 24 VDC V2
2 GN = 24 VDC V1
3 WH = GND V1
4 BK = GND V2
1
2
3
4
X1 X2
1 BK = GND V2
2 BU = GND V1
3 GNYE = FE
4 BN = 24 VDC V1
5 WH = 24 VDC V2
3
4
5
2
1
w v
3
4
5
2
1
X1 X2
Fig.ī€¬16: TBIP-L4-ā€¦ ā€“ pin assignment power
supply connectors
Fig.ī€¬17: TBIP-L5-ā€¦ ā€“ pin assignment power
supply connectors
Connector Function
X1 Power feed
X2 Continuation of the power to the next node
V1 System voltage: Supply voltage 1 (incl. supply of electronics)
V2 Load voltage: Power supply 2
NOTE
The system voltage (V1) and the load voltage (V2) are fed in and monitored separ-
ately. In case of an undercut of the admissible voltage, the connectors are switched-
off according to the module's supply concept. In case of an undervoltage at V2, the
LED PWR changes from green to red. In case of an undervoltage at V1, the LED PWR
is turned off.
Connecting
Connecting the power supply
20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
6.3.1 24 V Supply (SELV/PELV)
WARNING
Incorrect or defective power supply unit
Danger to life due to dangerous voltages on touchable parts
ī€ƒOnly use SELV or PELV power supplies in accordance with EN ISO 13849-2, which
allow a maximum of 60 VDC or 25 VAC in the event of a fault.
External supply of sensors and actuators
Sensors and actuators with external power supply can also be connected to
TBIP-Lā€¦-4FDI-4FDX. The use of SELV or PELV power supplies must also be guaranteed for
externally supplied sensors and actuators.
Decoupling of external electrical circuits
Decouple circuits that are not designed as SELV or PELV systems by means of optocouplers, or
other measures.
WARNING
Potential differences
Dangerous additions of voltages
ī€ƒAvoid potential differences between internal and external load voltage supplies
(24 V DC).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

turck TBIP-L4-4FDI-4FDX Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI