Johnson Controls FC-2000 Installing Instruction

Category
Fire protection
Type
Installing Instruction

This manual is also suitable for

FC-2000 Technical Manual 406
Installation Section
Technical Bulletin
Issue Date 0794
© 1994 Johnson Controls, Inc.
1
Order No. 406-020
Introduction Page 3
Description 3
Key Features 4
Minimum System Configurations 4
NFPA Standards 5
UL Documents 6
Other Standards and Documents 6
Installation 9
Installation Outline 10
Cabinet Installation 12
Trim Ring for CAB-x3 Enclosures 15
CAB-x3 Door Assembly 16
Installing the CHS-4 Chassis 19
Installing the AVPS-24 21
Mounting the Main Power Supply in the Cabinet 22
Mounting the ARM-4 Auxiliary Relay Module 23
Mounting Optional Module Expanders 26
Mounting Modules in the Chassis 27
Mounting the CPU-2000 28
Connecting Row Ribbon Cables to Modules 29
Field Wiring the Modules 31
Field Wiring the CPU-2000 32
Dummy-Loading Unused CPU-2000 Circuits 33
Connecting the RS-485 Interface 34
Typical NFPA Style B Initiating Device Circuit 35
Installing the FC-2000
2 Installation—Installing the FC-2000
Typical NFPA Style D Initiating Device Circuit
Page
37
Typical NFPA Style Y and Z Indicating Appliance Circuit 39
Field Wiring of the Control Relay Module (CRM-4) and Control Relay
Expander (CRE-4) 40
Power Supplies 41
MPS-24A Main Power Supply 41
Installing an Optional Main Power Meter 45
MPS-24B Main Power Supply 47
Applications 53
Waterflow Alarm 53
Supervisory Service 53
Central Station 54
Proprietary Protective Signaling 54
Transmitters 54
Digital Communicators 55
Tee-Tapping 58
4-Wire Smoke Detectors 59
Indicating Appliance Circuit Current Limitations 60
Remote Command Inputs 63
Remote Presignal Inhibit, All Call (General Alarm), Emergency Alert, Acknowledge,
Signal Silence, and System Reset Switches 65
Telephone Paging 68
Testing the System 71
Acceptance Test 71
Periodic Testing and Service 71
Operational Checks 71
Battery Checks and Maintenance 73
Calculating Power Supply Requirements 75
AC Branch Circuit 75
Main Power Supply 75
Installation—Installing the FC-2000 3
Introduction
The FC-2000 is an expandable multi-zone Fire Alarm Control Panel
designed with maximum flexibility and modularity as a basic requirement.
The heart of the system is the Central Processor Unit (CPU-2000) module,
which monitors and directs the actions of all other modules in the system.
Fifteen other modules may be installed in various configurations. Internal
communications are accomplished over a high-speed serial bus.
The CPU-2000 is provided with the Basic Equipment package. This
module provides two Style Z and/or Style Y indicating appliance circuits,
Form-C alarm and trouble contacts, remote station alarm and trouble
outputs, and a municipal central box output.
A Main Power Supply (MPS-24A or MPS-24B) and an Indicating Zone
Module (IZM-8) must be added to make the basic system functional.
The basic system can be expanded using one or more of the following
optional modules or boards:
IZM-8 Initiating Zone Module
IZE-A Initiating Zone Expander
ICM-4 Indicating Circuit Module
ICE-4 Indicating Circuit Expander
AVPS-24 Audio Visual Power Supply
CRM-4 Control Relay Module
CRE-4 Control Relay Expander
ARM-4 Auxiliary Relay Module
VCM-4 Voice Control Module
VCE-4 Voice Control Expander
DCM-2 Dual Channel Module
TCM-2 Time Control Module
TCM-4 Time Control Module
AIM-200 Addressable Intelligent Module
FFT-7 Fire Fighter’s Telephone
AMG-1 Audio Message Generator
Description
4 Installation—Installing the FC-2000
System expansion must comply with the:
physical limitations of the cabinet configuration
electrical limitations of the system power supply
capacity of the secondary power source (standby batteries)
See this section for a description of the various optional modules, and the
Installation section of this document for installation information.
The FC-2000 has the following important features:
Distributed microprocessor electronics using latest technology
Field programmable in minutes using front panel touch switches
Large system capacity, conventional or addressable/intelligent devices
Voice alarm options with solid state messages
Extensive line of serial annunciators
Manual On/Off/Disable control for all indicating appliance circuits
and control relays
Plug-in terminal blocks for ease of field wiring
Walk test any portion of system while remainder provides fire
protection
Liquid crystal display and printer options
The following FC-2000 components are required for compliance with
NFPA standards 71 and 72:
1. BE-2000 Basic Equipment Package, which includes:
CPU-2000 Central Processor Module, VP-1 Vented Dress Panel,
BP-3 Battery Dress Panel, CHS-4 Chassis, interconnecting cables,
and instruction manuals
2. An IZM-8 Initiating Zone Module for up to eight Style B initiating
device circuits or an AIM-200 Addressable Intelligent Module for up
198 addressable devices
3. Main Power Supply (MPS-24A or MPS-24B)
4. Standby Batteries--Refer to the Calculating Power Supply
Requirements section of this document.
5. Cabinet (CAB-A3, B3, C3 or D3)
Key Features
Minimum
System
Configurations
Installation—Installing the FC-2000 5
In addition, the following equipment is required for the specific NFPA
standards listed below:
An NFPA-72 Remote Station Protected Premises Control Unit requires:
6. Sprinkler Supervisory service requires a CRM-4 Control Relay
Module and a cable assembly (Part No. 71270). Refer to the
Applications section of this document.
An NFPA-72 Proprietary Protected Premises Control Unit requires:
6. NIB-96 Network Interface Board. Refer to the Applications section of
this document. Not for sprinkler supervisory service.
An NFPA-71 Central Station Protected Premises Control Unit requires:
6. 911A Digital Alarm Communicator. Refer to the Applications section
of this document.
7. Sprinkler Supervisory and/or Waterflow Alarm service requires a
CRM-4 Control Relay Module. Refer to the Applications section of
this document.
An NFPA-72 Emergency Voice/Alarm Communication System requires:
6. VTCC-1, VCC-2 or VTCC-2 Voice/Telephone Command Center for
a voice evacuation system
7. AA-120 Audio Amplifier
8 VCM-4 Voice Control Module for up to four speaker or telephone
circuits or DCM-4 Dual Channel Module
Before proceeding, the installer should be familiar with the following
standards (as appropriate):
NFPA 71 Installation, Maintenance, and Use of Central Station
Signaling Systems
NFPA 72 Installation, Maintenance, and Use of Local, Auxiliary,
Remote Station, and Proprietary Protective Signaling Systems
NFPA 72 Emergency Voice Alarm Service
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance, and Use of Indicating Appliances
for Protective Signaling Systems
NFPA 72 Testing Procedures for Signaling Systems
NFPA
Standards
6 Installation—Installing the FC-2000
Before proceeding, the installer should be familiar with the following
documents (as appropriate):
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers--Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling
Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
RS-232D Serial Interface Standards
RS-485 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
In addition, you must adhere to the standards of the applicable local and
state building codes and requirements of the local Authority Having
Jurisdiction (AHJ).
UL Documents
Other
Standards and
Documents
Installation—Installing the FC-2000 7
Figure 1: Physical Configuration Options
Note: The ARM-4 must be mounted under or in a position adjacent to its
associated CRM-4 or CRE-4.
ARM-4 ARM-4
DCM-4
ARM-4
IZE-A
IZM-8
Permissible Position Sharing Combinations
ARM-4
ICM-4
OR
TCM-2
OR
TCM-4
OR
VCM-4
ARM-4
CRE-4
CRM-4
or
AVPS-24
or
AVPS-24
or
AVPS-24
configop
CPU-2000
VCE-4, CRE-4 or ICE-A
8 Installation—Installing the FC-2000
Installation—Installing the FC-2000 9
Installation
Modules in the system communicate with the CPU through a common
ribbon cable connection.
aim200up
Figure 2: Module Connection Example
10 Installation—Installing the FC-2000
The following procedure outlines the installation and field wiring of the
FC-2000’s modules and refers to illustrations in the Installation, Field
Wiring the Modules, and Power Supplies sections of this document. This
procedure, and its diagrams and instructions, must be followed closely to
avoid damage to the control panel and its associated equipment. To a
great extent, reliability depends upon proper installation and maintenance.
1. Cabinet--Mount the cabinet and draw all field wiring through the
knockouts provided (Figure 3). Ensure that the cabinet is properly
grounded to earth.
Note: If the door is to be hung on the left side, mount door hardware
now. The MPS-24A/MPS-24B rests on the lower door mount.
Do not draw wiring into the bottom nine inches of the cabinet,
or conflict with the power supply and batteries may result.
2. Chassis--Mount all chassis. Refer to Figures 12 and 13 for
installation of the CHS-4 and CHS-4L chassis.
3. Main Power Supply--Mount the main power supply to the cabinet as
illustrated in Figure 15. Do not wire anything at this time!
4. Audio Visual Supplies--If any optional Audio Visual Power Supplies
(AVPS-24) are to be employed, mount them to the chassis. Refer to
Figure 14 for mounting of the AVPS-24 to the CHS-4.
5. Audio Visual Cables--Connect the AVPS trouble cable(s). Connect
the auxiliary bell power harness to the AVPS-24. Refer to Figure 36
to connect these cables.
6. Auxiliary Relay Modules--If any optional Auxiliary Relay Modules
(ARM-4) are to be employed, mount them to the chassis as illustrated
in Figure 16.
7. Preliminary System Wiring--The main power supply and any
AVPS-24s or ARM-4s should be wired at this time while the
terminals are readily accessible. Refer to the Power Supplies section
of this document to wire the MPS-24A/B, the AVPS-24s (see
Figure 36) and any ARM-4s (see Figure 22).
8. Module Ribbon Cables--Connect the first row ribbon cable to the
CPU as illustrated in Figure 17. For each additional row of modules
installed in the cabinet, connect an expander row ribbon cable to the
CPU.
9. CPU-2000--Install the CPU module in the top left cabinet position as
illustrated in Figure 20. Connect the power ribbon and power harness
between the CPU and the main power supply as illustrated in
Figures 32 and 35.
10. Module Expander Boards--If optional expanders are to be used with
a module, install as illustrated in Figure 18.
Installation
Outline
Installation—Installing the FC-2000 11
11. Modules--Mount each module in its respective chassis position as
shown in Figure 19.
12. Field-wire each module, using the following figures for reference:
CPU-2000: Figures 23, 24, and 25
IZM-8 (Style B): Figure 26
IZM-8 (Style D): Figure 27
ICM-4/ICE-4: Figure 28
CRM-4/CRE-4: Figure 29
LCD-80, ACM-16AT/32A, ACM-8R, NIB-96, AA-30: Refer to the
Fire Management Accessories Manual (FAN 445).
TCM-2 and TCM-4: Refer to those documents in this manual.
VCM-4/VCE-4, DCM-4, AMG-1, FFT-7: For installation and field
wiring of voice alarm equipment, refer to the FC-2000 Fire Fighter’s
Command Center Technical Bulletin in this manual.
13. Power-on-check--Apply AC power to the system. Do not connect
the batteries at this time! To silence the audible trouble sounder, push
the ACKNOWLEDGE switch on the CPU. The system should reflect
the following status:
On the CPU:
Green AC POWER indicator is on.
SYSTEM TROUBLE and POWER FAILURE indicators will be
on due to the absence of batteries.
ANNUNCIATOR or MODULE TROUBLE indicator may light
shortly after AC power is applied (applies only to a system that has
not been previously configured).
On each module
The yellow trouble indicators may come on approximately
10 seconds after AC power is applied (applies only to a system
that has not previously been configured).
On each AVPS-24
The yellow trouble indicators will light due to the absence of
batteries.
On the MPS-24A/B
The BATTERY FAIL indicator will be on due to the absence of
batteries.
Failure of the AC POWER indicator, or the presence of indications
not mentioned above may suggest an installation problem. Carefully
review the installation instructions to isolate the source.
12 Installation—Installing the FC-2000
14. Programming--To configure and program the system for operation, refer
to the Programming the FC-2000 Technical Bulletin in this manual.
15. Batteries--Once the system has been programmed and is functional,
connect the batteries. Ensure that all indicators except AC POWER
are extinguished.
16. Testing--Fully field test the system by conducting the test procedure
in the Testing the System section of this document.
17. Dress Panels--Complete the installation by installing the cabinet door
first, followed by the Battery Dress Panel (BP-3), and finally,
installing all remaining dress panels (VP-1, DP-1, and the MP-1).
You may either surface or semi-flush mount the cabinet.
Mount the cabinet in a clean, dry, vibration-free area, using the four
holes provided in the back surface of the backbox.
Place the cabinet so that the top edge is 66 inches above the surface of
the finished floor. This procedure places the center of the control
panel keypad 60 inches above the finished floor.
CAB-C3
Mounting
Holes
bckbxmnt
Note: The lock for this
cabinet is mounted
on either the left or the
right side. Leave
3 inches clearance on
the side of the
backbox where the
lock is located.
Figure 3: Mounting the Cabinet Backbox
IMPORTANT: Unless you are familiar with the placement of
components within this backbox, use only the knockout
locations provided for conduit entry.
Cabinet
Installation
Mounting the
CAB-x3 Cabinet
Backbox
Installation—Installing the FC-2000 13
Figure 4: CAB-A3 and CAB-B3 Cabinets (inches)
24-1/8
20-1/8
24
19-1/2
4
16
11-9/32
1-5/8
2-1/4
5/16 dia.
20
2-1/16
8-5/8
2-9/16
CAB-A3
24-1/8
28-5/8
24
19-1/2
4
16
19-25/32
1-5/8
2-1/4
28-1/2
2-1/16
8-5/8
2-9/16
CAB-B3
5/16 dia.
8-5/8
5-5/32
5-5/32
cab-x3b1
14 Installation—Installing the FC-2000
Figure 5: CAB-C3 and CAB-D3 Cabinets (inches)
24-1/8
37-1/4
24
19-1/2
4
16
28-3/32
1-5/8
2-1/4
37-1/8
2-1/16
8-5/8
2-9/16
CAB-C3
5/16 dia.
8-5/8
8-5/8
24-1/8
45-7/8
24
19-1/2
4
16
37-1/32
1-5/8
2-1/4
45-3/4
2-1/16
8-5/8
2-9/16
CAB-D3
5/16 dia.
8-5/8
8-5/8
8-5/8
cab-x3b
5-5/32
5-5/32
Installation—Installing the FC-2000 15
The TR-x3 Trim Ring consists of four pieces and is used when semi-flush
mounting the CAB-x3 enclosure (where x is the cabinet size, ranging
from A to D).
Note: To semi-flush mount the cabinet, ensure ample room to allow the
door to swing fully open.
1. Place the top piece on the top of the backbox against the wall.
2. Mark the wall with the locations to drill holes using the trim ring as a
template.
3. Drill 3/16 inch diameter holes where marked. Holes should be drilled
to a depth of 1 inch.
4. Insert the provided wall anchors using a rubber mallet, tapping them
in until they are flush with the wall surface.
5. Secure the trim ring piece to the wall with the screws provided.
6. Repeat Steps 1-5 to install the left, right, and bottom trim ring pieces.
Install the bottom piece last.
Note: The side trim ring pieces should have the holes nearest to the edge
facing outward. See Figure 6.
TR-A3 = 19-5/8 in.
TR-B3 = 28-1/8 in.
TR-C3 = 36-3/4 in.
TR-D3 = 45-3/8 in.
trimring
Figure 6: Trim Ring Installation
Trim Ring for
CAB-x3
Enclosures
Installing the
Trim Ring
16 Installation—Installing the FC-2000
You may mount the hinges for the CAB-x3 doors on either the left or
right-hand sides of the cabinet. The following illustrations and text depict
a left-hand mounted example. For a right-hand mounting, simply
substitute right for left in the instructions.
cabx3aa0
Left-hand mounted door
Right-hand mounted door
Figure 7: Mounting the CAB-x3 Cabinet Door
IMPORTANT: Assemble the two hinges and two alignment tabs to the
backbox before you install any equipment. Installing
the chassis severely limits space in the areas where the
hinges and alignment tabs are installed.
CAB-x3 Door
Assembly
Installation—Installing the FC-2000 17
Follow the directions below for door assembly.
1. Insert door hinges into the top and bottom slots of the side you wish
to hinge (in this case, the left side). Secure the hinges to the studs in
the backbox with the nuts provided.
Threaded
Stud
Door Hinge
Bottom
Left Corner
cabx3aa1
Figure 8: Bottom Door Hinge Insertion
2. Insert the threaded stud into the bottom hinge first. Thread from the
bottom up. Place the grounding “star” washer on the stud. Place the
door’s lower corner onto this stud. Placing the door on the lower stud
first provides a place for the door to rest while you complete the
assembly, as shown above.
18 Installation—Installing the FC-2000
cabx3aa2
Threaded
Stud
Door Hinge
Small hole
faces outward.
Top
Left Corner
Figure 9: Top Door Hinge Insertion
3. Align the door on the backbox, so that the door sits directly under the
top hinge. Thread the remaining stud into the top hinge and through
the hole in the top of the door, as shown above. The door should now
swing freely.
4. Install the door alignment tabs in the unused slots on the backbox (top
and bottom). In the example below, the door was mounted on the left,
leaving the unused slots on the right. Secure the alignment tab to the
top PEM stud with the nut provided. These tabs align the door
correctly with the backbox and prevent the door from being “skewed”
open.
Figure 10: Door Alignment Tabs
Top
Right Corner
Door Alignment Tab
Bottom
Right Corner
Door Alignment Tab
cabx3aa3
Installation—Installing the FC-2000 19
5. Punch out the knockout for the door lock and install the lock
mechanism. Make sure you do this last, so that you knock out the
correct side.
Install
Lock Here
The lock mechanism as viewed in a
left-hinged mounting application.
The lock would be placed in the
right side of the door
(as shown below).
cabx3aa4
Open
Locked
Figure 11: Lock Mechanism Installation
To install a CHS-4, complete the following steps and refer to Figure 12.
1. Place the CHS-4 over the screw mounts on the cabinet.
2. Connect a grounding cable assembly (71073) to one of the screw
mounts.
3. Secure the assembly with the two nuts provided.
Repeat this procedure for each CHS-4 in the cabinet.
Installing the
CHS-4 Chassis
20 Installation—Installing the FC-2000
CHS-4 Chassis
chsmnt1
Connect the grounding cable between
the main power supply earth ground
terminals and at least one chassis.
Use Cable 71073
Figure 12: Installing the CHS-4 Chassis
The optional CHS-4L Chassis is used to mount an AMG-1 Audio Message
Generator, FFT-7 Fire Fighter’s Telephone, or AA-30 Audio Amplifiers in
the cabinet. To install a CHS-4L, complete the following steps and refer
to Figure 13.
1. Place the CHS-4L over the screw mounts on the cabinet.
2. Connect a grounding cable assembly (71073) to one of the screw
mounts.
3. Secure the assembly with the two nuts provided.
Repeat this procedure for each CHS-4L in the cabinet.
Use Cable 71073
chsmnt
Figure 13: Installing the CHS-4L Chassis
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84

Johnson Controls FC-2000 Installing Instruction

Category
Fire protection
Type
Installing Instruction
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI