IFC Networking—Metasys Intelligent Fire Network 3
Introduction
The Metasys® Intelligent Fire Network (MIFN) can be set up for
operation in two separate configurations. The Primary Reporting MIFN
utilizes the Fire OWS (Operator Workstation) and is defined in this
document (see Figure 1). The Secondary Reporting configuration (see
Figure 28) of the MIFN provides secondary (ancillary) reporting of alarm
and trouble conditions on a standard Operator Workstation (OWS). Unlike
the Primary configuration of the MIFN where the Fire OWS is
Underwriters Laboratories (UL) 864 UOJZ Listed as a Proprietary
Protective Signaling Station, the standard OWS in the Secondary
Reporting configuration is not UL Listed for fire alarm operation and only
serves as a Secondary annunciator for the MIFN. For example, in the
Primary configuration, the Fire OWS can reset the fire controllers.
However, in the Secondary Reporting configuration, the control of the fire
alarm panels is limited to viewing and adjusting detector sensitivity,
enabling or disabling alarm verification, and enabling or disabling
day/night sensitivity. The standard OWS communicating with
IFC-1010/2020 panels in the Secondary Reporting configuration of the
MIFN cannot acknowledge alarms, control fire points, or reset IFC panels.
All information in this document pertains to both the Primary Reporting
and the Secondary Reporting configuration unless indicated otherwise
(see the Secondary Reporting section of this document for the exceptions
and differences in configuration).
The Primary Reporting Metasys Intelligent Fire Network is an interface
that allows Intelligent Fire Controller (IFC) fire alarm system products and
the Fire OWS to communicate over a true peer-to-peer network while
meeting the requirements of UL 864 UOJZ and NFPA 72 for Local and
Proprietary Protective Signaling Systems.
Note: Proprietary systems as defined by the National Fire Protection
Association National Fire Alarm Code (NFPA 72) are installations
of fire alarm systems that serve contiguous and noncontiguous
properties under one ownership from a Proprietary Protective
Supervising Station located at the protected property. Trained,
competent personnel must be in constant attendance at the
supervising station. In addition, the Proprietary Protective
Supervising Station must be located in a fire-resistive, detached
building or in a suitable cutoff room where it is not exposed to the
hazardous part of the protected facility.
Application
Details