ICM Controls ICM105 Installation guide

Type
Installation guide
ICM105
DELAY ON MAKE
MPS00C
18-240 VAC/VDC, 2-Wire
Compressor Staging/
Startup Delay Timer
SPECIFICATIONS
Input
• Voltage: 18-240 VAC/VDC
• Frequency: 50-60 Hz
Output
Output Ratings:
– Maximum: 1.5 amps
– Minimum: 10 mA
– Inrush: 15 amps
Time Delay
.03-10 minutes adjustable
INSTALLATIONMODE OF OPERATION
Knob adjustable from .03-10 minutes
Simple 2-wire hookup for non-anticipator type systems
1. Disconnect power.
2. Connect terminals in series with the
starting device as shown in the wiring
diagram below.
3. Select the desired time delay.
4. Reapply power, check operation.
When power is applied to the input, the
time delay begins. After the time delay is
complete, the load energizes and remains
energized as long as power is applied. The
control is reset by removing power during or
after the time delay period.
TIMING DIAGRAM
0V
Load
Voltage
0V
Input
Voltage
Transfer
Load
Energized
Time Delay
Time
Time
WIRING DIAGRAM
Y
R
C
T’STAT Contactor
Compressor
Control
Transformer
Line
Voltage
7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com LII275-1
  • Page 1 1

ICM Controls ICM105 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI