Product Specification Sheet HD30.14
Answers for industry.
Heavy Duty Double Throw
Safety Switch
Type VBII, 30 Amp, Type 3R (Outdoor)
Catalog Max Shipping
Number AC Volts Description Weight (lbs)
DTF321R
2
240 Fusible, 3 Pole, 3 Wire 39
DTNF361R 600 Non-fusible, 3 Pole, 3 Wire 35
Catalog
240V 1Ø 240V 3Ø 480V 3Ø 600V 3Ø 250V DC
Number Std Max Std Max Std Max Std Max Std Max
DTF321R 1¹⁄₂ 33 7¹⁄₂ — — 5
DTNF361R 5 10 20 — 30 5
General Information
Horsepower Ratings
3
1
Lugs are aluminum alloy as standard. Optional copper body lugs are available.
2
Catalog number DTF321R accepts Class H fuses as standard and Class R fuses with kit HR21.
3
Dual horse ratings: Std - applies when non-time delay fuses are installed.
Max - applies when time-delay fuses are installed.
4
(2) required per switch (one for each of the two line bases).
Standards and Ratings
• UL Listed under file #E4776
Meets UL98 for switches and UL 50
for enclosures
• Suitable for use as Transfer
Equipment on optional standby
systems as defined by Article 702
of the NEC
• Meets NEMA Standard KS-1 for
enclosed switches (Type HD)
• Meets NEC wire bending space
requirements
Suitable for use as Service Equipment
Rated 10,000 AIC with Class H or
200,000 AIC when used with Class R
or J fuses (fuse ampere rating must
not exceed switch ampere rating)
Features
Quick-make and break switching
action
Visible blade, double break
construction
• Highly visible ON/OFF indication
Modular design allows quick and
easy replacement of parts
• Front removable lugs which can
easily be converted to copper body
or compression type lugs
Defeatable dual cover interlock
All copper current carrying parts
1
Tangential knockouts
Handle is padlockable in OFF position
Accessories
Catalog Number Description
HA161234 Auxiliary Switch (1-NO & 1 NC)
4
HA261234 Auxiliary Switch (2-NO & 2 NC)
4
HA361234 Low Voltage Auxiliary Switch
4
HG61234 Equipment Ground Lug Kit (two lugs provided)
HG261234 Isolated Equipment Ground Lug Kit
HP61 Fuse Puller (3 per kit, (2) kits required per switch)
HNC612 Neutral Kit
HR21 240 Volt Class R Fuse Clip Kit (3 fuse clips per kit,
(2) kits required per switch)
HLC612 Copper Lug Kit (9 lugs per kit)
4
HCL612 Compression Lug Neutral Barrier Kit
HS075 0.75” Type “HS” Outdoor Hub
HS100 1.00” Type “HS” Outdoor Hub
Product Specification Sheet #HD30.14 (page 2 of 2)
Catalog
Number Description
HFB21 Fusible 240 Volt Line Side Replacement Base (2) kits required per switch
HBB21 Fusible 240 Volt Load Side Replacement Base (2) kits required per switch
HFB612 Fusible 600 Volt Line Side Replacement Base (2) kits required per switch
HBB612 Fusible 600 Volt Load Side Replacement Base (2) kits required per switch
HNB612 Non-fusible Replacement Line Base (2) Kits required per switch
HHD61234 Replacement Handle/Handle Guard
HL612 Replacement Lugs (3 lugs per kit)
HM6123 Replacement Mechanism (2) kits required per switch
1
Replacement Door
Replacement Parts
Mechanical Lug Wire Ranges (60/75°C, Cu/Al)
Description Wire Range
Line, Load #12-6 AWG (Al) or
Neutral #14-6 AWG (Cu)
Ground #14-4 AWG
1
Catalog number is same as switch catalog number plus “DOOR” suffix.
2
If compression lugs are used for the neutral, order compression lug neutral barrier kit HCL612.
Compression Lugs (UL listed for field installation)
2
Wire
Burndy Thomas-Betts IIsco
Size CU Only CU/AL CU Only CU/AL CU Only CU/AL
60096
#14-10
60097
YA8C-L BOX 54104 60101 CRA-8 ACL-8
#8 YA8C-L1 BOX 54130 60102 ACN-8
61102
#6 61107
Catalog
Dimensions Wire Bending Space
Number A B C Top Bottom
DTF321R
29.14 23.50 29.63
4.75 7.50
(740) (597) (753)
DTNF361R
24.50 19.00 24.98
(622) (483) (634)
4.75 4.75
Dimension Drawing
C
L
2.09 (53)
Provision for HS
Type 3R Hub
B
2.44
(62)
6.75 (171)
3.375
(86)
C
L
(6) .268" (6.8)
diameter
mounting
holes
(2) knockouts
in back (1) in
each side for
1/2, 3/4 & 1"
conduit
1.65
(42)
1.65
(42)
.55 (14)
6.54
(166)
5.73
(146)
C
2.45
(62)
6.09
(155)
.94 (24)
.25(6)
2.06
(52)
16.44
(418)
Note: This
KO only
omitted on
Non-Fusible
Switches
.80 (20)
A
(OD Box
Less Cover)
1.13
(29)
This mounting
hole omitted
on DTNF361R
Dimensions and Wire Bending Space
Dimensions shown in inches and millimeters ( ).
Dimension shown accurate to
+
¹⁄₈ inch.
Enclosure: Galvanized Steel .053 Thick (17 Gauge)
Finish – ANSI Grey #61 Paint
11.65
(296)
C
L
2.00
(51)
2.00
(51)
(2) knockouts
for 1/2" conduit
(2) 1/2" knockouts
3.32
(84)
.97
(25)
1.00
(25)
1.00
(25)
9.53
(242)
1.69 (43)
(4) knockouts for
1/2, 3/4, 1" conduit
(62)
Siemens is a registered trademark of Siemens AG. Product names
mentioned may be trademarks or registered trademarks of their
respective copanies. Specifications subject to change without notice.
www.usa.siemens.com/switches
Siemens Industry, Inc.
Building Technologies Division
5400 Triangle Parkway
Norcross, GA 30092
1-800-964-4114
Subject to change without prior notice
All rights reserved
Printed in USA
© 2009 Siemens Industry, Inc.
/