Cooper Lighting Greengate OXC-P-1500-R, Extreme Temperature Sensors Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Cooper Lighting Greengate OXC-P-1500-R Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Eaton
Lighting Systems – Controls Products
203 Cooper Circle
Peachtree City, Georgia 30269
www.eaton.com/lightingsystems
Installation Instructions
Model # OXC-P-1500-R
Model # OXC-P-2MH0-R
Extreme Temperature PIR Sensor
10-26 VDC
• Readallinstructionsonbothsidesofthissheetrst
• Planallcomponentlocationscarefully
• InstallinaccordancewithALLlocalcodes
• ForusewithGreengateSwitchpacks&Greengate
Systems.Forusewithothersystems,contact
TechnicalSupport
• Forindooruseonly
• DONOTrunanyGreengatelowvoltagewiringinthe
sameconduitaspowerconductors
• ULlistedfordamplocations
Technology:PassiveInfrared(PIR)
Power Requirements:
Input:
• 10-26VDCfromGreengateSwitchpackor
Greengatesystem.Maximumcurrentneededis
25mApersensor
Output:
• Opencollectoroutputtoswitchuptoten
GreengateSwitchpacks
• IsolatedFormCRelay(-Rmodel)
• IsolatedFormCRelayRatings:1A,30VDC/VAC
Time Delays:
• Adjustabletimedelay
Ambient Light Features:
• Adjustabledowntoapproximately3LUX
Operating Environment:
• Temperature:-40°F–125°F(-40°C–52°C)
• RelativeHumidity:Lessthan95%non-condensing
• Indoororourdooruse
Housing:
• Mediumimpactinjectionmoldedhousing.ABS
resincomplieswithUL94V0.Paintableoff-white
Size:1-5/8”Hx4-1/2”Wx3-1/8”D
(41.3mmx114.3mmx79.4mm)
LED Indicators:RedLEDforPIRdetection
TheOXC-P-1500-RExtremeTemperatureandOXC-P-2MH0-RExtremeTemperatureHighBaySensoruses
passiveinfrared(PIR)technologywithtemperaturecompensatingcircuitrytocontrollightinginapplicationswhere
extremetemperatures/humiditymustbetolerated.Whenmotionisdetected,thebluewireiselectronicallyconnected
totheredwire,energizingtherelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,thebluewireis
disconnectedfromthered,causingtherelaytoopen,turningOFFtheload.Theredleadis+15VDCsupply,theblack
leadiscommon,andtheblueistherelaycontrol.
Time Delay:
Thesensorhasselectabletimedelayoptions(Auto,5,15,20minutes)
BAS Interface:
ThesensorhasanisolatedFormCrelayforBASinterface.
Ambient Lights Control Circuit:
UsetheAmbientLightscontrolslocatedontheDIPswitchtoselectthefoot-candlelevelatwhichambientlightwill
besufficient.Ifambientlightisattheselectedlevelwhenoccupancyisdetected,lightswillnotbeactivated.The
AmbientLightsControlCircuitincorporatesadeadbandandtimedelaywhichignorebriefchangesinlightlevels,
suchasheadlightsofapassingcar.
Temperature Compensating Circuitry:
Temperature-compensatingcircuitrystabilizessensitivityattemperaturesfrom-40°C(-40°F)to52°C(125°F)
toavoidfalseactivations.
P/N 9850-000411-01
Description
Specifications
General Information
Sensor:
Thesensormountstonormalceiling
tilethroughasingle3/4”hole.Thethreaded
mountingpostmaybecutdownifitistoo
longtotintothejunctionbox.Thesensor
mayalsobesurfacemountedormountedto
astandardNEMA2Sor4Sjunctionbox.
CAUTION: Finger-tighten the nut to avoid
stripping the mounting post. Do not apply
pressure to Fresnel lens.
Backplate:
Thesensorcanbeeasilysnappedontoorpulled
awayfromthebackplatewithoutdisturbingthe
mountinghardware.Topullthesensorawayfrom
thebackplate,placeyourfingersonthedooron
thefrontofthesensorandslideyourfingersup
ontothebackendofthesensor,withyourfingers
restingbelowtheedgeofthebackplate.
Asyoupressagainstthesensor,useyourotherhandtogriptheoppositeendofthesensorandpullitawayfromthe
backplate.
Tosnapthesensorbackontothebackplate,placetheendofthesensorwithoutadooragainstthebackplate
first,hookingtheedgeofthesensoronthetwosmallprongsthatextendfromthebackplate.Presstheotherendof
thesensoragainstthebackplateuntilitsnapsintoplace.
Switchpack:
Designedtobemountedexternallytoanyjunctionbox.Whenmounted,lineconnectionsareinsidetheboxand
theClass2wiringexitsthroughtherearoftheswitchpackhousing.InareaswhereClass2wiringisnotpermitted,
theswitchpackcanbemountedinternallytoanystandardelectricalbox.
Installation
Coverage
OXC-P-1500-R OXC-P-2MH0-R
Location
Surface Mount
2S Box Mounting
4S Box Mounting
Mounting
Post
4” Square
Box with
Mud Ring
1 Gang
Box with
Mud Ring
Top View
30’
10
10
30’
20’
20’
20’
20’
10
30’
30’
10
0’
0’
8’
25’
11
11 25’7’ 7’
3’
3’0’
0’
Side View
Top View
30’
10
10
10
25’
30’
30’
20’
20’
20’
20’
20’
20’
10
30’
30’
30’
10
10
0’
0’
0’
0’
Side View
Note:
ModelOXC-P-1500-RandOXC-P-2MH0-Risdesignedspecificallyforparkingstructures,coldstorageareas,andotherapplications
whereextremetemperaturesexist.UseModelOXC-P-1500-Rinareasuptoamaximumof1,500squarefeetofmajormotionatamounting
heightof8ft.CoverageofModelOXC-P-2MH0-Ris2MHortwicethemountingheightwhenmountedupto25ft.Inawarehouseaisle,asensor
mountedat25ftwillprovidecoveragefor25ftinanydirectionor50lin.ft.
Sensor:
Choosesensorlocationcarefully.Thesensormusthaveaclearviewoftheareatobecontrolled.Theremustbe
anunobstructedline-of-sightfromthesensortoanypartofthecontrolledarea.Formaximumcoverage,positionthe
sensorparalleltothelongestdimensioninthearea.
Switchpack:
Theswitchpackisgenerallymountedabovetheceilingonthe
outsideofthejunctionboxthatcontainsahotline,neutraland
theexistingswitchlegfromwhichthelightingiscontrolled.Ifadditional
switchpacksarerequired,theyaremountedontheoutsideoftheboxes
containingtheappropriateswitchlegs.Ininstallationswherethereareno
existingswitchlegs,theswitchpackmaybemountedontheoutsideofany
conventionalstandardjunctionbox,withorwithoutanextensionring.
J Box
Switchpack
Locknuts
Coverplates
Eaton
Lighting Systems – Controls Products
203 Cooper Circle
Peachtree City, Georgia 30269
www.eaton.com/lightingsystems
Printed in Malaysia
Pleaserefertowww.eaton.com/lightingsystemsundertheLegalsectionforourtermsandconditions.
1. DIPSwitchControlsarelocatedunderthedooronthefaceofthesensor.Beforeopeningthedoor,reviewfactory
settingstodetermineifchangesarenecessary.ThefactorysettingonallswitchesistheOFFposition.Ifyouelect
tochangesomeofthesesettings,openthedoorusingascrewdriver.
2. VerifythatDIPswitch5isintheoffpositiontoensurethesensorisnotinOverrideMode.
3. Standcompletelystillorleavetheroom.Inapproximately15seconds,thelightswillgoout.
4. TesttheareaofcoveragebywatchingtheLEDonthesensor.TheredLEDlightswhenthesensorisdetecting
motion.
5. Usingthechartatright,setthetimedelaytothedesiredtimeforthelightstoremainONaftertheoccupantleaves
thecoveredarea.Inapplicationswheremotionisminorthesensormayneedalongertimedelay.Ifthelightsgo
outwhiletheroomisoccupied,increasethetimeslightlyuntiloptimumtimedelayisreached.
6. Usingthechartbelow,settheambientlightlevel.Selectthefoot-candlelevelatwhichambientlightwillbe
sufcientandarticiallightingwillbeunnecessary.AtthislevelthesensorwillnotswitchlightsONwhenmotionis
detected.Ifyoudonotwantambientlighttoimpactthesensor,selecttheOFFsetting.IflightsgoONwhenthereis
adequateambientlight,decreasethefootcandlesetting.
Manual-ON Override Switch:
TheOXC-P-1500-RandOXC-P-2MH0-RhasanoverrideDIPswitchdesignedtoturntheloadONintheeventof
sensorfailurewhenthesensorcannotbereplacedimmediately.Ifthesensorisusedwithaswitchpack,theswitchpack
mustbeoperativeforthisswitchtowork.Iftheswitchpackisdefective,itmustbereplacedorbypassedtoactivate
theload.
Tooperate,opentheDIPswitchdooronthesensorandmoveDIP5upwardstotheONposition.Allswitchpacks
connectedtothesensorwillnowbeenergized,orthesensorwillplacealowsignalonthebluewiretobesenttoaBAS
systemindicatingoccupancy.Ifmultiplesensorscontrolthesameswitchpack(s),activatingtheoverrideswitchonany
onesensorwillactivatealloftheswitchpacks.
Test Mode:
ThesensorcanbeputintoTestModetotestcoveragearea.ToplacethesensorintoTestMode,togglelightlevelDIP
Switch3or4.ThesensorLEDwillblinkfastwheninTestMode.TestModehasa15secondtime-outtoallowtheuser
toquicklyperformoccupancyvericationandsettingsadjustments.ToplacethesensorbackintoNormalOperating
Mode,toggleaTimeDelayDIPSwitch.Thesensorwillalsoreturntonormaloperationafter10minutes,regardlessof
userinput.
Checkout and Adjustment
DIP Switch Settings
Troubleshooting
Warranties and Limitation of Liability
Wiring
CAUTION: OXC-P is for use with 10-26 VDC only. For other voltages, refer to Greengate Spec Sheets. Do
not wire to control receptacle circuits. Confirm supply voltage before wiring the switchpack. Make sure the
switchpack is the correct model for the voltage being used.
VERIFYthattheconnectedloaddoesnotexceedtheswitchpackratings.Usetwist-onwireconnectorsforall
connections.AllinstallationsshouldbeincompliancewiththeNationalElectricCodeandallstateandlocalcodes.DO
NOTcontrolmorethantenswitchpackswithasinglesensor.
GreengatesensorsareprovidedwithTeflon-insulatedpigtails.Thecomponentsareinterconnectedusing18AWG
Class2wiringperNEC725.UseUL-recognizedTefloninsulatedwireapprovedforplenumareasperNEC725-2(b)
whererequired.
Wirethesensor(s),switchpack(s)andloadasshownintheWiringDiagram.
Controlling Multiple Circuits
CAUTION: In situations where an office is wired for multiple circuits using separate hot leads, it is very
important to connect only one circuit to each switchpack. You may combine the low voltage wiring from
switchpacks connected to different circuits. Consult with the building manager and occupant to determine
which lights should be OFF when the toggle switch is open.
LED will not turn ON
• Verify10-26VDCacrosstheredandblackwiresofthesensor
• Ifthereisnopoweratthesensor,checkfor10-26VDCattheswitchpackoutputand120VAC
or277VACattheswitchpackinput.Verifycorrectprimaryconnections
• IfthevoltageisOKattheswitchpack,recheckallwiringandconnections
• IftheLEDstilldoesn’toperate,sensorisdefectiveandshouldbereplaced
Lights will not turn ON
• SwitchOFFAmbientLightsControlcircuitorincreasethefoot-candlesetting
• Conrmthatnootherswitchesorequipmentareinterruptingorbypassingpowertotheswitchpackorload
• Shorttheblueandredswitchpackcontrolleadstogethertoenergizetherelay
• IfthelightsturnON,thesensorisdefectiveandshouldbereplaced
• IfthelightsdonotturnON,checkwiringontheswitchpackloadsideandcheckswitchpackcontactsfor
continuity.Replacetheswitchpackifnecessary
Lights will not turn OFF
Insmallerrooms,thesensormaybeactivatedbypeoplemovinginthehallwayoutsidetheroom.Relocate
thesensor.
ObservetheLED.Ifitblinksthreetimeseveryveseconds,theenvironmentaltemperatureisoutsidetherange
ofthesensor’stemperaturecompensatingcircuitry.Sensorwillresumenormaloperationwhentemperaturereturns
towithin-40°C(-40°F)to52°C(125°F).
IfthelightswillnotturnOFFafterthetimeperiodsetonthesensor,andtheLEDhasnotlitduringthe
timeperiod:
• Conrmthatnootherswitchesorequipmentareinterruptingorbypassingpowertotheswitchpackorload
• VerifythattheoverrideswitchonallsensorcircuitboardsisintheOFFposition
• Checkallconnectionstotheswitchpack
• Temporarilydisconnectthesensorfromtheswitchpack
• IfthelightsturnOFF,thesensorisdefectiveandshouldbereplaced
• IfthelightsdonotturnOFF,replacetheswitchpack
NOTE:Ifmultiplesensors/switchpacksareinstalled,checkoneatatime.
HOT
RED (15 VDC )
RED (10-26 VDC)
BLUE (CONTROL)
BLACK (COMMON)
PURPLE (NORMALLY CLOSED)
TO ADDITIONAL SENSORS.
MAXIMUM 5 SENSORS PER
SWITCHPACK.
TO ADDITIONAL SWITCHPACK.
MAXIMUM 10 SWITCHPACKS PER
SENSOR.
GRAY (ISOLATED RELAY COMMON)
ORANGE (NORMALLY OPEN)
NEUTRAL
BLUE
LOAD “A
SWITCHPACK
WHITE
**HOT
BLUE
BLACK (COMMON)
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, BOTH
LOADS TURN ON.
2. LOAD TURNS OFF, WHEN SENSOR TIMES
O U T.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
BLUE (CONTROL)
Time Delay Light Level (FC) Override
DIP Switch 1 2 3 4 5
Auto
OFF Disable
5 3 Enable
10 5
20 10
/