Kampmann Venkon, electromechanical control version Installation Plan

  • Hello! I am an AI chatbot trained to assist you with the Kampmann Venkon, electromechanical control version Installation Plan. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Venkon
01/21 EN
Note these points in the following wiring diagrams for Venkon AC with electromechanical control:
Comply with the details on cable types and cabling with due consideration for VDE 0100.
Without *: NYM-J. The requisite number of wires, including protective earth, is stated on the cable. Cross-sections are not stated, as the
cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from power lines.
If other types of cables are used, they must be at least equivalent.
The terminals on the unit are suitable for a maximum wire cross-section of 2.5 mm².
The electrical data need to be respected when rating the in situ mains power supply and fusing.
Venkon
01/21 EN
Cabling, Venkon AC (*A00M), control by room thermostat type 148916
NPE
L
1
2
gn/ge
PE N S1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
6
1
gn/ge
1
2
3
4
5
6
gn/ge
1
2
3
4
5
6
PE NS1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
6
1
12 3 4 5 6 7 8 9 10 11 12 13 14
LV
VmaxVmed
Vminn.c.LLNNC
HGND
15 16 17 18 19
GND DI
GND DIAI n.c. n.c.
1
2
3
4
5
6
7
COMNO 1 2
1
2
1
2
1
2
COM
NO
1
2
1
2
1
2
2*
W6
2*
W7
W5
2*
1
2
3
4
5
6
7
gn/ge
1
2
3
W1
W2
7
W4
8
7
W3
Mains
230 V/50 Hz Venkon AC
electromechanical *00M
Venkon AC
electromechanical *00M
Terminal box
by pothers
Room thermostat
type 148916
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
3 of 5 fan stages
Valve drive(s)
230 V AC Open/Closed
Fan junction box
3 of 5 fan stages
Fan junction box
Valve drive(s)
230 V AC Open/Closed
Jumper
Jumper
Contact
e.g. window
Contact
e.g. heating/cooling Room sensor
- Options -
For more information, see the instructions for the room
thermostat
Venkon
01/21 EN
Cabling, Venkon AC (*A00M), control by room thermostat type 148916, with condensation monitor
NPE
L
1
2
gn/ge
NC COM
LN PE NO
PE N S1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
6
3
4
1
2
gn/ge
1
gn/ge
1
2
3
4
5
6
gn/ge
1
2
gn/ge
1
2
3
4
5
6
7
3
4
NC COML N PE NOPE N S1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
6
3
4
1
2
gn/ge
1
gn/ge
1
2
3
4
5
6
gn/ge
1
2
3
4
gn/ge
1
2
3
4
5
6
7
12 3 4 5 6 7 8 9 10 11 12 13 14
LV
VmaxVmed
Vminn.c.LLNNC
HGND
15 16 17 18 19
GND DI
GND DIAI n.c. n.c.
1
2
3
4
5
6
7
1
2
1
2
1
2
2*
W9
2*
W10
W8
2*
1
2
3
4
5
6
7
gn/ge
1
2
3
W1
W2
7
W3
5
W7
8
W5
7
W6
5
8
W4
COMNO 1 2
1
2
1
2
1
2
COM
NO
Mains
230 V/50 Hz Venkon AC
electromechanical *00M
Venkon AC
electromechanical *00M
Terminal box
by pothers
Room thermostat
type 148916
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
3 of 5 fan stages
Valve drive(s)
230 V AC Open/Closed
Fan junction box
3 of 5 fan stages
Fan junction box
Valve drive(s)
230 V AC Open/Closed
Jumper
Jumper
Contact
e.g. window
Contact
e.g. heating/cooling Room sensor
- Options -
For more information, see the instructions for the room
thermostat
Mains
230 V AC
Condensation alarm Condensation alarm
Mains
230 V AC
Terminal box
by pothers
Junction box
for condensate monitor
Junction box
for condensate monitor
Venkon
01/21 EN
Cabling, Venkon AC (*A00M), control by room thermostat type 148915/148918/148917
NPE
L
1
2
gn/ge
PE N S1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
1
gn/ge
1
2
3
4
5
gn/ge
1
2
3
4
5
PE NS1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
1
1
2
3
4
5
6
gn/ge
1
2
3
W1
W2
6
W4
7
1
2
3
4 5 6 7
8
9 11 12 13
VmaxVmed
Vmin n.c. LL N N
C
H
H/K
N
2
1
3
4
5
6
W3
6
Mains
230 V/50 Hz Venkon AC
electromechanical *00M
Venkon AC
electromechanical *00M
Terminal box
by pothers
Room thermostat,
type 148915
type 148918
type 148917
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
3 of 5 fan stages
Valve drive(s)
230 V AC Open/Closed
Fan junction box
3 of 5 fan stages
Fan junction box
Valve drive(s)
230 V AC Open/Closed
Jumper
Jumper
Room thermostat, heating only type 148915
Room thermostat, cooling only type 148918
Room thermostat with heating/cooling changeover type 148917
Venkon
01/21 EN
Cabling, Venkon AC (*A00M), control by room thermostat type 148915/148918/148917, with
condensation monitor
NPE
L
1
2
gn/ge
NC COM
LN PE NO
PE N S1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
3
4
1
2
gn/ge
1
Brücke
gn/ge
1
2
3
4
5
gn/ge
1
2
gn/ge
1
2
3
4
5
6
3
4
NC COML N PE NOPE N S1 S2 S3 S4 S5 TK TK VK1 2 VH
gn/ge
2
3
4
5
3
4
1
2
gn/ge
1
gn/ge
1
2
3
4
5
gn/ge
1
2
3
4
gn/ge
1
2
3
4
5
6
1
2
3
4
5
6
gn/ge
1
2
3
W1
W2
6
W3
5
W5
6
W6
5
7
W4
W7
7
1
3
4 5 6 7
8
9 11 12 13
VmaxVmed
Vmin n.c. LL N N
H
H/K
N
2
1
3
4
5
6
Mains
230 V/50 Hz Venkon AC
electromechanical *00M
Venkon AC
electromechanical *00M
Terminal box
by pothers
Room thermostat,
type 148918
type 148917
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
3 of 5 fan stages
Valve drive(s)
230 V AC Open/Closed
Fan junction box
3 of 5 fan stages
Fan junction box
Valve drive(s)
230 V AC Open/Closed
Jumper
Jumper
Room thermostat, heating only type 148915
Room thermostat, cooling only type 148918
Terminal box
by pothers
Mains
230 V AC
Junction box
for condensate monitor
Condensation
alarm
Junction box
for condensate monitor
Mains
230 V AC
Condensation
alarm
Venkon
01/21 EN
Note these points in the following wiring diagrams for Venkon EC with electromechanical control:
Comply with the details on cable types and cabling with due consideration for VDE 0100.
Without *: NYM-J. The requisite number of wires, including protective earth, is stated on the cable. Cross-sections are not stated, as the
cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from power lines.
If other types of cables are used, they must be at least equivalent.
The terminals on the unit are suitable for a maximum wire cross-section of 2.5 mm².
Only pulse and/or all-current sensitive residual current protective devices (type A or B) are permitted when using residual current protect-
ive devices. When power is applied to the unit, pulse-like capacitor load currents in the integrated EMC filter can lead to the RCCB being
immediately tripped. We recommend residual current protective switches with a threshold of 300 mA and delayed triggering (super res-
istant, characteristic K).
The electrical data need to be respected when rating the in situ mains power supply and fusing.
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by Climate Controller 30155
gn/ge
1
2
1
1
gn/ge
3
1
1
2
2
2
4
2
3
gn/ge
1
2
3
1
2
1
2
4
1
2
1
2
1
2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
N N N L H K AI GND AO GND UI GND DI GND
3
4
1
2
COMNO 1 2
1
2
1
2
1
2
COM
NO
2*
W7
2*
W8
W4
W6
W3
2*2*5
5
2*
W5
VK UC GND
L N PE 1 2 VH 5 6 VK UC GNDL N PE 1 2 VH 5 6
4
W2
3
W1
N PE
L
1
2
gn/ge
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by Climate Controller 30155, with condensation monitor
gn/ge
1
2
1
1
3
gn/ge
4
1
1
2
2
1
2
gn/ge
3
2
4
4
3
1
2
gn/ge
1
2
3
gn/ge
1
2
1
2
gn/ge
3
4
1
gn/ge
2
3
1
2
1
2
4
3
2
3535
3
W1 W2 W3 W5
W4
2*
W8
VK UC GNDL N PE 1 2 VH 5 6NC COML N PE NO VK UC GNDL N PE 1 2 VH 5 6 NC COML N PE NO
N PE
L
1
2
gn/ge
1
2
4
1
2
1
2
1
2
1 2 3 4 5 6 7 8 9 10 11 12 13 14
N N N L H K AI GND AO GND UI GND DI GND
3
1
2
COMNO 1 2
1
2
1
2
1
2
COM
NO
2* 2*2*2*5
W10
W11
W7
W9
W6
Mains
230 V/50 Hz
Venkon EC
electromechanical (*00M or *01M)
Air conditioning
controller
type 30155
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
Valve drive(s)
230 V AC Open/Closed
Fan junction box
Mains 230 V AC
Junction box
for condensate monitor
Valve drive(s)
230 V AC Open/Closed
Jumper
Contact
e.g. window
Contact
e.g. heating/cooling Room sensor
- Options -
See air conditioning controller instruction for further information
- Optional -
Fault Speed
Fan
Venkon EC
electromechanical (*00M or *01M)
Evaluation
by others
Fan
Condensation alarm
- Optional -
Fault Speed
Evaluation
by others
Junction box
for condensate monitor
Mains 230 V AC
Condensation alarm
230 V AC
Refer to "Electrical
data”
information table!
230 V AC
Refer to "Electrical
data”
information table!
Fan junction box
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by Climate Controller 30256
gn/ge
1
2
1
1
gn/ge
3
1
1
2
2
2
4
2
3
gn/ge
1
2
3
1
2
1
2
4
1
2
1
2
3
4
1
2
1 2
1
2
1
2
COMNO
2*
W7
W4
W6
W3
2*2*5
5
2*
W5
VK UC GND
L N PE 1 2 VH 5 6 VK UC GNDL N PE 1 2 VH 5 6
4
W2
3
W1
N PE
L
1
2
gn/ge
GNDO3N Q1 Q2 I1 GND I2 GND
L
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by Climate Controller 30256, with condensation monitor
gn/ge
1
2
1
1
3
gn/ge
4
1
1
2
2
1
2
gn/ge
3
2
4
4
3
1
2
gn/ge
1
2
3
gn/ge
1
2
1
2
gn/ge
3
4
1
gn/ge
2
3
1
2
1
2
4
3
2
3535
3
W1 W2 W3 W5
W4
2*
W8
VK UC GNDL N PE 1 2 VH 5 6NC COML N PE NO VK UC GNDL N PE 1 2 VH 5 6 NC COML N PE NO
N PE
L
1
2
gn/ge
1
2
4
1
2
1
2
3
1
2
12
1
2
1
2
COMNO
2*2*2*5
GND
O3N Q1 Q2 I1 GND I2 GND
L
W10
W7
W9
W6
Mains
230 V/50 Hz
Venkon EC
electromechanical (*00M or *01M)
Air conditioning
controller
type 30256
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
Valve drive(s)
230 V AC Open/Closed
Fan junction box
Mains 230 V AC
Junction box
for condensate monitor
Valve drive(s)
230 V AC Open/Closed
Jumper
Contact
e.g. heating/cooling Room sensor
- Options -
See air conditioning controller instruction for further information
- Optional -
Fault Speed
Fan
Venkon EC
electromechanical (*00M or *01M)
Evaluation
by others
Fan
Condensation alarm
- Optional -
Fault Speed
Evaluation
by others
Junction box
for condensate monitor
Mains 230 V AC
Condensation alarm
230 V AC
Refer to "Electrical
data”
information table!
230 V AC
Refer to "Electrical
data”
information table!
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by Climate Controller Type 148941/148942
gn/ge
1
2
1
1
gn/ge
3
1
1
2
2
2
4
2
3
gn/ge
1
2
3
1
2
1
2
1
2
1
2
4
COMNO 1 2
1
2
1
2
1
2
COM
NO
3
W7
2*
W8
W4
W6
W3
2*2*5
5
2*
W5
VK UC GND
L N PE 1 2 VH 5 6 VK UC GNDL N PE 1 2 VH 5 6
4
W2
3
W1
N PE
L
1
2
gn/ge
128 4 5 69 10 11 12
GND0-10VN A2 A1 E3
E1 E1 E2 E2
7
L
3
1
2
4
3
2
1
Mains
230 V/50 Hz
Venkon EC
electromechanical (*00M or *01M)
Climate Controller
type 148941
type 148942
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
3 of 5 fan stages
Valve drive(s)
230 V AC Open/Closed
Fan junction box
Mains 230 V AC
Fan junction box
Valve drive(s)
230 V AC Open/Closed
Jumper
Jumper
Contact
e.g. heating/cooling Room sensor
- Options -
See air conditioning controller instruction for further information
- Optional -
Fault Speed
Fan
Venkon EC
electromechanical (*00M or *01M)
Evaluation
by others
Fan
Refer to "Electrical data”
information table!
- Optional -
Fault Speed
Evaluation
by others
Contact
e.g. window
Support bracket by others
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by Climate Controller Type 148941/148942, with
condensation monitor
gn/ge
1
2
1
1
3
gn/ge
4
1
1
2
2
1
2
gn/ge
3
2
4
4
3
1
2
gn/ge
1
2
3
gn/ge
1
2
1
2
gn/ge
3
4
1
gn/ge
2
3
1
2
1
2
4
3
2
3535
3
W1 W2 W3 W5
W4
2*
W8
VK UC GNDL N PE 1 2 VH 5 6NC COML N PE NO VK UC GNDL N PE 1 2 VH 5 6 NC COML N PE NO
N PE
L
1
2
gn/ge
1
2
1
2
1
2
COMNO 1 2
1
2
1
2
1
2
COM
NO
3 2*2*2*5
1
2
8 4 5 69 10 11 12
GND
0-10V
N A2 A1 E3E1 E1 E2 E2
7
L
3
1
2
4
3
2
1
W10
W11
W7
W9
W6
Climate Controller
type 148941
type 148942
Support bracket by others
Mains
230 V/50 Hz
Venkon EC
electromechanical (*00M or *01M)
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
Valve drive(s)
230 V AC Open/Closed
Fan junction box
Mains 230 V AC
Junction box
for condensate monitor
Valve drive(s)
230 V AC Open/Closed
Jumper
Contact
e.g. window
Contact
e.g. heating/cooling Room sensor
- Options -
See air conditioning controller instruction for further information
- Optional -
Fault Speed
Fan
Venkon EC
electromechanical (*00M or *01M)
Evaluation
by others
Fan
Condensation alarm
- Optional -
Fault Speed
Evaluation
by others
Junction box
for condensate monitor
Mains 230 V AC
Condensation alarm
230 V AC
Refer to "Electrical
data”
information table!
230 V AC
Refer to "Electrical
data”
information table!
Venkon
01/21 EN
Cabling, Venkon EC (*00M or 01M), control by DDC/BMS
gn/ge
2
1
1
gn/ge
5
5
6
6
1
2
gn/ge
1
2
2
1
2
gn/ge
3
W1
VK UC GNDL N PE 1 2 VH 5 6 NC COM
LNPE NO
NPE
L
1
2
gn/ge
1
2
24V GND
3
4
AA
0-10V
AA
0-10V
1
2
2
1
1
2
4
3
3
4
DO
24V
DO
24V
AA
0-10V GND
5
6
DI1 DI1
1
2
DI2 DI2
1
2
3
W2
2*
W5
W4
W3
2*
6*
3
W6
6*
W8
gn/ge
2
1
1
gn/ge
5
6
1
2
gn/ge
1
2
2
VKL N PE 1 2 VH NC COML N PE NO
1
2
2
1
4
3
3
W7
DI3 DI3
1
2
DI4 DI4
1
2
2*
W10
W9
2*
UC GND5 6
Supply voltage
valve actuator(s)
Mains
230 V/50 Hz
Venkon EC
electromechanical (*00M or *01M)
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1 Unit no. 2
Valve drive(s)
230 V AC Open/Closed
24 V AC/ 0 - 10 V DC
Note model fitted.
Fan junction box
Mains 230 V AC
- Optional - Junction box
Condensate monitor
Note model
fitted!
- Optional -
Fault Speed
Fan
Venkon EC
electromechanical (*00M or *01M)
Condensation alarm
Model 61: Ri = 100 KΩ
Model 63: Ri = 100 KΩ
Model 66: Ri = 50 KΩ
Model 67: Ri = 50 KΩ
Mains 230 V
AC
Refer to "Electrical
data”
information table!
Mains 230 V AC
Refer to "Electrical data”
information table!
Building automation
system
4-pipe heating
4-pipe cooling
2-pipe heating/cooling
or
Speed
(Note unit’s internal resistance)
Unit 1 motor fault
Contact closed = fault
Unit 1 condensate alarm
Contact open = alarm
(alarm = close cooling valve)
Unit 2 motor fault
Contact closed = fault
Unit 2 condensate alarm
Contact open = alarm
(alarm = close cooling valve)
max. 24 V
max. 24 V
max. 24 V
max. 24 V
Valve drive(s)
230 V AC Open/Closed
24 V AC/ 0 - 10 V DC
Note model fitted.
Fan junction box
Fan
- Optional -
Fault Speed
Model 61: Ri = 100 KΩ
Model 63: Ri = 100 KΩ
Model 66: Ri = 50 KΩ
Model 67: Ri = 50 KΩ
Mains 230 V AC
- Optional - Junction box
Condensate monitor
Condensation alarm
/