Kampmann Venkon XL, KaControl version Installation Plan

  • Hello! I've reviewed the installation instructions document for the Venkon XL KaControl. It details the wiring diagrams, cabling specifications, and connection procedures for units. I'm ready to answer any questions you have about connecting your device, or any other topic covered in the document.
  • What type of cable should be used without an asterisk?
    What type of cable should be used with one asterisk (*)?
    What is the maximum length of BUS cable from KaController to unit 1?
    What is the maximum number of parallel units?
    What is the maximum wire cross-section for mains power supply terminals?
Venkon XL
01/21 EN
Note these points in the following wiring diagrams for Venkon XL with KaControl:
Comply with the details on cable types and cabling with due consideration for VDE 0100.
Without *: NYM-J. The requisite number of wires, including protective earth, is stated on the cable. Cross-sections are not stated, as the
cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from power lines.
With **: Lay UNITRONIC BUS LD 0.22 mm² or similar separately from high-voltage cables.
If other types of cables are used, they must be at least equivalent.
Length of BUS cable from the KaController to unit 1: max. 30 m.
Maximum number of parallel units: 6 units. CANbus cards type 3260301 needed for each unit (see accessories) maximum 30 no. Length
of BUS cable from unit 1 to the last unit max. 30 m. The cable length can be increased to 500 m using CANBUS cards type 3260301 (see
accessories).
The terminals on the unit for the mains power supply are suitable for a maximum wire cross-section of 2.5 mm².
The electrical data need to be respected when rating the in situ mains power supply and fusing.
Venkon XL
01/21 EN
Cabling, Venkon XL, KaControl (*C1), control by KaController
1
2
3
2*
2*
W5
W3
2*
W4
2**
W6
3
W7 2**
W8
3
W9
TX+GND 24VTX- GND
1 2
1
2
NOCOM
1
2
NOCOM
1
2
3
W1
3**
W2
N PEL
1
2
gn/ge
X1
L N PE
gn/ge
1
1
2
2
gn/ ge
Tx V+ DI2GND AI2GND AI1GND GND GNDTx
1
2
1
2
V1 GND V2 GND
X1
L N PE
gn/ge
1
1
2
2
gn/ ge
Tx V+ DI2GND AI2GND AI1GND GND GNDTx
1
2
1
3
2
1
2
1
2
1
2
V1 GND V2 GND
Mains
230 V/50 Hz
KaController
type 321000x
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1
Electrical junction box
PCB
PUR-EC01
- Optional -
Room sensor
type 3250110
Venkon XL
KaControl (*C1)
SmartBoard
circuit board
Venkon XL
KaControl (*C1)
Unit no. 2
Electrical junction box
SmartBoard
circuit board
PCB
PUR-EC01
- Optional -
Contact
e.g. window
- Optional -
Contact
e.g. heating/cooling
To further units
(refer to information
for maximum
number)
- Optional -
Multifunctional inputs
(refer to instructions for possible functions)
Valve drive(s)
24 V DC Open/Close
Valve drive(s)
24 V DC Open/Close
Venkon XL
01/21 EN
Cabling, Venkon XL, KaControl (*C1), control by in situ 0-10 V DC signal
1
2
4*
0-10V GND
3
W1
3
4*
3
3
4
0-10V GND
4*
W2
W3
W4
W5
W6
N PEL
1
2
gn/ge
X1
L N PE
gn/ ge
1
1
2
2
gn/ge
AI2 AI3GND GND
1
1
2
2
3
4
3
4
Ri = 20 KΩ Ri = 20 KΩ
GNDV2GNDV1
X1
L N PE
gn/ ge
1
1
2
2
gn/ge
AI2 AI3GND GND
1
1
2
2
3
4
3
4
Ri = 20 KΩ Ri = 20 KΩ
GNDV2GNDV1
Mains 230 V AC
In situ fusing.
Observe
"Electrical data"
information table.
Mains
230 V/50 Hz
Venkon XL
KaControl (*C1)
Unit no. 1
PCB
PUR-EC01
SmartBoard circuit board
Electrical junction box
Venkon XL
KaControl (*C1)
Unit no. 2
PCB
PUR-EC01
SmartBoard circuit board
Electrical junction box
To further units
(refer to information
for maximum
number)
Building automation
system
* To other units (number depends on maximum current of
the analogue outputs of the BMS)
4-pipe cooling
2-pipe heating/ cooling
Note internal resistance of unit!
4-pipe heating
Note internal resistance of unit!
Note:
0 V - 3 V = valve closed, speed 0
3 V - 10 V = valve open
4 V - 9.5 V = min. speed up to 100%
*
Valve drive(s)
24 V DC Open/Close
Valve drive(s)
24 V DC Open/Close
/