Note these points in the following wiring diagrams for Venkon XL with KaControl:
Comply with the details on cable types and cabling with due consideration for VDE 0100.
Without *: NYM-J. The requisite number of wires, including protective earth, is stated on the cable. Cross-sections are not stated, as the
cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from power lines.
With **: Lay UNITRONIC BUS LD 0.22 mm² or similar separately from high-voltage cables.
If other types of cables are used, they must be at least equivalent.
Length of BUS cable from the KaController to unit 1: max. 30 m.
Maximum number of parallel units: 6 units. CANbus cards type 3260301 needed for each unit (see accessories) maximum 30 no. Length
of BUS cable from unit 1 to the last unit max. 30 m. The cable length can be increased to 500 m using CANBUS cards type 3260301 (see
accessories).
The terminals on the unit for the mains power supply are suitable for a maximum wire cross-section of 2.5 mm².
The electrical data need to be respected when rating the in situ mains power supply and fusing.
Venkon XL
01/21 EN
Cabling, Venkon XL, KaControl (*C1), control by KaController
1
2
3
2*
2*
W5
W3
2*
W4
2**
W6
3
W7 2**
W8
3
W9
TX+GND 24VTX- GND
1 2
1
2
NOCOM
1
2
NOCOM
1
2
3
W1
3**
W2
N PEL
1
2
gn/ge
X1
L N PE
gn/ge
1
1
2
2
gn/ ge
Tx V+ DI2GND AI2GND AI1GND GND GNDTx
1
2
1
2
V1 GND V2 GND
X1
L N PE
gn/ge
1
1
2
2
gn/ ge
Tx V+ DI2GND AI2GND AI1GND GND GNDTx
1
2
1
3
2
1
2
1
2
1
2
V1 GND V2 GND
Mains
230 V/50 Hz
KaController
type 321000x
In situ fusing.
Observe
"Electrical data"
information table.
Mains 230 V AC
Unit no. 1
Electrical junction box
PCB
PUR-EC01
- Optional -
Room sensor
type 3250110
Venkon XL
KaControl (*C1)
SmartBoard
circuit board
Venkon XL
KaControl (*C1)
Unit no. 2
Electrical junction box
SmartBoard
circuit board
PCB
PUR-EC01
- Optional -
Contact
e.g. window
- Optional -
Contact
e.g. heating/cooling
To further units
(refer to information
for maximum
number)
- Optional -
Multifunctional inputs
(refer to instructions for possible functions)
Valve drive(s)
24 V DC Open/Close
Valve drive(s)
24 V DC Open/Close
Venkon XL
01/21 EN
Cabling, Venkon XL, KaControl (*C1), control by in situ 0-10 V DC signal
1
2
4*
0-10V GND
3
W1
3
4*
3
3
4
0-10V GND
4*
W2
W3
W4
W5
W6
N PEL
1
2
gn/ge
X1
L N PE
gn/ ge
1
1
2
2
gn/ge
AI2 AI3GND GND
1
1
2
2
3
4
3
4
Ri = 20 KΩ Ri = 20 KΩ
GNDV2GNDV1
X1
L N PE
gn/ ge
1
1
2
2
gn/ge
AI2 AI3GND GND
1
1
2
2
3
4
3
4
Ri = 20 KΩ Ri = 20 KΩ
GNDV2GNDV1
Mains 230 V AC
In situ fusing.
Observe
"Electrical data"
information table.
Mains
230 V/50 Hz
Venkon XL
KaControl (*C1)
Unit no. 1
PCB
PUR-EC01
SmartBoard circuit board
Electrical junction box
Venkon XL
KaControl (*C1)
Unit no. 2
PCB
PUR-EC01
SmartBoard circuit board
Electrical junction box
To further units
(refer to information
for maximum
number)
Building automation
system
* To other units (number depends on maximum current of
the analogue outputs of the BMS)
4-pipe cooling
2-pipe heating/ cooling
Note internal resistance of unit!
4-pipe heating
Note internal resistance of unit!
Note:
0 V - 3 V = valve closed, speed 0
3 V - 10 V = valve open
4 V - 9.5 V = min. speed up to 100%
*
Valve drive(s)
24 V DC Open/Close
Valve drive(s)
24 V DC Open/Close
  • Page 1 1
  • Page 2 2
  • Page 3 3

Kampmann Venkon XL, KaControl version Installation Plan

Type
Installation Plan

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI