GreenBrook RCDL Operating instructions

Type
Operating instructions

GreenBrook RCDL is a two pole in-line portable RCD, designed for use in commercial and industrial environments where rough handling is expected. It protects against live and neutral faults to earth, but not against electric shock due to contact with both conductors, short circuits between live and neutral, or a fault in the wiring supplying this device. The device has an IP55 rating, making it resistant to dust and water jets. It has a maximum load of 3kW and a maximum operating current of 13 Amps (4 amps inductive load). The rated tripping current is 30 mA.

GreenBrook RCDL is a two pole in-line portable RCD, designed for use in commercial and industrial environments where rough handling is expected. It protects against live and neutral faults to earth, but not against electric shock due to contact with both conductors, short circuits between live and neutral, or a fault in the wiring supplying this device. The device has an IP55 rating, making it resistant to dust and water jets. It has a maximum load of 3kW and a maximum operating current of 13 Amps (4 amps inductive load). The rated tripping current is 30 mA.

Installation/Operating Instructions For
SafetySure 13 Amp 230V/250V
In-line Portable RCD
Part No: RCDL
SafetySure RCDL is a two pole in-line portable RCD, designed for
use in commercial and industrial environments where rough
handling is expected.
IMPORTANT FOR YOUR PROTECTION
This unit should be installed by a competent person in
accordance with the current IET Wiring Regulations.
If in doubt consult a qualified electrician.
Electricity is dangerous and an RCD must not be used as a
substitute for normal precautionary measures.
Always unplug from mains supply before any inspection or
repair to equipment.
Do not allow children to tamper with electrical devices.
Should your In-line RCD repeatedly trip with an appliance
connected, or fail to trip when tested, seek advice
immediately from a competent electrician or return to place
of purchase.
This device will protect against live and neutral faults to earth.
It will not protect against electric shock due to contact with
both conductors, short circuits between live and neutral, or a
fault in the wiring supplying this device.
1. Make sure the LINE is the input end, and the LOAD is at the
output end. Prepare cable as per wiring diagram.
2. The cable goes through the product from the OUTSIDE
STOPPER to INSIDE STOPPER, TIGHTENING RUBBER RING
and end hole of UPPER COVER in sequence.
3. Clamp conductor ends to terminals according to wiring
diagram.
4. Clamp cable with cord grip. tighten the two screws.
5. Tighten outside stopper to secure cable.
6. Locate the BOTTOM COVER with the four screws, making
sure all screws are securely tightened.
WIRING
Bottom Cover
Cord Grip
Outside
Stopper
Inside
Stopper
Tightening
Rubber Ring
Upper Cover
LINE/LOAD
Wire
Terminal
RCDL Ins Mar 22_RCDL 22/06/2022 14:42 Page 1
INSTRUCTIONS
Input
Test
Reset
Indicator Output
TECHNICAL INFORMATION
Rated voltage: 230V/250V AC~50/60Hz
No of Poles: 2
Maximum Operating 13 Amps
Current: (4 amps inductive load)
IP Rating: IP55
Maximum Load: 3kW
Rated Tripping Current: 30 mA
Max Cable Dia: 7 - 10mm
Conforms to: BS 7071, EN 61543
WIRING LAYOUT
Test Before use:
1. Plug line input into socket outlet.
2. Press ‘RESET’ button indicator should be
‘ON’ (Red).
3. Press ‘TEST’ button indicator should be
‘OFF’(Black).
4. Press ‘RESET’ button for use, DO NOT USE if
‘TEST’ fails.
Blue to (N) Neutral wire terminal
Green/Yellow to Earth Terminal
Brown to (L) Live wire terminal
Replace the cord grip and secure with screws.
NOTE: The cable must extend past the cord grip by 3mm.
8-10mm
Length of bare
conductor
Cord Grip
30 1mm
Blue to (N)
Neutral terminal
30 1mm
Brown to (L)
Neutral terminal
38 1mm
Green/Yellow to
Earth terminal
Issue No: 706840
WEST ROAD . HARLOW
ESSEX . CM20 2BG . UK
info@greenbrook.co.uk
www.greenbrook.co.uk
GUARANTEE
Your GreenBrook In-line RCD
is guaranteed for 1 year from the
date of purchase.
This is in addition to your statutory rights.
Note:
The SafetySure In-line Portable RCD has been designed
for storage and use between -5°C and +40°C at an
altitude no greater than 2000m above sea level. Care
must be taken not to subject your SafetySure to abnormal
pollution by smoke chemical or flammable fumes, salt
laden spray, prolonged periods of high humidity,
immersion, repeated dropping, or any other abnormal
conditions.
PLEASE KEEP THESE INSTRUCTIONS
SAFE FOR FUTURE REFERENCE
Type A RCD
NOTE: Product & Packaging Disposal
When disposing of this item and its packaging please follow
local regulations and use an appropriate waste disposal
centre.
See GreenBrook website for further details.
RCDL Ins Mar 22_RCDL 22/06/2022 14:42 Page 2
  • Page 1 1
  • Page 2 2

GreenBrook RCDL Operating instructions

Type
Operating instructions

GreenBrook RCDL is a two pole in-line portable RCD, designed for use in commercial and industrial environments where rough handling is expected. It protects against live and neutral faults to earth, but not against electric shock due to contact with both conductors, short circuits between live and neutral, or a fault in the wiring supplying this device. The device has an IP55 rating, making it resistant to dust and water jets. It has a maximum load of 3kW and a maximum operating current of 13 Amps (4 amps inductive load). The rated tripping current is 30 mA.