Elsner KNX S4-B12 24 V User manual

Type
User manual
Item number 70533
EN
KNX S4-B12 24 V
Actuator for 12/24 V Drives
Installation and Adjustment
1 Content
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Actuator KNX S4-B12 24 V • from software version 4.00, ETS programme version 4.0
Status: 28.08.2023 • Technical changes and errors excepted.
1. Description ........................................................................................... 5
1.0.1. Scope of delivery .......................................................................................... 5
1.1. Technical data ........................................................................................................... 6
2. Installation and Commissioning ........................................................... 6
2.1. Safety notice for automatic functions .................................................................... 7
2.2. Connection ................................................................................................................ 8
2.2.1. Device design ................................................................................................ 9
2.2.2. Display of operating status by the power supply LED ............................. 10
2.2.3. Status display by the channel LEDs .......................................................... 10
2.3. Notes on mounting and commissioning .............................................................. 10
2.4. Connection examples ............................................................................................ 11
2.5. Addressing of the device at the bus ..................................................................... 12
3. Disposal ............................................................................................. 12
4. Transfer protocol ............................................................................... 13
4.1. List of all communication objects ......................................................................... 13
5. Parameter setting .............................................................................. 39
5.1. General settings ..................................................................................................... 39
Parameter „Application when programming“ ......................................... 39
5.1.1. Local operation ........................................................................................... 39
5.2. Inputs ....................................................................................................................... 40
Input as bus button ..................................................................................... 41
5.3. Outputs .................................................................................................................... 44
5.3.1. Channel settings – drives ........................................................................... 45
5.3.1.1. Control (drives) ............................................................................ 47
Block – blocking objects ............................................................................. 51
Block – wind blocking ................................................................................. 52
Block – rain blocking ................................................................................... 53
Movement limits ......................................................................................... 54
5.3.1.2. Manual ........................................................................................... 55
5.3.1.3. Automation - external .................................................................. 55
5.3.1.4. Automatic - internal for shading (drives) .................................... 56
5.3.1.5. Automatic for windows (drives) .................................................. 60
5.3.1.6. Scenes (drives) .............................................................................. 64
5.3.1.7. Button inputs (drives) ................................................................... 65
Input as bus button ..................................................................................... 65
Input as actuator button ............................................................................. 65
Input as zero position sensor ..................................................................... 66
5.3.2. Output channel with drive .......................................................................... 66
Control modi for drive control ................................................................... 66
5.3.3. Connection option for zero position sensors ........................................... 68
5.3.4. Output channel with switch function ........................................................ 70
Correlation connection – time switch – block ........................................... 70
5.3.5. Channel settings – switch functions .......................................................... 71
2 Content
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Actuator KNX S4-B12 24 V • from software version 4.00, ETS programme version 4.0
Status: 28.08.2023 • Technical changes and errors excepted.
5.3.5.1. Connection (switch functions) ..................................................... 71
5.3.5.2. On/Off switch delays, time switching (switch functions) .......... 72
5.3.5.3. Blocking function (switch functions) ........................................... 73
5.3.5.4. Button input (switch functions) ................................................... 73
Input as bus button ..................................................................................... 73
Input as actuator button ............................................................................. 73
3 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.
4 Clarification of signs
5 Description
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
1. Description
The Actuator KNX S4-B12 24V with integrated facade control has 4 outputs for
direct current drives (12...24V DC, Up/Down), 4 button pairs and control LEDs. The
outputs are compatible with shutter, awning, blind or window drives. Connected drives
can be operated directly at KNX S4-B12 24V and via a hand switch.
The automation can be specified externally or internally. Internally, there are
numerous options available for blocking, locking (e.g. master-slave) and priority
definition (e.g. manual-automatic). Scenes can be saved and called up via the bus
(scene control with 16 scenes per drive).
Twelve binary inputs can be used either for direct operation (e.g. hand switches) or as
bus switches (or also for e.g. alarm notifications). The desired behaviour can be
defined precisely through selection of the response times in Standard, Comfort or
Deadman mode.
Functions:
4 outputs with polarity changer for motors 12...24 V DC (shading,
windows)
20...32 V DC internal supply voltage for inputs and for outputs
Keypad with 4 button pairs and status LEDs
12 binary inputs for use as hand switches or as bus switches with variable
voltage (12...24 V DC)
Automatic runtime measurement of the drives for positioning (including
fault notification object)
Position feedback (movement position, also slat position for blinds)
Position storage (movement position) via 1-bit object (storage and call-up
e.g. via buttons)
•Control via internal or external automation
•Integrated shade control for each drive output (with slat tracking
according to sun position for blinds)
Scene control for movement position with 16 scenes per drive (also slat
position for blinds)
Mutual locking of two drives using zero position sensors prevents collisions
e.g. of shade and window (master–slave)
Blocking objects and alarm notifications have different priorities, so safety
functions always take precedence (e.g. wind block)
Manual or automatic priority setting via time or communication object
Brief time limit (movement command blocked) and 2 movement limits
Configuration is made using the KNX software as of ETS 5. The product file can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de.
1.0.1. Scope of delivery
•Actuator
6 Installation and Commissioning
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
1.1. Technical data
The product conforms with the provisions of EU guidelines.
2. Installation and Commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
Housing Plastic
Colour White
Assembly in distribution boxes or small housings according to
DIN VDE 0603 on 35 mm mounting rails according to
DIN EN 60715
Degree of protection IP20 according to DIN EN 60 529
Dimensions approx. 107 x 88 x 60 (W × H × D, mm)
6 dividing units
Weight approx. 300 g
Ambient temperature Operation -5…+45 °C, storage -25…+70 °C
Ambient humidity max. 95 % RH, avoid condensation
Operating voltage 20...32 V DC.
A suitable power pack can be
purchased from Elsner Elektronik.
Power consumption typically 5 mA, max. approx. 80 mA
Power on bus: 10 mA
Outputs 4 x Output with polarity changer
for motors 12 V DC/24 V DC (+/-), max. 3A
separate power supply for each channel
(internal or external voltage)
Maximum load Each terminal contact may be loaded with a maximum
of 10 A.
Minimum current for runt-
ime measurement
DC 150 mA
Inputs 12 x binary inputs, low voltage (12...24 V DC)
Max. cable length
Binary inputs
100 m
Data output KNX +/- Bus connector terminal
Group addresses max. 1024
Assignments max. 1024
Communication objects 585
7 Installation and Commissioning
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
CAUTION!
Live voltage!
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating
instructions. Improper use, modifications to the device or failure to observe the
operating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition and
after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.1. Safety notice for automatic functions
WARNING!
Risk of injury from automatically moving components!
Parts of the system can be started by the automatic controls
and be a danger to persons.
No persons may remain in the travelling range of parts
driven by an electric motor.
Adhere to the relevant building regulations.
Ensure that the return path/access to the building is not blocked
if spending time outside the building (danger of being locked out).
Correctly decommission the system for maintenance and
cleaning work.
If there is a power outage, the system does not work. Therefore, shadings should be
moved to a save position if there are anticipated weather conditions, for example, if
this has not already been done by the automatic function (product protection).
If the power supply is removed, the connected drive switches off. When the power is
restored, the consumer remains switched off until a new movement command is
received by the actuator.
8 Installation and Commissioning
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
2.2. Connection
Follow the guidelines and standards for SELV electric circuits
while installing and cable laying of the KNX connection and the
inputs and outputs!
Mixed installation of SELV and non-SELV electrical circuits on the inputs and
outputs of the device is not permitted.
9 Installation and Commissioning
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
2.2.1. Device design
The device is designed for series installation on mounting rails and occupies 6U.
1) Binary inputs 1-12 (see also connection example )
2) Programming LED and programming buttons (PRG)
3) Bus terminal slot (KNX +/-)
4) LED "Power", mode display. See “Display of operating status by the power supply
LED” on page 10.
5) Up/Down button pairs and LEDs channel A-D
6) 24 V DC supply voltage input
7) Output A "Up"-"Down", max. 3 A
8) Output B "Up"-"Down", max. 3 A
9) Output C "Up"-"Down", max. 3 A
10) Output D "Up"-"Down", max. 3 A
All +24 V terminals and the top terminal strip are bridged internally.
All +24 V terminals and the bottom terminal strip are bridged internally.
3
4
5
7 9 10
12
6
8
10 Installation and Commissioning
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
2.2.2. Display of operating status by the power supply LED
2.2.3. Status display by the channel LEDs
2.3. Notes on mounting and commissioning
Device must not be exposed to water (rain). This could result in the electronics being
damaged. A relative air humidity of 95% must not be exceeded. Avoid condensation.
Behaviour Colour
On Green Normal operation.
Bus connection/bus voltage available.
Flashes Green Normal operation.
No bus connection/bus voltage available.
On Orange Device starts up or is being programmed via
the ETS. No automatic functions are executed.
Flashes Green (on),
Orange (flashing)
Programming mode active.
Behaviour LED
To top Drive in top end position/device on.
To bottom Drive in bottom end position/drive on.
Flashes slowly top Drive moves up.
Flashes slowly bottom Drive moves down.
Flashes
quickly
top Drive in top end position, barrier active.
Flashes
quickly
bottom Drive in bottom position, barrier active.
Flashes
quickly
both
simultaneously
Drive in intermediate position, barrier active.
Extend both Drive in intermediate position.
Flashes both alternately Automatic runtime determination error.
If the drive can be moved, drive it into the end
position by hand (drive in/drive out
completely or open/close) in order to restart
the runtime determination.
If the drive cannot be moved, check the
connections.
"Runlight"
above all LEDs
all channels Incorrect application version was loaded. Use
the version compatible with the device!
11 Installation and Commissioning
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
After the operating voltage has been applied, the device will enter an initialisation
phase lasting a few seconds. During this phase no information can be received or sent
via the bus.
For KNX devices with safety functions (e.g. wind or rain blocks), periodical monitoring
of the safety objects must be set up. The optimal ratio is 1:3 (example: if the weather
station sends a value every 5 minutes, the actuator must be configured for a
monitoring period of 15 minutes).
2.4. Connection examples
Use of binary input No. 1
with external auxiliary voltage
(12...24 V DC)
Use of binary input No. 12
with internal auxiliary voltage
(20...32 V DC)
Use of drive output A
with external auxiliary voltage
(12...24 V DC)
Use of drive output D with internal auxiliary
voltage (20...32 V DC). The +20...32 V DC
internal voltage must be bridged to the
+ terminal of output D for this.
supply unit
(12...24 V DC)
supply unit
(12...24 V DC)
Operating voltage
20...32 V DC
Each terminal con-
tact may be loaded
with a maximum of
10 A.
12 Disposal
Actuator KNX S4-B12 24V • Status: 28.08.2023 • from software version 4.00, ETS programme version 4.0 •
Technical changes and errors reserved.
2.5. Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another
address into the ETS by overwriting the 15.15.255 address or by teaching via the
programming button.
3. Disposal
After use, the device must be disposed of in accordance with the legal regulations. Do
not dispose of it with the household waste!
13 Transfer protocol
Actuator KNX S4-B12 24 V • Status: 28.08.2023 • Technical changes and errors excepted.
4. Transfer protocol
4.1. List of all communication objects
Abbreviations:
R Read
W Write
C Communication
T Transfer
No. Name Function Flags Data Point Type Size
1 Software version Readable R C [217.1]
DPT_Version
2 Bytes
50 Input 1 long term Input /
output
RWCT [1.8]
DPT_UpDown
1 Bit
51 Input 1 short term Output R CT [1.8]
DPT_UpDown
1 Bit
52 Input 1 switching Input /
output
RWCT [1.1]
DPT_Switch
1 Bit
53 Input 1 dim relative Input /
output
RWCT [3.7]
DPT_Control_Dimmi
ng
4 Bit
54 Input 1 encoder 8 bit Output R CT [9.1]
DPT_Value_Temp
1 Byte
55 Input 1 encoder
temperature
Output R CT [9.4]
DPT_Value_Lux
2 Bytes
56 Input 1 encoder brightness Output R CT [18.1]
DPT_SceneControl
2 Bytes
57 Input 1 scene Output R CT [1.1]
DPT_Switch
1 Byte
58 Input 1 blocking object Input WC [1.8]
DPT_UpDown
1 Bit
60-
68
Input 2 (see input 1)
70-
78
Input 3 (see input 1)
80-
88
Input 4 (see input 1)
100 Channel A status automatic
or
manual
Output R CT [1]
1.xxx
1 Bit
101 Channel A manual long
term
Input RWC [1.8]
DPT_UpDown
1 Bit
102 Channel A manual short
term
Input RWC [1.8]
DPT_UpDown
1 Bit
14 Transfer protocol
Actuator KNX S4-B12 24 V • Status: 28.08.2023 • Technical changes and errors excepted.
103 Channel A manual
movement position
Input RWC [5.1]
DPT_Scaling
1 Byte
104 Channel A manual slat
position
Input RWC [5.1]
DPT_Scaling
1 Byte
105 Channel A automatic short
term
Input RWC [1.8]
DPT_UpDown
1 Bit
106 Channel A automatic long
term
Input RWC [1.8]
DPT_UpDown
1 Bit
107 Channel A automatic
movement position
Input RWC [5.1]
DPT_Scaling
1 Byte
108 Channel A automatic slat
position
Input RWC [5.1]
DPT_Scaling
1 Byte
109 Channel A switch from
manual to automatic
Input RWC [1]
1.xxx
1 Bit
110 Channel A automatic
blocking object
Input RWCT [1.1]
DPT_Switch
1 Bit
111 Channel A current
movement position
Output R CT [5.1]
DPT_Scaling
1 Byte
112 Channel A current slat
position
Output R CT [5.1]
DPT_Scaling
1 Byte
113 Channel A status object Output R CT [1]
1.xxx
1 Bit
114 Channel A - Approach
position memory for
manual
Input RWC [1.1]
DPT_Switch
1 Bit
115 Channel A - Learn object
position memory for
manual 0
Input RWC [1.1]
DPT_Switch
1 Bit
116 Channel A - Learn object
position memory for
manual 1
Input RWC [1.1]
DPT_Switch
1 Bit
119 Channel A - Approach
position memory for
automatic
Input RWC [1.1]
DPT_Switch
1 Bit
120 Channel A - Learn object
position memory for
automatic 0
Input RWC [1.1]
DPT_Switch
1 Bit
121 Channel A - Learn object
position memory for
automatic 1
Input RWC [1.1]
DPT_Switch
1 Bit
124 Channel A call saving
scenes
Input WC [1.1]
DPT_Switch
1 Bit
125 Channel A outdoor
temperature
Blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
No. Name Function Flags Data Point Type Size
15 Transfer protocol
Actuator KNX S4-B12 24 V • Status: 28.08.2023 • Technical changes and errors excepted.
126 Channel A outdoor
temperature blocking
measurement value
Input WC [1.1]
DPT_Switch
1 Bit
127 Channel A outdoor
temperature blocking status
Output R CT [1.1]
DPT_Switch
1 Bit
128 Channel A twilight object Input RWC [1.1]
DPT_Switch
1 Bit
129 Channel A twilight
measurement value
Input RWC [1.1]
DPT_Switch
1 Bit
130 Channel A twilight status Output R CT [18.1]
DPT_SceneControl
1 Byte
131 Channel A time control Input RWC [1.1]
DPT_Switch
1 Bit
132 Channel A inside
temperature release object
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
133 Channel A inside
temperature release
measurement value
Input RWC [1.1]
DPT_Switch
1 Bit
134 Channel A inside
temperature release target
value
Input RWC [1.1]
DPT_Switch
1 Bit
135 Channel A inside
temperature release status
Output R CT [9.4]
DPT_Value_Lux
2 Bytes
136 Channel A shading object Input RWC [1.1]
DPT_Switch
1 Bit
137 Channel A shading
brightness Measurement
value 1
Input RWC [1.1]
DPT_Switch
1 Bit
138 Channel A shading
brightness Measurement
value 2
Input RWC [1.1]
DPT_Switch
1 Bit
139 Channel A shading
brightness
Measurement value 3
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
140 Channel A shading
threshold value
Input /
output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
141 Channel A shading
threshold value 1 = + | 0 = -
Input RWC [1.1]
DPT_Switch
1 Bit
142 Channel A shading
threshold value +
Input RWC [1.1]
DPT_Switch
1 Bit
143 Channel A shading
threshold value -
Input RWC [9.4]
DPT_Value_Lux
2 Bytes
144 Channel A shading status Output R CT [9.4]
DPT_Value_Lux
2 Bytes
No. Name Function Flags Data Point Type Size
16 Transfer protocol
Actuator KNX S4-B12 24 V • Status: 28.08.2023 • Technical changes and errors excepted.
145 Channel A shading position
Teaching object
Input RWC [9.4]
DPT_Value_Lux
2 Bytes
146 Channel A azimuth Input RWC [9.4]
DPT_Value_Lux
2 Bytes
147 Channel A elevation Input RWC [1]
1.xxx
1 Bit
148 Channel A cold air supply
blocking object
Input RWC [1]
1.xxx
1 Bit
149 Channel A cold air supply
outside temperature
measurement value
Input RWC [1]
1.xxx
1 Bit
150 Channel A cold supply air
blocking status
Output R CT [1.1]
DPT_Switch
1 Bit
151 Channel A forced
ventilation
Input RWC [1]
1.xxx
1 Bit
152 Channel A warm air supply
blocking object
Input RWC [9]
9.xxx
2 Bytes
153 Channel A warm air supply
inside temperature
measurement value
Input RWC [9]
9.xxx
2 Bytes
154 Channel A warm air supply
outside temperature
measurement value
Input RWC [1.1]
DPT_Switch
1 Bit
155 Channel A warm air supply
blocking target value
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
156 Channel A warm air supply
blocking status
Output R CT [1.1]
DPT_Switch
1 Bit
157 Channel A inside
temperature opening object
Input RWC [1.1]
DPT_Switch
1 Bit
158 Channel A inside
temperature opening
measurement value
Input RWC [1.1]
DPT_Switch
1 Bit
159 Channel A inside
temperature opening target
value
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
160 Channel A inside
temperature opening
threshold value
Input /
output
RWCT [9.1]
DPT_Value_Temp
2 Bytes
161 Channel A inside
temperature opening
threshold value 1 = +
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
162 Channel A inside
temperature opening
threshold value
Input RWC [1.1]
DPT_Switch
1 Bit
No. Name Function Flags Data Point Type Size
17 Transfer protocol
Actuator KNX S4-B12 24 V • Status: 28.08.2023 • Technical changes and errors excepted.
163 Channel A inside
temperature opening
threshold value -
Input RWC [1.1]
DPT_Switch
1 Bit
164 Channel A inside
temperature opening status
Output R CT [9.1]
DPT_Value_Temp
2 Bytes
165 Channel A inside humidity
opening object
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
166 Channel A inside humidity
opening Measurement
value
Input RWC [9.1]
DPT_Value_Temp
2 Bytes
167 Channel A inside humidity
opening status
Output R CT [1]
1.xxx
1 Bit
170 Channel A zero position
reached
Input RWC [1]
1.xxx
1 Bit
171 Channel A zero position
sensor malfunctioning
Output R CT [1]
1.xxx
1 Bit
172 Channel A master zero
position status
Output R CT [1.1]
DPT_Switch
1 Bit
173 Channel A master zero
position command
Output R CT [1.1]
DPT_Switch
1 Bit
174 Channel A slave zero
position status
Input RWC [9.7]
DPT_Value_humidity
2 Bytes
175 Channel A master zero
position status
Input RWC [1.1]
DPT_Switch
1 Bit
176 Channel A master zero
position command
Input RWC [1.1]
DPT_Switch
1 Bit
177 Channel A slave zero
position status
Output R CT [1.1]
DPT_Switch
1 Bit
178 Channel A drive moving Output R CT [1.1]
DPT_Switch
1 Bit
179 Channel A malfunction
object
Output R CT [1.1]
DPT_Switch
1 Bit
180 Channel A block 1 blocking
object
Input RWC [1.1]
DPT_Switch
1 Bit
181 Channel A block 1 wind
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
182 Channel A block 1 wind
blocking
Measurement value
Input RWC [1.1]
DPT_Switch
1 Bit
183 Channel A block 1 wind
blocking status
Output R CT [1.1]
DPT_Switch
1 Bit
184 Channel A block 1 rain
blocking object
Input RWC [1]
1.xxx
1 Bit
185 Channel A block 2 blocking
object
Input RWC [1]
1.xxx
1 Bit
No. Name Function Flags Data Point Type Size
18 Transfer protocol
Actuator KNX S4-B12 24 V • Status: 28.08.2023 • Technical changes and errors excepted.
186 Channel A block 2 wind
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
187 Channel A block 2 wind
blocking Measurement
value
Input RWC [1.1]
DPT_Switch
1 Bit
188 Channel A block 2 wind
blocking status
Output R CT [9.5]
DPT_Value_Wsp
2 Bytes
189 Channel A block 2 rain
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
190 Channel A block 3 blocking
object
Input RWC [1.1]
DPT_Switch
1 Bit
191 Channel A block 3 wind
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
192 Channel A block 3 wind
blocking Measurement
value
Input RWC [1.1]
DPT_Switch
1 Bit
193 Channel A block 3 wind
blocking status
Output R CT [9.5]
DPT_Value_Wsp
2 Bytes
194 Channel A block 3 rain
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
195 Channel A block 4 blocking
object
Input RWC [1.1]
DPT_Switch
1 Bit
196 Channel A block 4 wind
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
197 Channel A block 4 wind
blocking
Measurement value
Input RWC [1.1]
DPT_Switch
1 Bit
198 Channel A block 4 wind
blocking status
Output R CT [9.5]
DPT_Value_Wsp
2 Bytes
199 Channel A block 4 rain
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
200 Channel A block 5 blocking
object
Input RWC [1.1]
DPT_Switch
1 Bit
201 Channel A block 5 wind
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
202 Channel A block 5 wind
blocking Measurement
value
Input RWC [1.1]
DPT_Switch
1 Bit
203 Channel A block 5 wind
blocking status
Output R CT [9.5]
DPT_Value_Wsp
2 Bytes
204 Channel A block 5 rain
blocking object
Input RWC [1.1]
DPT_Switch
1 Bit
205 Channel A - Movement
limitation 1 - Blocking
object
Input RWC [1.1]
DPT_Switch
1 Bit
No. Name Function Flags Data Point Type Size
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78

Elsner KNX S4-B12 24 V User manual