Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1andBSEN55015.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.a10ampcircuitbreakerandvoltagesurgeprotection.
Pleaseensurethatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Ceiling Surface PIR absence switch
CESFA PIR
DANLERS ceiling surface passive infra-red absence switch (CESFA
PIR)canbeceilingmountedonasquarepattressbox(DANLERScode:
PABO).TheCESFAPIRincorporatesapassiveinfra-redquadsensor
todetectmovementofawarmbodywithinitsdetectionzone(diagram
A)andaphotocelltomonitortheambientlightlevel.
Whenenteringtheroom,iftheambientlightisdarkenough,thelights
canbeactivatedbypressingamomentarylightswitchforlessthan2
seconds. The ambient threshold can be set by the user to between
approximately 30 lux and innite lux (photocell inactive) via the LUX
adjuster(diagramB). Ifnomoremovementisdetectedwithinapre-
selectedtime,thentheCESFAPIRwillswitchtheloadoff.Thistimelag
canbesetviatheTIMEadjusterto10seconds,20s,40s,1minute15
seconds,2m30s,5m,10m,20mor40minutes(diagramB).
Pressingandholdingthemomentaryswitch(for2secondsormore)
(whileCESFAisinitsONstate)willoveridethecontrolenablingtheload
tobeswitchedOFF.Thisisusefulwhenadarkenedroomisrequired
oriftheuserdoesnotwishthetimelagperiodtoelapse.
Allow a minimum of 1 second to elapse after the lights have gone off before
repressing the momentary switch (allowing CESFA PIR to reset).
Loading
Theswitchshouldonlybeconnectedtoa230V50HzACsupply.
ThesePIRswitchescanswitchupto:
6amps(1500W)ofresistiveloads.
6amps(1500W)ofuorescentloads.
3amps(750W)ofelectronicandwirewoundtransformerloads.
2amps(500W)ofCFL,2Dlamps,LEDDriversandLEDlamps
andttings.
1amp(250W)offans
Minimumload2Wresistive,suitableformostenergysavinglamps,
LEDsandemergencyttings.
Forlargerloads,theCESFAPIRcanbeusedtoswitchacontactor.
22/07/15 INS954 CESFA PIR
Troubleshooting
The load will not switch on when the momentary switch is operated:
• TheLUXadjusterissettoolowandisinhibitingtheswitch.
The Absence detector switches off when the room is occupied:
• Theoccupationisoutsideofthedetectionzone(seediagramA),
movementsaretoosmallortooinfrequent.IncreasetheTIMEadjuster.