Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1andBSEN55015.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.a10ampcircuitbreakerandvoltagesurgeprotection.
Pleaseensurethatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Ceiling surface PIR absence switch/dim control
CESFAPIRSD
DANLERS ceiling surface passive infra-red absence switch/dim
controls(CESFAPIRSD)canbeceilingmountedonasquarepattress
box(DANLERScode:PABO).
CESFAPIRSDcontrolsincorporateapassiveinfra-redquadsensorto
detectmovementofawarmbodywithintheirdetectionzone(diagram
A)andaphotocelltomonitortheambientlightlevel.
Whenenteringtheroom,iftheambientlightisdarkenough,thelightscan
beactivatedbyusingamomentarylightswitch.Theambientthreshold
canbesetbytheusertobetweenapproximately30luxand1000lux
and maximum (photocell inactive) at the PIR via the LUX adjuster
(diagram B). Ifno more movementis detected within apre-selected
time,thentheCESFAPIRSDwillswitchtheloadoff.Thistimelagcan
besetviatheTIMEadjusterto10seconds,20s,40s,80s,2m30s,5m,
10m,20mor40minutes(diagramB).
Pressingthemomentaryswitch again(whileCESFAPIRSDisin its
ONstate)willoperatetheSWITCHANDDIMfunctionoftheballast.
Pleaserefertoballastmanufacturer’sdatasheetsforoperationand
synchronisationoftheballast.
Loading
CESFAPIRSDcanswitchupto:
6amps(1500W)ofresistiveloads.
6amps(1500W)ofuorescentloads.
3amps(750W)ofelectronicandwirewoundtransformerloads.
2amps(500W)ofCFL,2Dlamps,LEDDriversandLEDlamps
andttings.
1amp(250W)offans.
Minimumload2Wresistive,suitableformostenergysavinglamps,
LEDsandemergencyttings.
15/12/15 INS232 CESFAPIRSD
Troubleshooting
The load will not switch on:
• TheLUXadjusterissettoolowandisinhibitingtheswitch.
• ThemovingbodyisnotemittingmoreIRthanthebackground.
  (Personwearinginsulatingclothinginawarmenvironment)
• PersonistoofarfromthePIRswitch,seedetectiondiagram.
• Personismovingunusuallyslowly(perhapswhentesting).
• PleasecontactDANLERSforfurthertechnicalsupport.
Momentary switches
DANLERScansupplyarangeofMomentary/Retractiveswitches-
push to make or break:
MOMSWMP-PlatedgreymetalnishwithPRESSpreprintedonswitch.
MOMSWM-Platedgreymetalnishwithblankswitch.
MOMSWWHP-PlatedwhitenishwithPRESSpreprintedonswitch
MOMSWWH-Platedwhitenishwithblankswitch.
MOMSWPMOD-GridmodulesuitableforMKGridPluswithPRESS
preprintedonswitch.
MOMSWMOD-GridmodulesuitableforMKGridPluswithblankswitch.
Installation procedure
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
2.
POSITIONING: The CESFAPIRSD should be installed to achieve
correct
coverageofthearea,seediagramA.
Ifthephotocelloverride
facilityisrequired,theswitchmustbelocatedaboveanareawhere
daylightcangivegreaterilluminationthanthearticiallight.Avoid
locatingthisproductwhereitisexposedtowindyordraftyconditions
(exposed lobbies, open ceiling voids or near ventilation fans) or
nearheatsources.TocoverlargeareasCESFAPIRSDsshouldbe
spacedina5metregridformation.
3.
The greatest energy savings will be made if each
CESFAPIRSD
controls
anindependentsetoflamps.Theycanbewiredinparallel
but this should ideally be limited to three, see diagram D.
4.Makesurethepowerisisolatedfromthecircuit.
The
CESFAPIRSD
shouldbeconnectedasshownindiagramsC&D:
L-Livein.N-Neutralin.SW1 -Switchinput.SL-SwitchedLineout.
Start-up mode
WhentheCESFAPIRSDispoweredup,itwillswitchontheloadfor1
minute,theloadwillthenswitchoffandtheCESFAPIRSDwillenter
itsOperatingMode.
Time and Lux set-up
Forconvenience,ensurethattheTIMEissettotheminimumwhen
settinguptheLUXlevel.AfterwardssettheTIMEtoavaluesuitable
fortheapplication,makingreferencetodiagramB.
TheLUXisbestsetupwhenthelocalambientlightisatapproximately
theminimumdesiredworkinglightlevel.WiththeLUXsetfullyclockwise
waitforthe
CESFAPIRSD
toswitchoff.SteptheLUXadjusterslowly
anticlockwise(- to+), at eachposition operatethe momentary wall
switchandcontinuinguntilthelampsswitchon.
Typical settings
TIME
min max
LUX
max min
30 LUX
1000 LUX
PHOTOCELL
INACTIVE
40m
20m
10m
5m
2.5m
80s
10s
20s
40s
up to 5m
up to 7m
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
For optimum coverage
recommended mounting
height: 2.4 to 5m
A: Detection diagram
C: Wiring diagram, Single CESFAPIRSD
D: Wiring diagram, multiple CESFAPIRSD’s
B: Adjusting time and lux
L
N
load
CESFAPIRSD or
CESRAPIRSD
230 VAC
L
SW1
SL
Mains rated
retractive wall
switch
L
N
Switch / DIm
ballast input
L
Nload
A few
CESFAPIRSD or
CESRAPIRSD
230 VAC
Mains rated
retractive wall
switch
L
SL
Switch / DIm
ballast input
SW1