Danfoss BasicRail / BasicClip - Liquid screed User guide

Type
User guide
Application sheet
BasicRail / BasicClip
Carpet / tiles / parquet / laminate / synthetics
Liquid screed
1
2
3
4
5
1 Carpet / tiles / parquet
2 Liquid screed (≥ CAF F5) 50 mm
3 FH composite pipe (16 mm)
4 Basic Insulation overlap panels 20-2 20 mm
5 Insulation WLG 040 70 mm
6 Basic perimeter insulation
Floor nish NA mm Carpet / tiles / parquet / laminate / synthetics
Construction height 140 mm Height excluding oor nish
Weight ~ 114 kg / m² Weight excluding oor nish
Thermal resistance R 2,19 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,42 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 1,0 kN
Impact subsonic noise reduction 26 dB Calculated value according to DIN 4109; applies to concrete slabs
thicker than 12 cm (DIN 4109: m² > 276 kg/m²).
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3.
Requirements & special features
A screed thickness of 60 mm must be maintained with CAF-F4 tile screeds.
The screed thicknesses must be adjusted in case of higher design load or point load
values.
Observe all installation instructions and manufacturer’s instructions.
Additional insulation
Insulation: 70 mm EPS 040 DEO
Construction
According to EnEV, EN 1264, DIN 4109, 1055 and 18560
Construction number 111
Technical Data Floors/ceilings exposed to outside air
6
© Danfoss 11/2008
VA.CS.W1.02
Danfoss HES
  • Page 1 1

Danfoss BasicRail / BasicClip - Liquid screed User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI