Application sheet
BasicGrip
Carpet / tiles / parquet / laminate / synthetics
Liquid screed
1
2
3
4
5
1 Carpet / tiles / parquet
2 Liquid screed (≥ CAF F5) 50 mm
3 FH composite pipe (16 mm)
4 BasicGrip panel 11mm insulation 11 mm
5 Insulation WLG 040 40 mm
6 Basic perimeter insulation
Floor nish NA mm Carpet / tiles / parquet / laminate / synthetics
Construction height 101 mm Height excluding oor nish
Weight ~ 110 kg / m² Weight excluding oor nish
Thermal resistance R 1,31 m²K / W The minimum thermal resistance requirement of DIN EN 1264 is
fullled.
Thermal transmission coecient U 0,76 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 1,0 kN
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3.
Requirements & special features
The R value must be increased if the groundwater level is less than or equal to 5 m. A U
value not exceeding 0.5 W/m²K must be maintained in existing buildings and additions
with areas up to 50 m². Structural sealing according to DIN 18195 must be placed be-
neath the oor panel in case of structures facing the ground, and otherwise on the un-
nished oor. A screed thickness of 60 mm must be maintained with CAF-F4 tile screeds.
The screed thicknesses must be adjusted in case of higher design load or point load
values. Observe all installation instructions and manufacturer’s instructions.
Additional insulation
Insulation: 40 mm EPS 040 DEO
Construction
According to EnEV, EN 1264, DIN 4109, 1055 and 18560
Construction number 172
Technical Data Floors/ceilings facing unheated rooms or the ground
6
© Danfoss 11/2008
VA.CT.V1.02
Danfoss HES