Installation and maintenance instructions
Fig. 1
1
2
11
3 a
3 b
7
8
9
6
5
12 1013
18
14 16
17 15 20 2119
4
ELECTRICAL CONNECTIONS AND CURRENTS
Connect the incoming supply to earth (1), neutral terminal block 3 b
and phases L1, L2 and L3 to terminal block group 3 a (see the figure
above) in the control panel. If the STAZ-81 energy analyser has been
selected, connect the incoming supply directly to the energy analyser
(see page 18) Connect the protective earth directly to the earthing bar,
1, (see the figure above). Tighten incoming terminal blocks 3a and b
and earthing bar 1 after connection. Each incoming supply must be
provided with a manually operated lockable main circuit breaker/
load interrupter confirming to Machinery Directive 2006/42/EC and
Standard SS-EN 60204-1 Electrical equipment of machines.
The load interrupter is available as an accessory (STAZ-80). The
safety circuit breaker is available as a motor accessory (APAC).
Protect the incoming power supply of the air handling unit with a
fuse in accordance with current legislation in the country where the
equipment is installed.
1. Earthing bar
2. Transformer
3. Incoming supply, 7,5 kW - 15 kW
a. Connecting phases
Tightening torque: 2,5 - 3,0 Nm
b. Connecting neutral
Tightening torque: 3,2 - 3,7 Nm
CONTROL PANEL
4. Internal operation (red switch)
5. Power supply, air handling unit loads, 3-phase.
6. Air handling unit load short-circuit protection
7. Vertical mounting plate with DIN rail
8. Mounting plate with DIN rail
9. Earthing cable for mounting plate
10. Connection of multiconductor cable
11. Terminal block for connection with eQ cables
12. 24 VAC, also supply to internal DUC 24 VDC
13. Terminal block for selection of supply neutral.
Supplied with jumpers between G0 and PE
14. Control panel electrical supply
15. 230 VAC supply
16. Connection, transformer
17. Connection of thermostat-controlled thermal film
18. Supply to rotary heat recovery unit
19. Glass tube fuse
24 VDC max 1.6A T
24 VAC max 4A T
20. Connect the power supply for G and G0 for the eQ to INPUT.
Internal DUC: Jumper between LOCAL and INPUT (supplied design)
External DUC: Supply of G and G0 from external cabinet to INPUT.
21. Selection of functions on terminal blocks 34 and 42.