Installation and maintenance instructions
FläktGroup DC_8636GB 20180605_R0 We reserve the right to make changes without prior notice
CODE KEY – AIR HEATER, ELECTRIC, DUCT-MOUNTED
EQKK-aaa-bbb-c-d-e-f-g-h
Width/diameter in cm (aaa)
031 = 31,5
040 = 40
050 = 50
060 = 60
080 = 80
090 = 90
100 = 100
110 = 110
120 = 120
140 = 140
150 = 150
160 = 160
Height in cm (bbb)
000 = circular connection (aaa=031,040,050)
030 = 30 (aaa=050,060)
040 = 40 (aaa=080,090)
050 = 50 (aaa=100,110)
060 = 60 (aaa=120,140)
070 = 70 (aaa=150)
080= 80 (aaa=140,160)
Power version (c)
1,2,3
Construction (d)
1 = 3 x 230 V AC (≤ 3kW =2 x 230 v)
2 = 3 x 400 V AC (≤ 3kW =2 x 400 v)
Mains connection (e)
1 = with thyristor and stepping switch
Control connection (f)
1 = with quick-fit connector
Inspection side (g)
1 = Right or left
Construction version (h)
2 = version 2
Connection size
3 x 400 V 3 x 230 V
(only Norway) Minimum flow
m3/s
Kw/Power version Kw/Power version
1 2 3 1 2 3
ø315mm 3** 6 9 2* 6 9 0.12
ø400mm 4.5 915 4.5 915 0.19
ø500mm 10 17 24 10 17 24 0.37
500 x 300mm 2 5 10 2 5 10 0.23
600 x 300mm 2 5 10 2 5 10 0.27
800 x 400mm 512 24 512 24 0.54
900 x 400mm 512 24 512 24 0.48
1000 x 500mm 512 24 512 24 0.75
1100 x 500mm 12 30 43 12 30 43 0.83
1200 x 600mm 12 30 43 12 30 43 1.08
1400 x 600mm 15 34 54 15 34 54 1.26
1500 x 700mm 15 34 54 15 34 54 1.58
1400 x 800mm 23 48 75 23 48 75 1.68
1600 x 900mm 23 48 75 23 48 75 2.16
* 1x230V
** 2x400V
ELECTRICAL CONNECTIONS
1. The installationworkmust only be carried out by a qualified fitter.
2. The power supply, output and overheating protection data of the duct
air heater is specified in the wiring diagram supplied and can be
read on the rating plate on the lid of the heater.Carefully check that
the data of the air heater agrees with the power supply and control
equipment selected.
3. The air heater should be connected to the mains supply across a
fixed round cable. The cable should be rated to fit the relevant site
and ambient temperature.
4. You should not be able to switch on the current to the elements,
unless the associated fan has started first or at the same time.
5. You should not be able to switch off the current to the associated fan,
unless the current to the elements is first or at the same time
switched off. For outputs in excess of 30 kW we recommend that
the fans continue running for at least 3 minutes before they stop to
ensure that the overheating protections will not trip due to remaining
heat.
6. All-pole switching with a contact clearance of at least 3 mm must be
arranged in the fixed installation.
7. The duct heaters are fabricated toDegree of Protection IP 43.
8. The duct heaters are tested and approved by SEMKO in accordance
with the following:
LVD Directives: EN60355-1, EN60335-2-30, 1-4 and
SEMKO111 FA11982. EMC Directives: EN61000-6-2 and
EN61000-6-3.
The air heaterwith built-in controls aremanufactured in accordance
with the directives above and are tested, approved and CE marked in
accordance with EMC Directives: EN61000-6-2 and EN61000-6-3.
9. The air heater is equipped with two over heating protections (one
of which must be reset manually), designed for preventing
overheating if the airflow is too low and if a malfunction occurs in the
plant.
MAINTENANCE
No maintenance is required except a periodic performance check.
Accessing the duct air heater, such as removing the lid,may only be
done by a qualified fitter.
OVERHEATING
If the overheating protection with manual reset has tripped, the
following should be observed:
1. Switch off the current.Accessing the air heater, such as removing
the lid,may only be done by a qualified fitter.
2. Carefully determinewhy the overheating protection has tripped.
3. After you have corrected the fault, reset the heating protection.