Legrand Walkerduct/Walkerduct ProSeries Underfloor Duct Activation Fittings - S165B, S166B Installation guide

Type
Installation guide

Legrand Walkerduct/Walkerduct ProSeries Underfloor Duct Activation Fittings - S165B, S166B

are designed to provide easy access to electrical outlets and data connections in underfloor duct systems. These activation fittings are compatible with both Walkerduct and Walkerduct ProSeries underfloor duct systems and can be installed in concrete floors. The S165B model features a flip lid plate, while the S166B model features a slide cover. Both models include an adjusting ring that allows for precise height adjustment of the activation fitting to ensure a flush fit with the floor surface. Installation is simple and requires only a few basic tools. Once installed, these activation fittings provide a convenient and safe way to access electrical outlets and data connections in underfloor duct systems. Additionally, their durable construction ensures long-lasting performance in commercial and industrial applications.

Legrand Walkerduct/Walkerduct ProSeries Underfloor Duct Activation Fittings - S165B, S166B

are designed to provide easy access to electrical outlets and data connections in underfloor duct systems. These activation fittings are compatible with both Walkerduct and Walkerduct ProSeries underfloor duct systems and can be installed in concrete floors. The S165B model features a flip lid plate, while the S166B model features a slide cover. Both models include an adjusting ring that allows for precise height adjustment of the activation fitting to ensure a flush fit with the floor surface. Installation is simple and requires only a few basic tools. Once installed, these activation fittings provide a convenient and safe way to access electrical outlets and data connections in underfloor duct systems. Additionally, their durable construction ensures long-lasting performance in commercial and industrial applications.

S165B and S166B
Activation Fittings
INSTALLATION INSTRUCTIONS
1. Locate center line of duct from measurement
from Cat. No. 415 insert markers, existing pre-
sets and activations, or junction boxes. Core
drill 4" [102mm] diameter hole in concrete.
NOTE: Do not drill through the top of raceway.
2. Drill 2 1/2" [64mm] diameter hole in
duct concentric with the center of the
4" [102mm] diameter hole.
3. Install attaching ring (Cat. No. 437) in hole
by use of locking tabs in bottom of attaching
ring. As the tabs are tighened, the locking tabs
will rotate on inside of raceway. Tighten these
screws firmly to lock attaching ring in place.
Locking tabs are to be parallel to the center
line of the raceway.
4. Pull wires through hole in bottom of
attaching ring.
5. Install adjusting ring with the aid of three
adjusting screws. Adjust all three adjusting
screws a few turns at a time until adjusting
ring is at desired level.
6. Wire device and then attach to adjusting ring.
7. Place gasket on adjusting ring
8. Attach flange to adjusting ring with three
#8 flat head screws.
9. For S165B: Attach flip lid plate to flange with
four #8 flat head brass screws (see Figure 1).
10. For S166B: Attach slide cover to flange
with four #8 flat head brass screws (see
Figure 2). Remove cover and invert slides
for cable egress and reattach.
Walker
®
electrical systems conform to and
should be properly grounded in compliance with
requirements of the current National Electrical
Code or codes administered by local authorities.
All electrical products may present a possible
shock or fire hazard if improperly installed or
used. Walker electrical products may bear the
mark as UL listed and/or classified and should
be installed in conformance with current local
and/or the National Electrical Code.
Flip Lid Plate
Flange
Flange
437 Attaching Ring
437 Attaching Ring
Adjusting Ring
Adjusting Ring
Gasket
Duplex Receptacle
Slide Cover
Figure 1
Figure 2
Walker Systems, Inc.
1000 Innovation Drive, Williamstown, WV 26187
IB0002-1 0300
IB0002-2
© Copyright 2000 The Wiremold Company All Rights Reserved
  • Page 1 1

Legrand Walkerduct/Walkerduct ProSeries Underfloor Duct Activation Fittings - S165B, S166B Installation guide

Type
Installation guide

Legrand Walkerduct/Walkerduct ProSeries Underfloor Duct Activation Fittings - S165B, S166B

are designed to provide easy access to electrical outlets and data connections in underfloor duct systems. These activation fittings are compatible with both Walkerduct and Walkerduct ProSeries underfloor duct systems and can be installed in concrete floors. The S165B model features a flip lid plate, while the S166B model features a slide cover. Both models include an adjusting ring that allows for precise height adjustment of the activation fitting to ensure a flush fit with the floor surface. Installation is simple and requires only a few basic tools. Once installed, these activation fittings provide a convenient and safe way to access electrical outlets and data connections in underfloor duct systems. Additionally, their durable construction ensures long-lasting performance in commercial and industrial applications.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI