Dwyer CDT-2W44-LCD User manual

Category
Measuring, testing & control
Type
User manual

This manual is also suitable for

Series CDT and CDTR Wall Mount Carbon Dioxide/
Temperature Transmitter
Specications - Installation and Operating Instructions
Bulletin AQ-CDT/CDTR-W
Series CDT and CDTR Wall Mount Carbon Dioxide Temperature Transmitters
accurately monitor the CO
2 concentration and temperature in schools, ofce buildings,
and other indoor environments to help achieve LEED
®
certication. Additionally, the
Series CDTR also measures ambient relative humidity. For increased sensor life,
a single- beam dual-wavelength non-dispersive infrared (NDIR) sensor is used to
automatically correct the measurement in both occupied and unoccupied buildings
against aging effects. The single-beam dual-wavelength sensor technology provides
the highest level of accuracy compared to Automatic Baseline Correction methods,
which can unintentionally shift the calibration based on CO
2 levels and barometric
pressure conditions. In order to achieve a higher level of accuracy, the Series CDT
includes digital barometric pressure adjustment and the ability to eld-calibrate the
sensor.
Universal outputs allow users to select the transmitter output to be 4 to 20 mA, 0 to
5 VDC, or 0 to 10 VDC to work with virtually any building management controller. An
optional relay with user adjustable set points can be used to control exhaust fans, open
actuated windows or dampers, or signal a light or horn.
For applications that require visual indication, the Series CDT and CDTR can be ordered
with an integral LCD display or the Model A-449 remote LCD display that can plug into
the mini-connector port on the side of the transmitter. Both the CDT and CDTR can be
congured to display temperature only, CO
2 only, or CO2 and temperature together.
The CDTR can also display relative humidity or CO
2 and relative humidity together.
Push buttons are standard on the transmitters for access to the menu structure, but
the transmitter can be ordered without the buttons. To prevent tampering, the action of
the buttons can be locked out using an internal jumper selection. Menu items that can
be accessed include: engineering units, relay output set points, display conguration,
transmitter output scaling, ambient barometric pressure and eld calibration of the
transmitter.
Single-beam dual-wavelength sensor advantages:
Automatically corrects for aging effects in occupied and unoccupied buildings
Perfect for hospitals and manufacturing plants that are occupied 24 hours per day
• Measures actual unltered light intensity directly
Eliminates error from incorrect assumptions of gas concentration in theoretical
logic assumption methods
INSTALLATION
LEED
®
is a registered trademark of the U.S. Green Building Council
Disconnect power supply before installation to prevent electrical
shock and equipment damage.
Make sure all connections are in accordance with the job wiring diagram and in
accordance with national and local electrical codes. Use copper conductors only.
Use electrostatic discharge precautions (e.g., use of wrist straps)
during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present.
Do not exceed ratings of this device, permanent damage not
covered by warranty may result.
Upon powering the transmitter, the rmware version will ash on
the display. A warm up period of 30 minutes is required for the
transmitter to adjust to the current CO
2 concentration.
Self calibration feature of the transmitter requires exposure to
normal outdoor equivalent carbon dioxide level once every thirty
days.
NOTICE
NOTICE
7/8 [22.35]
3-13/32 [86.52]
1-13/32
[50.01]
1-53/64
[46.43]
1-13/32
[35.72]
3X 3/8
[9.53]
4-31/64
[113.9]
35/64
[13.89]
4X 3/16
[4.76]
1-3/16
[30.20]
1-3/16
[30.20]
SPECIFICATIONS
Range: CO
2: 0 to 2000 or 0 to 5000 ppm (depending on model); RH: 0 to 100% (for
units congured with humidity output); Temperature: 32 to 122°F (0 to 50°C);
Accuracy: ±40 ppm +3% of reading; RH: ±2% (for units congured with humidity
output); Temperature: ±1°C @ 25°C.
Temperature Dependence: ±8 ppm / °C at 1100 ppm.
Non-Linearity: 16 ppm.
Pressure Dependence: 0.13% of reading per mm of Hg.
Response Time: 2 minutes for 99% step change.
Temperature Limits: 32 to 122°F (0 to 50°C).
Humidity Limits: 10 to 95% RH (non-condensing).
Power Requirements: 16 to 35 VDC / 19 to 28 VAC.
Power Consumption: Average: 2 watts; Peak: 3.75 watts.
Sensor: Single-beam, dual-wavelength NDIR.
Output: Current: 4 to 20 mA (max 500 Ω); Voltage: 0 to 5 VDC or 0 to 10 VDC
(min 500 Ω); Relay: SPST NO 2A @ 30 VDC; RTD or thermistor per r-t curves
(depending on model).
Weight: 5.6 oz (158.8 g).
WARNING
CAUTION
CAUTION
CAUTION
®
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
MOUNTING
1. Push tab on bottom of cover and lift cover from back plate (See Figure 1).
2. Select the mounting location, away from diffusers, lights or any external inuences.
3. Mount transmitter on a vertical surface to a standard electrical box using the two
#6 M2C type screws provided.
4. Pull wires through sub base hole and make necessary connections.
5. Reattach cover to base plate.
WIRING
Use maximum 18 AWG wire for wiring to terminals. Refer to Figure 5 for wiring
information.
Selection of Current and Voltage Outputs
Prior to wiring, verify that the current/voltage selection jumpers (PJ1, PJ2, and PJ5)
are set to the desired output type. Refer to Figure 2 to locate the selection jumpers.
See Figure 3 for diagram of the current/voltage selection jumper. For voltage output
selection, the output can be 0 to 10 VDC, 0 to 5 VDC, 2 to 10 VDC or 1 to 5 VDC. See
Figure 4 for the type of voltage output selection jumper (PJ5).
Current / Voltage Outputs
On the CDT, the transmitter may be wired for current or voltage output for both carbon
dioxide and temperature. On the CDTR, the transmitter may be wired for current or
voltage output for both carbon dioxide and humidity. The transmitter can be powered
with either 16 to 35 VDC or 19 to 28 VAC. Wire the transmitter according to Figure 5.
Remote Display
For models that are ordered without an integral LCD display, remote display Model
A-449 can be used to display the temperature, humidity, and carbon dioxide. The mini
USB plug of the remote display plugs into the receptor on the side of the housing.
After a short warm up time, the display will begin to show the current temperature and
carbon dioxide measurements unless congured by the user to show humidity and
carbon dioxide, only temperature, only humidity, or only carbon dioxide.
EDITING MENU PARAMETERS
Before any adjustment can be made to the transmitter, the Menu Lockout Jumper
(PJ4) must be set to the ˝On˝ position (See Figure 6).
ACCESSING MENU PARAMETERS
Step 1: To enter the menu structure, press
and simultaneously for 5
seconds (display will show RON parameter).
Step 2: Press
or to cycle between menu items.
Step 3: Press
to edit the value for the displayed menu item (SET will appear on
display).
Step 4: Press
or to adjust the value of the menu item.
Step 5: Press
to save the changes (SET will disappear).
Step 6: Repeat Steps 2 through 5 for each of the parameters.
Step 7: To exit the menu at any time, press and hold
and simultaneously
for 5 seconds or wait 10 seconds without pushing any buttons.
PASSIVE
TEMPERA
TURE
SENSOR
RELAY
CONTACT
POWER
SUPPLY
TEMP OR RH
RECEIVER
CO2
RECEIVER
Figure 1: Removal Of Cover From Back Plate
Figure 5: Active Output Wiring Diagram
Figure 2: Diagram Of Circuit Board
Optional relay can be used as either a dry contact or low voltage
switched circuit up to 2 A at 30 VDC.
NOTICE
HINGE
BOTTOM TAB
SELF-LATCHING
COVER
MOUNTING
BACK PLATE
MOUNTING
SCREWS
TO REMOVE COVER
APPLY PRESSURE TO
BOTTOM TAB WHERE
INDICATED AND THE
TWO PARTS WILL
BECOME UNHINGED
AT TOP
REVERSE PROCESS
TO APPLY COVER
PJ2
PJ1
PJ4
PJ5
CURRENT
OUTPUT
VOLTAGE
OUTPUT
C
C
VV
Figure 3: Current/Voltage Output
Selection Jumper (PJ1 and PJ2)
Figure 4: Output Range Selection Jumper (PJ5)
Figure 6: Menu Lockout Jumper
2 to10 V
4 to 20 mA
0 to 10 V
0 to 20 mA
0 to 5 V
0 to 10 mA
1 to 5 V
2 to 10 mA
ENABLED
DISABLED
OFF
MENU MENU
PJ4
PJ4
OFFON
ON
Relay on set point
Sets the CO
2 concentration which the optional relay is energized.
Low limit: 0 PPM
Factory setting: 1000 PPM
High limit: 2000/5000 PPM (depending on model)
Relay off set point
Sets the CO2 concentration which the optional relay is de-energized. Setting
value lower than RON provides direct action for detecting high concentrations
of CO
2. Setting value higher than RON provides indirect action for detecting
low concentrations of CO
2. or on the LCD display will be lit to
indicate when the relay is energized.
Low limit: 0 PPM
Factory setting: 950 PPM
High limit: 2000/5000 PPM (depending on model)
Display conguration
Determines the LCD display conguration during normal operation. The LCD
display can indicate the CO
2 concentration, temperature, relative humidity
(CDTR only) and CO
2 concentration combined with temperature or relative
humidity (CDTR only).
CH CO
2 concentration and relative humidity (CDTR only)
CT CO
2 concentration and temperature
C CO
2 concentration only
T Temperature only
H Relative humidity only (CDTR only)
Units selection
Temperature and barometric pressure measurements can be displayed in US
engineering units or SI engineering units. The factory default is to display US
engineering units.
US units °F for temperature and in Hg for barometric pressure
SI units °C for temperature and hPa for barometric pressure
CO
2 low output range
Sets the CO
2 concentration for the lowest output (4 mA or 0 VDC).
Low limit: 0 PPM
Factory setting: 0 PPM
High limit: 2000/5000 PPM (depending on model)
CO
2 high output range
Sets the CO
2 concentration for the highest output (20 mA, 5 VDC or 10 VDC).
When COH is set above COL, the transmitter is direct acting and the output
will increase with an increase in CO
2 level. When COH is below COL, the
transmitter is reverse acting and the output will increase with a decrease in
CO
2 level.
Low limit: 0 PPM
Factory setting: 2000/5000 PPM (depending on model)
High limit: 2000/5000 PPM (depending on model)
Temperature low output range (CDT with active temperature only)
Sets the temperature for the lowest output (4 mA or 0 VDC).
Low limit: 32.0°F / 0.0°C
Factory setting: 32.0°F / 0.0°C
High limit: 122.0°F / 50.0°C
Temperature high output range (CDT with active temperature only)
Sets the temperature for the highest output (20 mA, 5 VDC or 10 VDC).
When TOH is set above TOL, the transmitter is direct acting and the output
will increase with an increase in temperature. When TOH is below TOL, the
transmitter is reverse acting and the output will increase with a decrease in
temperature.
Low limit: 32.0°F / 0.0°C
Factory setting: 122.0°F / 50.0°C
High limit: 122.0°F / 50.0°C
RON
ROF
DSP
UNI
COL
COH
TOL
TOH
HOL
HOH
BAR
CAL
Humidity low output range (CDTR only)
Sets the temperature for the lowest output (4 mA or 0 VDC).
Low limit: 0.0%
Factory setting: 0.0%
High limit: 100.0%
Humidity high output range (CDTR only)
Sets the temperature for the highest output (20 mA, 5 VDC or 10 VDC).
When HOH is set above HOL, the transmitter is direct acting and the output
will increase with an increase in temperature. When HOH is below HOL, the
transmitter is reverse acting and the output will increase with a decrease in
temperature.
Low limit: 0.0%
Factory setting: 100.0%
High limit: 100.0%
Barometric pressure
Sets the typical barometric pressure for the location where the transmitter is
mounted. The factory setting is for standard pressure at sea level. Adjusting the
barometric pressure gives a more accurate measurement, especially at higher
elevations. Refer to the elevation charts in Figure 9 for typical barometric
pressures at a given elevation.
Low limit: 20.0 in Hg / 600 hPa
Factory setting: 29.9 in Hg / 1013 hPa
High limit: 32.0 in Hg / 1100 hPa
Calibration
Calibrates the carbon dioxide sensor to a known gas value. Read calibration
instructions before using this feature. Hold
for 5 seconds.
Menu Descriptions
CALIBRATING SENSOR
Step 1: Remove the cover as shown in Figure 1.
Step 2: Slide the calibration tubing through the slots on the back plate and attach to
one of the nipples on the CO2 sensor (See Figure 7).
Step 3: Carefully re-attach the cover to the back plate without pinching the tubing
between the back plate and the cover.
Step 4: Follow the steps in the accessing parameter section to access the
calibration parameter (CAL).
Step 5: Press the
button.
Step 6: Flow zero reference gas at 0.3 SLPM for 5 minutes.
Step 7: Press and hold the
button for 3 seconds.
Step 8: Flow the full scale reference gas at 0.3 SLPM for 5 minutes.
Step 9: Press and hold the
button for 3 seconds.
Step 10: Exit the parameter menu.
Step 11: Remove cover as shown in Figure 1.
Step 12: Remove tubing from sensor and re-attach the gas nipple cover to the sensor.
Step 13: Re-attach the cover to the back plate.
©Copyright 2019 Dwyer Instruments, Inc. Printed in U.S.A. 1/19 FR# 443800-20 Rev. 3
MAINTENANCE/REPAIR
Upon nal installation of the Series CDT and CDTR, no routine maintenance is
required. The Series CDT and CDTR are not eld serviceable and should be returned
if repair is needed. Field repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.
Series CDT -2 N 4 4 -LCD Example: CDT-2W44-LCD
Range 2
5
0 to 2000 ppm CO
2 range
0 to 5000 ppm CO
2 range
Conguration W Wall
CO
2 Output 4 4 to 20 mA / 0 to (5 or 10) VDC
Temperature
Output
0
4
A
B
C
D
E
F
None
4 to 20 mA / 0 to (5 or 10) VDC
10 KΩ NTC thermistor type III
10 KΩ NTC thermistor type II
3 KΩ NTC thermistor
Pt100 Ω RTD
Pt1000 Ω RTD
20 KΩ NTC thermistor
Options LCD
RLY
NBC
LCD display
Relay
No buttons
US Customary Units
ft in Hg
0
400
800
1200
1600
2000
2400
2800
3200
3600
4000
4400
4800
5200
5600
6000
6400
6800
7200
7600
8000
8400
8800
9200
9600
10000
29.92
29.50
29.10
28.69
28.29
27.90
27.51
27.13
26.76
26.39
26.02
25.66
25.30
24.95
24.60
24.26
23.93
23.60
23.27
22.94
22.63
22.31
22.00
21.70
21.40
21.40
SI Units
m hPa
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1013
1002
990
979
968
957
946
935
924
914
904
893
883
873
863
853
844
834
824
815
806
797
787
779
770
761
Series CDTR -2 W 4 A 4 -LCD Example: CDTR-2W4A4-LCD
Range 2
5
0 to 2000 ppm CO
2 range
0 to 5000 ppm CO
2 range
Conguration W Wall
CO
2 Output 4 4 to 20 mA / 0 to (5 or 10) VDC
Temperature
Output
0
A
B
C
D
E
F
None
10 KΩ NTC thermistor type III
10 KΩ NTC thermistor type II
3 KΩ NTC thermistor
Pt100 Ω RTD
Pt1000 Ω RTD
20 KΩ NTC thermistor
RH Output 4 4 to 20 mA / 0 to (5 or 10) VDC
Options LCD
RLY
NBC
LCD display
Relay
No buttons
Temperature Resistance Curves (in Ohms)
°C °F A B C D E F
-55
-50
-45
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
-67.0
-58.0
-49.0
-40.0
-31.0
-22.0
-13.0
-4.0
5.0
14.0
23.0
32.0
41.0
50.0
59.0
68.0
77.0
86.0
95.0
104.0
113.0
122.0
131.0
140.0
149.0
158.0
167.0
176.0
185.0
194.0
203.0
212.0
221.0
230.0
239.0
248.0
257.0
266.0
275.0
284.0
293.0
302.0
607800.00
441200.00
323600.00
239700.00
179200.00
135200.00
102900.00
78910.00
61020.00
47540.00
37310.00
29490.00
23460.00
18780.00
15130.00
12260.00
10000.00
8194.00
6752.00
5592.00
4655.00
3893.00
3271.00
2760.00
2339.00
1990.00
1700.00
1458.00
1255.00
1084.00
939.30
816.80
712.60
623.60
547.30
481.80
425.30
376.40
334.00
297.20
265.10
237.00
963849.00
670166.00
471985.00
336479.00
242681.00
176974.00
130421.00
97081.00
72957.00
55329.00
42327.00
32650.00
25392.00
19901.00
15712.00
12493.00
10000.00
8057.00
6531.00
5326.00
4368.00
3602.00
2986.00
2488.00
2083.00
1752.00
1480.00
1255.00
1070.00
915.50
786.60
678.60
587.60
510.60
445.30
389.60
341.90
301.00
265.80
235.30
208.90
186.10
289154.70
201049.80
141595.50
100943.70
72804.30
53092.20
39126.30
29124.30
21887.10
16598.70
12698.10
9795.00
7617.60
5970.30
4713.60
3747.90
3000.00
2417.10
1959.30
1597.80
1310.40
1080.60
895.80
746.40
624.90
525.60
444.00
376.50
321.00
274.65
235.98
203.58
176.28
153.18
133.59
116.88
102.57
90.30
79.74
70.59
62.67
55.83
78.32
80.31
82.29
84.27
86.25
88.22
90.19
92.16
94.12
96.09
98.04
100.00
101.95
103.90
105.85
107.79
109.74
111.67
113.61
115.54
117.47
119.40
121.32
123.24
125.16
127.08
128.99
130.90
132.80
134.71
136.61
138.51
140.40
142.29
144.18
146.07
147.95
149.83
151.71
153.58
155.46
157.33
783.2
803.1
822.9
842.7
862.5
882.2
901.9
921.6
941.2
960.9
980.4
1000.0
1019.5
1039.0
1058.5
1077.9
1097.4
1116.7
1136.1
1155.4
1174.7
1194.0
1213.2
1232.4
1251.6
1270.8
1289.9
1309.0
1328.0
1347.1
1366.1
1385.1
1404.0
1422.9
1441.8
1460.7
1479.5
1498.3
1517.1
1535.8
1554.6
1573.3
2394000.00
1646200.00
1145800.00
806800.00
574400.00
413400.00
300400.00
220600.00
163500.00
122280.00
92240.00
70160.00
53780.00
41560.00
32340.00
25360.00
20000.00
15892.00
12704.00
10216.00
8264.00
6722.00
5498.00
4520.00
3734.00
3100.00
2586.00
2166.00
1822.60
1540.00
1306.40
1112.60
951.00
815.80
702.20
606.40
525.60
N/A
N/A
N/A
N/A
N/A
Figure 8: CDT Model Chart
Figure 7: Calibration
Figure 9: Elevation Chart
Figure 10: Resistance vs Temperature
RESISTANCE VS TEMPERATURE TABLE
Figure 9: CDTR Model Chart
CO
2
SENSOR
This symbol indicates waste electrical products should not be disposed
of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
dwyer-inst.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Dwyer CDT-2W44-LCD User manual

Category
Measuring, testing & control
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI