  • Hello! I am an AI chatbot trained to assist you with the FläktGroup eQ Controls STBZ-50 and STAZ-50 Installation and Maintenance Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
FläktGroup DC_9806GB 20180525_R0 We reserve the right to make changes without prior notice
CO2 SENSOR
STBZ-50, STAZ-50, STCZ-82
DATASHEET
FEATURES
3 sensors in one enclosure
Infrared CO
2
measuring technology (NDIR)
Internally separated measuring chamber for humidity and
temperature
5 year warranty
Normally maintenance-free
Reduces energy costs for demand-driven ventilation
FUNCTION
The sensor is an advanced and versatile 3-in-1 controller and
measures the CO
2
concentration, temperature and relative
humidity in the ambient atmosphere. It has a change-over
relay output and three separate 0-10V outputs, of which one is
pre-programmed as a combined output for CO
2
, temperature and
relative humidity.
This combined 0-10V output has three separate P bands for CO
2
(600-900 ppm), temp-erature (22-23 °C) and relative humidity
(75-85% RH). Configurations and preferences are set using a PC.
OPERATION
The sensor combines all the data necessary to effectively
regulate the indoor environment in buildings such as offices,
hotels and schools. The use of CO
2
measurement for demand-
driven ventilation results in a healthy, comfortable and cost
effective environment in the building.
INSTALLATION
The sensor is installed in a normal indoor environment on a
wall where it is not exposed to direct sunlight or draughts.
When installing the unit over a mounting box or conduit these
must be sealed so as to prevent draughts that could affect the
performance and accuracy of the unit.
Fig. 1 Terminal block for connection
NC Relay
COM Relay
NO Relay
OUT(3)
OUT(2)
OUT(1)
Max
24V AC/DC
+_ 20 %
2
Datasheet
FläktGroup DC_9806GB 20180525_R0 We reserve the right to make changes without prior notice
TECHNICAL DATA
Supply voltage: 12V DC, 24V AC/DC ± 20 %, (50-60Hz)
Power consumption Average:
Max./peak:
Output signal/P band:
Relay output:
< 0.35W
< 2W
Rout <100, Load: >5 k
Activated > 1000 ppm CO2
Deactivated > 900 ppm CO2
OUT1 Combined output:
CO2:
Temperature:
Relative humidity:
0-10V DC
600-900 ppm
22-23°C
75-85% RH
OUT2 CO2: 0-10V DC, 0-2000 ppm
OUT3 Temperature: 0-10V DC, 0-50 °C
CO2Accuracy:
Measuring method:
Measuring interval:
± 3 % of the measured value
NDIR
15 s
Temperature sensor Accuracy:
Measuring interval:
0,3 °C *2
15 s
Relative humidity: Accuracy*:
Measuring interval:
5 % RH (@ 20-80 % RH)
15 s
Relay Change-over potential-free: 1A, 50V AC/24V DC
Storage temperature:
Operating temperature:
Operating humidity:
Dimensions (HxWxD):
Enclosure class:
-30 to +70 °C
0 to +50 °C
0-95 % RH
125x85x22 mm
IP20
* Measurement accuracy depends on the installation of the product. See the heading INSTALLATION.
/