Dwyer Wireless Temperature/Humidity User manual

Type
User manual
Wireless Output Modules are designed to work with Series
WHP and Series WTP wireless humidity and temperature
sensors. Output modules are available with current, voltage,
resistive thermistor or relay contact outputs. For quick
installation, the output modules can be plugged directly into the
receiver without any wires. The integral mounting tabs allow for
the output modules to be DIN rail mounted or surface mounted.
For applications that require multiple output signals, more than
one output module can be trained to a single wireless humidity
or temperature sensor.
Wireless products are intended for use in U.S. territories,
Canada and Mexico only.
MOUNTING & TERMINATION
Output modules can be mounted to a flat surface, 2.75˝
snaptrack or 35 mm DIN rail. On the sides of the modules there
are two sets of terminal blocks for communication bus and
power bus. If relying on the receiver to provide communication
and power directly to the output module, the terminal blocks can
be removed and the pins can snap directly into the receiver or
other output modules. Otherwise, wires can be connected from
the receiver or other output module to the terminal block. See
the receiver instruction manual for more details.
Wireless Output Modules
Specifications - Installation and Operating Instructions
Bulletin W-WM-OM
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
SPECIFICATIONS
Supply Voltages: Thermistor, Relay, 0 to 5 VDC models: 9 to
30 VDC/17 to 31 VAC; 0 to 10 VDC models: 15 to 30 VDC/17
to 35 VAC; Current models: Loop powered 9 to 36 VDC.
Power Consumption: Thermistor, 0 to 5 VDC models: 3 mA
max DC; 0.1 VA max AC; Relay models: 15 mA max (relay on);
Current models: 20 mA max.
Temperature Limits: Ambient: 32 to 140°F (0 to 60°C).
Humidity Limits: Ambient: 5 to 95% (non-condensing).
Output: Thermistor: 35 to 120°F (1 to 50°C) 10K Type II or
10K Type III (depending on model); Relay: 40 V, 150 mA max;
Voltage: 0 to 5 VDC or 0 to 10 VDC (depending on model);
Current: 4 to 20 mA.
Output Resolution: 10 bit (voltage), 12 bit (current), 40Ω
(resistance).
Housing Material: ABS UL 94V-0 plastic.
Weight: 1.9 oz (54 g).
FCC Approval: FCC ID# T4F06811RH.
Agency Approvals: RoHS.
©Copyright 2010 Dwyer Instruments, Inc. Printed in U.S.A. 6/10 FR# R6-443764-00
Possible Problem
Power LED does not light
Transmissions not getting
through
Possible Solution
Make sure that power is plugged
into unit and that it is turned on.
Make sure that the transmitters
and receiver are powered up and
operating properly. Make sure
that the repeater is within range
of the transmitter and receiver.
TROUBLESHOOTING
1-9/32
[32.51]
1-15/16
[49.19]
2-31/32
[75.38]
2-3/4
[69.85]
WM-TSX-XX (SURFACE MOUNT MODELS)
W-WM-OM:TEMPLATE 6/2/10 4:05 PM Page 1
  • Page 1 1

Dwyer Wireless Temperature/Humidity User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI