4
3Installing Cables
•Connect UPS AC input and output power cables in the same phase sequence. Connect battery
terminals correctly.
•Before connecting cables to the UPS, ensure that the input, output, and battery circuit breakers
are OFF to prevent operations with power applied.
Installing Cables for a Single UPS
Scenario 1
Wiring Terminal Input (AC INPUT) Output (AC OUTPUT)
External Circuit Breaker 32 A
Earth Leakage Circuit Breaker 100 mA -
Cable Cross-sectional Area 6 mm²
Terminal Type OT-6 mm2-M5 terminal
Torque for Tightening Bolts 2 N·m
1. Install AC input and output power cables.
Installing Power Cables
3.1
1. The UPS2000-G-6KRTLL needs to connect to external lithium batteries ESM-48100B1 or
ESM-48150B1. Each UPS supports a maximum of 16 batteries connected in parallel. This
document uses four lithium batteries connected in parallel as an example.
2. When lithium batteries are connected, it is recommended that a DC circuit breaker (150 A 80
V DC circuit breaker for the 6 kVA UPS) be installed between the lithium batteries and the
UPS.
3. Before connecting cables to the UPS, ensure that the battery circuit breakers are OFF to
prevent operations with power applied.
4. If the UPS shares a battery string, the PE bar and battery busbar are configured.
2. Install battery cables.