Schneider Electric AK5JB143 User manual

Type
User manual

Schneider Electric AK5JB143 is a circuit breaker designed for use in Schneider Electric switchboards, capable of delivering up to 18k Amperes of symmetrical current at a maximum voltage of 480 Volts. It requires Class RK5 fuses rated at a maximum of 225 Amps. This device offers protection against electrical hazards and can be used in various applications, including industrial and commercial settings, to safeguard electrical systems and equipment.

Schneider Electric AK5JB143 is a circuit breaker designed for use in Schneider Electric switchboards, capable of delivering up to 18k Amperes of symmetrical current at a maximum voltage of 480 Volts. It requires Class RK5 fuses rated at a maximum of 225 Amps. This device offers protection against electrical hazards and can be used in various applications, including industrial and commercial settings, to safeguard electrical systems and equipment.

Linergy HK
zh
AK5JBpppp / AK5PCpppp / AK5PApppp
fr
en de
es pt it ru
Les instructions de ce document
décrivent le montage de Linergy HK
dans un tableau Schneider électric.
Le montage dans tout autre tableau
est de la responsabilité du metteur
en œuvre.
Las instrucciones de este documento
describen el montaje de Linergy HK
en un cuadro Schneider Electric.
El montaje de dicho sistema en
cualquier otro panel será
responsabilidad del instalador.
Die Anweisungen in diesem Dokument
beschreiben die Montage der Linergy HK
in einer Schneider Electric-Schaltanlage.
Die Montage in einer anderen
chaltanlage obliegt dem Nutzer.
The instructions in this document
describe how to fit Linergy HK in a
Schneider Electric switchboard.
The installer is fully liable if it is fitted in
any other switchboard.
Le presenti istruzioni descrivono il
montaggio di Linergy HK in un quadro
Schneider Electric.
Il montaggio in qualsiasi altro quadro
ricade sotto la responsabilità
dell'installatore.
As instruções deste documento
descrevem a montagem de Linergy
HK num quadro Schneider Electric.
A montagem em qualquer outro
quadro é da responsabilidade do
instalador.
Инструкции в данном документе
объясняют как установить HK в
распределительный щит
Schneider Electric.
Ответственность за установку в
любой иной распределительный щит
полностью лежит на монтажнике.
本文阐释如何在 Schneider Electric
配电盘中安装 Linergy HK。
如果安装在任何其它配电盘中,
该安装程序也同样适用。
AK5JB143 / AK5JB144 /
AK5JB145 / AK5JB146
AK5JB143
AK5JB144
AK5JB145
AK5JB146
330
438
L
546
654
AK5PC pppp AK5PA pppp
x2
REMARQUE IMPORTANTE
L’installation, l’utilisation, la réparation
et la maintenance des équipements
électriques doivent être assurés
uniquement par du personnel qualifié.
Schneider Electric décline toute
responsabilité quant aux
conséquences de l’utilisation de ce
matériel.
PLEASE NOTE
Electrical equipment should be installed,
operated, serviced, and maintained
only by qualified personnel.
No responsibility is assumed by
Schneider Electric for any
consequences arising out of the
use of this material.
TENGA EN CUENTA
La instalación, manejo, puesta en
servicio y mantenimiento de equipos
eléctricos deberán ser realizados sólo
por personal cualificado.
Schneider Electric no se hace
responsable de ninguna de las
consecuencias del uso de este
material.
BITTE BEACHTEN
Elektrische Geräte dürfen nur von
Fachpersonal installiert, betrieben,
bedient und gewartet werden.
Schneider Electric haftet nicht für
Schäden, die durch die Verwendung
dieses Materials entstehen.
NOTA
Manutenzione, riparazione, installazione
e uso delle apparecchiature elettriche si
devono affidare solo a personale
qualificato.
Schneider Electric non si assume
alcuna responsabilità per qualsiasi
conseguenza derivante dall’uso di
questo materiale.
NOTA
A instalação, utilização e manutenção
do equipamento eléctrico devem ser
efectuadas exclusivamente por
pessoal qualificado.
A Schneider Electric não assume
qualquer responsabilidade pelas
consequências resultantes da
utilização deste material.
请注意
电气设备的安装、操作、维修和维护工
作仅限于合格人员执行。
Schneider Electric不承担由于使用
本资料所引起的任何后果。
ОБРАТИТЕ ВНИМАНИЕ
Установка, эксплуатация, ремонт и
обслуживание электрического
оборудования может выполняться
только квалифицированными
электриками.
Компания Schneider Electric не несет
никакой ответственности за любые
возможные последствия
использования данной документации.
EAV6376201
01/2022 - 1/4
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
L
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
AK5JB149 / AK5JB1410
AK5JB149
AK5JB1410
L
978
1086
x2
L
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
EAV6376201
2/4
A’’’
AK5JB pppp
6 N.m
LVS03001
LVS03401
LVS03166
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
AF1-CD 061
AA’
AM1-PA
AF1-EA6 AM1-EC
AF1-CD6
AK5JB pppp AK5JB pppp
6 N.m6 N.m
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
b Suitable for use on a circuit capable of delivering not more than the below data:
p 18 kA rms Symmetrical Amperes
p 480 V maximum
b Use fuses only:
p Class RK5
p Rated 225 A maximum
UL Technical Data
A’AK5JB pppp
AM1-ED
6 N.m
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
AF1-CF 56
2
1
=
=
AK5JB149
AK5JB1410
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
B
EAV6376201 3/4
C
min
DZ5-C
max
²mm01²mm5,2
70 mm²
2 x 16 mm²
1 x 50 mm²
2 x 16 mm²
2,5 mm²
36 mm²
35 mm²
36 mm²
2 x 36 mm²
+
-
3
4
da
a = d + 2 mm
5
10 N.m
3’
4’
10 N.m
N L1 L2 L3
N L1 L2 L3
N + L1 + L2 + L3
c + L1 + L2 + L3
1
2
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
6
HAZARD OF EQUIPMENT DAMAGE
b Electrical equipment should be installed and serviced only
by qualified personnel.
b Turn off swich before removing or installing the plug-in
connection or the wires.
Failure to follow these instructions can result in injury
or equipment damage.
OFF ON
AK5PApppp
AK5PApppp
OFF ON
1
2
4
3
5
7
6
AK5PCpppp
AK5PCpppp
OFF ON
1
2
3
4
5
OFF ON
1
2
3
4
5
OFF ON
6
4
5
7
8
1
2
3
EAV6376201 4/4
© 2022 Schneider Electric - All rights reserved.
Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F - 92506 Rueil Malmaison Cedex
www.se.com
AM1-ED AM1-ED
.
En raison de l'évolution des normes et du matériel, les caractéristiques
indiquées par le texte et les images de ce document ne nous engagent
qu'après confirmation par nos services.
As standards, specifications and designs change from time to time,
please ask for confirmation of the information given in this publication.
Ce document a été imprimé
sur du papier écologique.
This document has been
printed on ecological paper
Publication : Schneider Electric
Réalisation : Schneider Electric
Impression :
Format de pliage : 210 x 297 mm
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Schneider Electric AK5JB143 User manual

Type
User manual

Schneider Electric AK5JB143 is a circuit breaker designed for use in Schneider Electric switchboards, capable of delivering up to 18k Amperes of symmetrical current at a maximum voltage of 480 Volts. It requires Class RK5 fuses rated at a maximum of 225 Amps. This device offers protection against electrical hazards and can be used in various applications, including industrial and commercial settings, to safeguard electrical systems and equipment.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI