Application sheet
BasicGrip
Carpet / tiles / parquet / laminate / synthetics
Liquid screed
1
2
3
4
5
1 Carpet / tiles / parquet
2 Liquid screed (≥ CAF F5) 50 mm
3 FH composite pipe (16 mm)
4 BasicGrip panel 35mm insulation 35 mm
5 Insulation WLG 040 20 mm
6 Basic perimeter insulation
Floor nish NA mm Carpet / tiles / parquet / laminate / synthetics
Construction height 105 mm Height excluding oor nish
Weight ~ 110 kg / m² Weight excluding oor nish
Thermal resistance R 1,35 m²K / W
Thermal transmission coecient U 0,74 W / m²K If the architectural design species better thermal insulation, this
must be taken into account.
Design load ≤ 2,0 kN / m²
Point load (≥ 20 cm²) ≤ 1,0 kN
Impact subsonic noise reduction 28 dB Calculated value according to DIN 4109; applies to concrete slabs
thicker than 12 cm (DIN 4109: m² > 276 kg/m²).
Application area
Residential spaces, hallways and attic spaces in residential buildings and hotel rooms.
Corresponds to categories A1, A2 and A3 of DIN 1055-3.
Requirements & special features
The R value must be increased if the groundwater level is less than or equal to 5 m. A U
value not exceeding 0.5 W/m²K must be maintained in existing buildings and additions
with areas up to 50 m².
Structural sealing according to DIN 18195 must be placed beneath the oor panel in case
of structures facing the ground, and otherwise on the unnished oor.
A screed thickness of 60 mm must be maintained with CAF-F4 tile screeds.
The screed thicknesses must be adjusted in case of higher design load or point load
values.
Observe all installation instructions and manufacturer’s instructions.
Additional insulation
Insulation: 20 mm EPS 040 DEO
Construction
According to EnEV, EN 1264, DIN 4109, 1055 and 18560
Construction number 179
Technical Data Floors/ceilings facing unheated rooms or the ground
6
© Danfoss 11/2008
VA.DY.B1.02
Danfoss HES