Quadra-Fire 7100FP-NL-B Installation guide

Category
Fireplaces
Type
Installation guide

This manual is also suitable for

R
Installationandserviceofthisreplaceshouldbe
performedbyqualiedpersonnel.Hearth&Home
TechnologiesrecommendsNFIcertiedprofes-
sionals,ortechnicianssupervisedbyan
NFIcertiedprofessional.
EPA CERTIFIED WOODBURNING
FIREPLACE
Fire Risk.
WARNING
For use with solid wood fuel only.
Other fuels may overfi re and generate poisonous
gases (i.e. carbon monoxide).
O-T L
Tested and
Listed by
Portland
Oregon USA
OMNI-Test Laboratories, Inc.
CUS
Model(s):
Installation Manual
Installation and Fireplace Setup
WARNING
HOT SURFACES!
Glassandothersurfacesarehotduring
operationANDcooldown.
Hot glass will cause burns.
• DO NOTtouchglassuntilitiscooled
• NEVERallowchildrentotouchglass
• Keepchildrenaway
CAREFULLY SUPERVISE children in same room as
replace.
• Alertchildrenandadultstohazardsofhightemperatures.
High temperatures may ignite clothing or other ammable
materials.
• Keep clothing, furniture, draperies and other ammable
materialsaway.
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
7100FP-BK-B
7100FP-GD-B
7100FP-NL-B
NOTICE: DO NOT discard this manual!
• DO NOTstoreorusegasolineorotheram-
mablevaporsandliquidsinthevicinityofthis
oranyotherappliance.
DO NOToverre. Overringwillvoidyour
warranty.
• Complywithallminimumclearancestocom-
bustiblesasspecied.Failuretocomplymay
causehousere.
WARNING: If the information in these
instructions is not followed exactly, a  re
or explosion may result causing property
damage, personal injury, or death.
Pourdemanderunexemplaire
enfrançaisdeceManuel
dupropriétaire,visitezwww.
heatnglo.com/translations.
1
Quadra-Fire•7100FP•433-3610InstallationManual•RevG•5/27/14
Safety Alert Key:
• DANGER! Indicatesahazardoussituationwhich,ifnotavoidedwillresultindeathorseriousinjury.
• WARNING!Indicatesahazardoussituationwhich,ifnotavoidedcouldresultindeathorseriousinjury.
• CAUTION! Indicatesahazardoussituationwhich,ifnotavoided,couldresultinminorormoderateinjury.
• NOTICE:Indicatespracticeswhichmaycausedamagetothereplaceortoproperty.
Table of Contents
1 Product Specic & Important Safety Information
A.FireplaceCertication 4
B.GlassSpecications 4
C.Non-CombustibleMaterials 4
D.CombustibleMaterials 4
E.ElectricalCodes 5
2 Getting Started
A.TypicalFireplaceSystem 6
B.DesignandInstallationConsiderations 7
1.SelectingFireplaceLocations 7
2.LocatingFireplace&Chimney 8
C.ToolsandSuppliesNeeded 9
D.InspectFireplaceandComponents 9
E.FireplaceSystemRequirements 9
3 Framing and Clearances
A.FireplaceDimensions 10
B.Clearances 11
1.MinimumClearancestoCombustibles 12
C.ConstructtheChase 13
D.FrametheFireplace 14
E.SecureandLeveltheFireplace 14
F. ProtectiveMetalHearthStrips 15
G.FacingMaterial 15
H.OutsideAirKit 16
I. AuxiliaryConvectionAirSystem 18
J. HeatZoneKit(Optional) 20
4 Electrical Wiring
5 Chimney and Termination Requirements
A.ChimneyRequirements 24
B.Offsets/Returns 25
C.TerminationRequirements 26
6 Chimney Installation
A.TypicalChimneySystem 27
B.AssembleChimneySections 28
C.InstallChimneyAirkit(CAK4A) 28
D.SecureOffset/Return 30
E.InstallCeilingFirestops 30
F. InstallAtticInsulationShield 31
G.RoofPenetration 32
H.ManufacturedHomeInstallation 32
I. InstallChase/ChaseTop 33
J. TerminationCapRequirements 34
K.InstallTerminationCap 34
7 Finishing
A.Template 36
B FinishtheWall 36
1.Stone,BrickFinish 36
2.Tile,Granite,MarbleFinish 36
C.MantelandWallProjections 37
D.FinishingtheHearthExtension 37
E.Non-CombustibleSealantMaterial 39
8 Fireplace Setup
A.FirebrickPlacement 40
B.BafeandBlanketPlacement 41
C.InstallFascia(Fronts) 41
9 Reference Materials
A.ChimneyComponents 42
B.Accessories 46
MESH-HHTFirescreen 46
2Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
Customer:
Lot/Address
Model (circle one): 7100FP-BK-B 7100FP-GD-B
7100FP-NL-B
Fireplace Install YES IF NO, WHY?
Verifiedthatthechaseisinsulatedandsealed.(Pg.13)
Requirednon-combustibleboardisinstalled.(Pg.15)
Verifiedclearancestocombustibles.(Pg.11)
Fireplaceisleveledandsecured.(Pg.14)
Hearthextensionsize/heightdecided.(Pg.14&37)
Outsideairkitinstalled.(Pg.16)
OptionalHeatZonehasbeeninstalledbyaqualifiedservicetechnician.(Pg.18)
Chimne
y
Section 5 (Pg. 24)
Chimneyconfigurationcomplieswithdiagrams.
Chimneyinstalled,lockedandsecuredinplacewithproperclearance.
Roofflashinginstalledandsealed.
Terminationsinstalledandsealed.
Electrical Section 4 (Pg. 23)
Switchwiresproperlyinstalled.
Finishing Section 7 (Pg. 36)
Combustible materials not installed in non-combustible areas
Dealer/Distributor Phone #
Serial #:
WARNING! Risk of Fire or Explosion! Failure to install fireplace acording to these instructions can lead to a fire or
explosion.
Firestopsinstalled.
Chimneyairkitinstalled.
Atticinsulationshieldsinstalled.
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Thisstandardworkchecklististobeusedbytheinstallerinconjuctionwith,notinsteadof,theinstructionscontainedinthis installation
manual.
Date Installed:
Location of Fireplace:
Installer:
Combustible materials not installed in non
-
combustible areas
.
Verifiedallclearancesmeetinstallationmanualrequirements.
Mantelsandwallprojectionscomplywithinstallationmanualrequirements.
Protectivehearthstripsandhearthextensioninstalledpermanualrequirements.
Fireplace Setup Section 8 (Pg. 40)
Allpackagingandprotectivematerialsremoved.
Firebrick,baffleandceramicblanketinstalledcorrectly.
Faciaanddoorsproperlyinstalled.
Allpackagingmaterialsareremovedfrominside/underthefireplace.
Hearth & Home Technologies recommends the following:
•Photographingtheinstallationandcopyingthischecklistforyourfile.
•Thatthischecklistremainvisibleatalltimesonthefireplaceuntiltheinstallationiscomplete.
Commentscommunicatedtopartyresponsible
Part#4017-254•RevB•01/29/13
__________________________by______________________on_________
(Builder/Gen.Contractor)(Installer)(Date)
Comments:Furtherdescriptionoftheissues,whoisresponsible(Installer/Builder/OtherTrades,etc.)andcorrectiveactionneeded:
_________________________________________________________________________________________________
Manualbagandallofitscontentsareremovedfrominside/underthefireplaceand
giventothepartyresponsibleforuseandoperation.
________________________________________________________________________________________________________
________________________________________________________________________________________________________
3
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
1 Product Specic & Important Safety Information
A. Fireplace Certication
Thisreplacesystemhasbeentestedandlistedinac-
cordancewithUL127andULC-S610-M87and(UM)84-
HUDstandardsforinstallationandoperationintheUnited
StatesandCanadaasdescribedinthismanual.
Checkwithyourlocalbuildingcodeagencybeforeyou
beginyourinstallationtoensurecompliancewithlocal
codes,includingtheneedforpermitsandfollow-upin-
spections.Besurelocalbuildingcodesdonotsupersede
ULspecicationsandalwaysobtainabuildingpermitso
thatinsuranceprotectionbenetscannotbeunexpectedly
cancelled.
QuadrareisaregisteredtrademarkofHearth&Home
Technologies.
C. Non-Combustible Materials
• Materialswhichwill not igniteandburn, composed of
anycombinationofthefollowing:
- Steel - Iron
- Brick - Tile
- Concrete - Slate
- Glass - Plasters
• MaterialsreportedaspassingASTM E 136, Standard
Test Method for Behavior of Metals, in a Vertical Tube
Furnace at 750° C
B. Glass Specications
Thisreplaceisequippedwith5mmceramicglass.Re-
placeglassonlywith5mmceramicglass.Pleasecontact
yourdealerforreplacementglass.
NOTICE: This installation must conform with local codes. In the
absence of local codes you must comply with the UL127, (UM)
84-HUD and NFPA211 in the U.S.A. and the ULC 610-M87
and CAN/CSA-B365 Installation Codes in Canada.
WARNING! Risk of Fire! Hearth & Home Technologies
disclaims any responsibility for, and the warranty and agen-
cy listing will be voided by the following actions.
DO NOT:
• installoroperatedamagedreplace
• modifyreplace
install other than as instructed by Hearth & Home
Technologies
operate the fireplace without fully assembling all
components
• overre
• installanygaslogset
• installanycomponentnotapprovedbyHearth&Home
Technologies
• installpartsorcomponentsnotListedorapproved
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied
installer, service agency or your dealer.
Model: 7100FPEPACertied
WoodburningFireplace
Laboratory: OMNITestLaboratories,Inc.
Report No: 061-S-41-2
Type: WoodFireplace
Standard: UL127andULC-S610-M87and
(UM)84-HUD,Manufactured
HomeApproved.
EPA# and Original Date: #5714-1-03
EPA Certied: 3.1gramsperhour
Efciency: upto77%
BTU Output
with EPA test fuel: 58,000/hr.
with Cord Wood: 90,000/hr.
Heating Capacity: upto3,500sqft
Chimney Size: 8inches
HHT SL300Series
DuraVent DuraPlus
Max Wood Length: 24inches
Fuel: CordWood
Shipping Weight: 670lbs
Firebox Size 3.4cubicfeet
WARNING! Risk of Fire!
Hearth & Home Technologies is not responsible for
discoloration, cracking or other material failures of
nishingmaterialsduetoheatexposureorsmoke.
• Choosenishingmaterialscarefully.
4Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
E. Electrical Codes
NOTICE: This replace must be electrically wired and
grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code ANSI/
NFPA 70-latest edition or the Canadian Electric Code
CSA C22.1.
• A110-120VACcircuitforthisproductmustbeprotected
with ground-fault circuit-interrupter protection, in
compliancewiththeapplicableelectricalcodes,when
itisinstalledindamplocations.
WARNING! Improper installation, adjustment, alteration,
service or maintenance can cause injury or property dam-
age.
D. Combustible Materials
• Materialsmadeoforsurfacedwithanyofthefollowing
materials:
- Wood - Compressedpaper
- Plantbers - Plastic
- Plywood/OSB - Sheetrock(drywall)
• Anymaterialthatcanigniteandburn;ameproofedor
not,plasteredorun-plastered
5
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
2 Getting Started
Termination Cap
Chimney penetrates roof
preferably without affecting
roof rafters
Offset/Return
(with hanger straps)
Attic insulation shield
must be used to keep
insulation away
from chimney if
attic is insulated
Storm Collar
Framing headed
off in ceiling joists
Mantel
Chimney system
Combustible
framing/header
on top of V-shaped
standoffs (spacers)
Non-combustible material
Hearth extension
Non-combustible
roof flashing maintains
minimum clearance
around chimney
Additional lateral
support for chimney
above roof (or enclosed
in chase) if needed
Enclosed space above
and around fireplace
Ceiling firestop
on floor of attic
Support straps
on rafter supports
chimney (not shown)
Outside
combustion air
Outside
combustion air
Chimney Air Kit (CAK-4A) (not
shown) must be used with SL300
chimney
Protective metal
hearth strip(s)
A. Typical Fireplace System
Figure 2.1 Typical Fireplace System
6Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
D
C
A
E
F
A
H
G
B
A
B
B
A
I
In an exterior chase
or projecting into a
garage
Across a corner
Along a wall
As a
room
divider
24 in.
(610mm)
24 in.
(610mm)
24 in.
(610mm)
48 in.
(1219mm)
24 in.
(610mm)
I
A
Figure 2.2 Fireplace Locations
NOTICE:
• Illustrationsandphotosreecttypicalinstallationsand
are FOR DESIGN PURPOSES ONLY.
• Illustrations/diagramsarenotdrawntoscale.
• Actualinstallation/appearancemayvaryduetoindividual
design preference.
• Hearth&HomeTechnologiesreservestherighttoalter
its products.
NOTICE: In addition to these framing dimensions, also
reference the following section:
• Clearances (Section 3).
NOTICE:
A minimum 1/2 in. air clearance at the back and
a minimum 1 in. air clearance to the sides of the
replaceassemblymustbemaintained.
Chimney sections at any level require a 2 in. mini-
mum air space clearance between the framing
and chimney sections.
B. Design and Installation Considerations
NOTICE: Check building codes prior to installation.
• InstallationMUSTcomplywithlocal,regional,stateand
nationalcodesandregulations.
• Consultinsurancecarrier,localbuildinginspector,re
ofcialsorauthoritieshavingjurisdictionoverrestrictions,
installationinspectionandpermits.
1. Selecting Fireplace Locations
Thisreplacemaybeusedasaroomdivider,installed
alongawall,acrossacornerorusedinanexteriorchase.
SeeFigure2.2.
Locatingthereplaceinabasement,nearfrequently
openeddoors,centralheatoutletsorreturns,orother
locationsofconsiderableairmovementcanaffectthe
performance.
Outsideairmustbeusedforcombustion.The7100FP
comesequippedwithanoutsideairinlettofeedcombus-
tionairfromoutsidethehome,alongwithanoutsideair
terminationcap;therigidmetalductisrequiredbutnot
supplied.Considerationshouldbegiventothesefactors
beforedecidingonalocation.
Model#7100FP A BC D E F GHI
(Dimensionsfor
nishedwalls)
in. 42-1/4 16 89-1/2 63-5/16 22-7/16 44-3/4 14-1/16 55-15/16 50-7/8
mm 1063 406 2273 1608 570 1137 357 1421 1292
7
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
2. Locating Fireplace & Chimney
Locationofthereplaceandchimneywillaffectperfor-
mance.
• Installwithinthewarmairspaceenclosedbythebuilding
envelope.Thishelpstoproducemoredraft,especially
duringlightinganddie-downofthere.
• Penetratethehighestpartof theroof.Thisminimizes
theeffectsofwindloading.
Locate termination cap away from trees, adjacent
structures,unevenrooflinesandotherobstructions.
• Minimizetheuseofchimneyoffsets.
• Considerthereplacelocationrelativetooorandceiling
andatticjoists.
• Takeintoconsiderationtheterminationrequirementsin
Sections5and6.
Marginal Location:
• Below peak
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Multi-level Roofs
Windward
Leeward
Recommended Location:
• Above peak
Recommended:
• Insulated exterior chase
in cooler climates
Recommended Location:
• Above peak
• Inside heated space
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Marginal Location:
Wind loading possible
Figure 2.3 Recommended Chimney Locations
• Installtheoutsideairkitwiththeintakefacingprevailing
windsduringtheheatingseason.
Ensure adequate outdoor air for all combustion
appliancesandexhaustequipment.
• Ensurefurnaceandairconditioningreturnventsarenot
locatedintheimmediatevicinityofthereplace.
• Avoidinstallingthereplaceneardoors,walkwaysor
smallisolatedspaces.
• Recessedlightingshouldbea“sealedcan”design.
• Attichatchesweatherstrippedorsealed.
• Atticmountedductworkandairhandlerjointsandseams
tapedorsealed.
8Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
C. Tools and Supplies Needed
Beforebeginningtheinstallationbesurethefollowing
toolsandbuildingsuppliesareavailable:
Reciprocatingsaw Framingmaterial
Pliers Non-combustiblesealant
Hammer Gloves
Phillipsscrewdriver Framingsquare
Flatbladescrewdriver Electricdrillandbits
Plumbline Safetyglasses
Level Tapemeasure
1/2-3/4in.length,#6or#8self-drillingscrews
Misc.screwsandnails
D. Inspect Fireplace and Components
WARNING! Risk of Fire and/or Explosion! Damaged
parts could impair safe operation. DO NOT install dam-
aged,incompleteorsubstitutecomponents.Keepre-
place dry.
• Removereplaceandcomponentsfrompackagingand
inspectfordamage.
• Vent system components and doors are shipped in
separatepackages.
• Reporttoyourdealeranypartsdamagedinshipment.
Read all the instructions before starting the
installation. Follow these instructions carefully
during the installation to ensure maximum safety
and benet.
E. Fireplace System Requirements
TheQuadra-Firereplacesystemrequirementsconsistof
thefollowing:
• Fireplace
- Firebrick(includedwithreplace)
- Door(includedwithreplace)
- Non-combustible facing material (included with
replace)
- HearthExtension
• OutsideAir System (hood and collars included with
replace)
• Fascia
• ChimneySystem
- Chimneyairkit(includedwithreplace,requiredwith
SL300serieschimney)
- AtticInsulationShield(includedwithreplace)
- Chimneyterminationcap
• Non-combustiblenishmaterial
Optionalcomponentsinclude:
• Firescreen
• LintelBar
• HeatZoneKit
9
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
3 Framing and Clearances
A. Fireplace Dimensions
C
L
Blower Electric Access
(right side of fireplace)
3-1/2 in.
(89 mm)
32-1/2 in.
(826 mm)
38 in.
(965 mm)
40 in.
(1016 mm)
42-5/16 in.
(1075 mm)
45-13/16 in.
(1148 mm)
23-7/16 in.
(595 mm)
13-3/16 in.
(335 mm)
10-13/16 in.
(259 mm)
4-5/16 in.
(109 mm)
6 in.
(152 mm)
1 in.
(25 mm)
13-3/4 in.
(349 mm)
9-7/16 in.
(240 mm)
43 in.
(1092 mm)
Figure 3.1 Fireplace Dimensions
10 Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
B. Clearances
WARNING! Risk of Fire!
YoumustcomplywithallminimumairspaceclearancestocombustiblesasspeciedinFigure3.2.DO NOT pack required
airspaceswithinsulationorothermaterials.Framingornishingmaterialusedonthefrontof,orinfrontof,thereplace
closer than the minimums listed must be constucted entirely of non-combustible materials (i.e., steel studs, concrete board,
etc.).Failuretocomplymaycausere.
Figure 3.2 Clearances to Combustible Materials
(ceiling)
(roof)
(ceiling)
2 in. (51 mm) min.
Attic
Insulation
Shield
Ceiling Firestop
(attic)
Storm Collar
Roof Flashing
2 in. min.
(51 mm)
2 in. (51 mm) min.
2 in. (51 mm) min.
Ceiling Firestop Offset/Return with
hanger straps
2 in.
(51 mm)
min.
2 in. (51 mm) min.
Must have 2 in. (51 mm)
minimum clearance
to header
Electrical wires must be 3-1/2: (89mm)
from top
0 in. to level
of standoffs
1 in. (25mm) to side of appliance
1/2 in. (13 mm) to back
of appliance
0 in.
to floor
36 in. (914 mm)
standoffs to ceiling
Chimney Air Kit required with SL chimney
11
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
1. Minimum Clearances to Combustibles
Position combustible/
non-combustible mantel
60 in. (1524 mm) from
base of fireplace
12 in.
(305 mm)
46-1/4 in.
(1175 mm)
24 in.
(610 mm)
2 in.
(51 mm)
48-1/4 in.
(1226 mm)
42-1/4 in.
(1073 mm)
The finished cavity depth must
be no less than 24 in. (610 mm)
from the finished backwall to
the outside of front wall framing.
Figure 3.3 Framing the Fireplace
WITHIN ENCLOSURE AREA
Fireplacetobackwall 1in.(25mm)
Fireplacetosidewall 1in.(25mm)
Ductbootstoframing 0in.(0mm)
Topstandoffstoheader 0in.(0mm)
Dooropeningtosidewall 22-7/8in.(581mm)
EXPOSED SURFACES
Faceplatetosidewall 16in.(406mm)
Heatzoneairgrillstoceiling 12in.(305mm)
MANTEL
Non-combustiblemantel
(Non-combustibleframing
materialsabovethereplace
toceiling) 46in.(1168mm)
Combustiblemantel
(Combustibleframing
materialsabovethereplace
toceiling) 60in.(1524mm)
Maximummanteldepth 12in.(305mm)
12 Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
C. Construct the Chase
Achaseisaverticalboxlikestructurebuilttoenclosethe
replaceand/oritsventsystem.Verticalchimneysthat
runontheoutsideofabuildingmustbeinstalledinsidea
chase.
Incoldclimates,Hearth&HomeTechnologiesrecom-
mendsthatthechasebewellinsulatedusingbatttype
insulationbetweenthejoists.
Constructionofthechasemayvarywiththetypeofbuild-
ing.Theseinstructionsarenotsubstitutesfortherequire-
mentsoflocalbuildingcodes.LocalbuildingcodesMUST
bechecked.
Chasesshouldbeconstructedinthemannerofalloutside
wallsofthehometopreventcoldairdraftingproblems.
Thechaseshouldnotbreaktheoutsidebuildingenvelope
inanymanner.Allouterwallsneedtobeinsulated.
Buildingcodesrequirefalseceilingandceilingrestops/
atticshieldsateachoorofthechaseorevery10ft(3048
mm)ofclearspacetocontrolspreadofre.
Walls,ceiling,baseplateandcantileveroorattherst
levelofthechaseshouldbeinsulated(seeFigure3.4.)
Vaporandairinltrationbarriersshouldbeinstalledinthe
chaseasperregionalcodesfortherestofthehome.Ad-
ditionally,Hearth&HomeTechnologiesrecommendsthat
theinsidesurfacesbedrywalledandtaped(ortheuseof
anequivalentmethod)formaximumairtightness.
Holesandotheropeningsshouldbecaulkedwithhigh
temperaturecaulkorstuffedwithunfacedberglass
insulation.
Ceiling
Firestop
Metal Chase Top
Round Termination Cap
False Ceiling
Insulation in the
outside walls
of the chase
Attic
Insulation
Shield
Chimney
Ceiling
Firestop
Tabs
False Ceiling
False Ceiling
Insulation
Insulation
Storm Collar
Figure 3.4 Chase Assembly
1 2 3
All outside walls should be insulated.
Figure 3.5 Chase Constructions
1. Fireplaceandchimneyenclosedinanexteriorchase.
2. Chimneyoffsetthroughexteriorwallandenclosedinchase.
3. Chaseconstructedonroof.
• Thechaseisconstructedusingframingmaterialsmuch
thesameasthewallsinyourhome.Avarietyofsiding
materials may be used including brick, stone, veneer
brick,orstandardsidingmaterials.
• In constructing the chase, several factors must be
considered:
- Maintain a 2 in. (51 mm) air space around the
chimney.
- The chase top must be constructed of non-
combustiblematerial.
- Incoldclimates,arestopspacerandatticinsulation
shieldshouldbeinstalledinaninsulatedfalseceiling
at the 8 ft. (2438 mm) level above the replace
assembly.Thisreducesheatlossthroughthechase.
- Incoldclimates,the walls ofthechaseshould be
insulatedtothelevelofthefalseceilingasshownin
Figure3.4.Thiswillhelpreduceheatlossfromthe
homearoundthereplace.
ThreeexamplesofchaseapplicationsareshowninFig-
ure3.5.
WARNING! You must install false ceilings and ceil-
ing restops at each oor of the chase or every 10 ft
(3.05 m) to control spread of re.
WARNING! Risk of Fire! DO NOT sealareabetweenre
stop opening and chimney pipe except where they enter
the attic or leave the warm air envelope of the home (use
600° F sealant).
WARNING! Risk of Fire! You must maintain a minimum
2 in. (51 mm) air space clearance to insulation and other
materials surrounding the chimney system.
• Insulationandothermaterialsmustbermlysecuredto
prevent accidental contact with chimney system.
• Thechasemustbeproperlyblockedtopreventblown
insulation or other combustibles from entering and
makingcontactwithreplaceorchimney.
• Failuretopreventcontactbetween insulationorother
materials and chimney system may cause overheating
andre.
13
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
D. Frame the Fireplace
NOTICE: Hearth extension design must be determined
beforeinstallationofreplace.
Ifthereplaceisplacedontheoorthemaximumheight
ofanishedraisedhearthis5-3/4”,ifyouwantahigher
raisedhearththereplacemustbeplacedonaplatform.
NOTICE: Wiring for fans must be done before framed
enclosure is completed. If using a Heat Zone Kit, it
also must be installed before enclosure is complete.
The7100FPFireplacewilltaframedopeningheightof
46-1/4in.(1174mm)talland42-1/4in.(1073mm)wide.
WARNING! Risk of Fire! You must comply with all
minimum air space clearances to combustibles. DO NOT
pack required air spaces with insulation or other materi-
als.
WARNING! Risk of Fire! Comply with all minimum clear-
ancesspecied.
• A minimum 1/2 in. (13 mm) air clearance must be
maintained at the back and 1 in. (25 mm) to the sides
ofthereplaceassembly.
• Chimneysectionsatanylevelrequirea2in.(51mm)
minimum air space clearance between the framing and
chimney section.
Figure3.3showsatypicalframing(using2x4lumber)
ofthereplace,assumingcombustiblematerialsare
used.Allrequiredclearancestocombustiblesaroundthe
replacemustbeadheredto.SeeFigure3.2.Anyframing
acrossthetopofthereplacemustbeabovethelevelof
thetopstandoffs.(Norecessabovestandoffs.)
The
nished cavity depth must be no less than 24 in.
(610mm)fromthenishedbackwalltotheoutsideoffront
wallframing.Framingmustextendstraightupalltheway
totheceiling.
CAUTION! Risk of Cuts/Abrasions. Wear protective gloves
and safety glasses during installation. Sheet metal edges
are sharp.
WARNING! Risk of Fire! Prevent contact with sagging,
loose insulation.
• DO NOT install against vapor barriers or exposed
insulation.
• Secureinsulationandvaporbarriers.
• Provideminimumairspaceclearancesatthesidesand
backofthereplaceassemblyasoutlinedinSection3.
E. Secure and Level the Fireplace
Thisreplacemaybeplacedoneitheracombustibleor
noncombustiblecontinuousatsurface.Followthein-
structionsforframinginSection3.Slidethereplaceinto
position.Besuretoprovidetheminimum1in.airclear-
anceatthesidesand1/2in.atthebackofthereplace.
Thereplaceshouldbepositionedsothefaceofthenon-
combustiblematerialonthereplacewillbeushwiththe
faceofthedrywallonthewalls.SeeFigure3.6.
Levelthereplaceandshimasnecessary.Securethe
replace(usingthepalletmountingbracketslocatedon
eithersideofthereplace)tothesuboor.
These surfaces
must be even!
Drywall Non-combustible
facing material
Figure 3.6 Drywall - Non-combustible Facing Material
14 Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
1in. (25 mm) Overlap
Metal strips 2 in. (51 mm) under edge of Fireplace
and Hearth Extension and extended 2 in. (51 mm)
beyond both sides of fireplace opening.
Nail or screw metal strips in place.
Pallet Mounting/Floor
Brackets
Raised Platform
Floor
2 in.
(51 mm)
1 in. (25 mm) min.
overlap
2 in.
(51 mm)
Top piece must overlap
bottom piece
Figure 3.8 Protect the Front of an Elevated Platform
F. Protective Metal Hearth Strips
Figure 3.7 Position the Protective Metal Hearth Strips
• Locatethetwoprotectivemetalhearthstripsmeasuring
approximately26in.x4in.(660mmx102mm)included
withthisreplace.
• Slideeachmetalstrip2in.(51mm)underfrontedgeof
replace.
• Overlapstripsinthemiddleofreplaceopeningby1in.
(25mm)minimum.
• Metal strips must extend beyond the frontand sides
of the replace opening by at least 2 in. (51 mm),
Figure3.7).
• Protectthefrontofaplatformelevatedabovethehearth
extensionwithmetalstrips(notincludedwithreplace)
per Figure 3.8. See Section 6 for hearth extension
instructions.
WARNING! Risk of Fire! Protective metal hearth
strips MUST be installed on combustible surfaces. DO
NOT cover metal strips with combustible materials.
Sparksorembersmayigniteooring.
WARNING! Risk of re! High temperatures, sparks,
embers or other burning material falling from the
replacemayigniteooringorconcealedcombustible
surfaces.
• ProtectivemetalhearthstripsMUSTbeinstalled.
• Hearth extensions MUST be installed exactly as
specied.
WARNING! Risk of Fire!
Follow these instructions exactly.
Facing materials must be installed properly to prevent
re.
No materials may be substituted without authorization by
Hearth & Home Technologies.
G. Facing Material
TOOLS NEEDED: Powered drill with #2 Phillips head bit;
caulkinggun.
Onlynon-combustiblematerials(suppliedwithreplace)
maybeusedtocoverthemetalreplacefront.
NOTE: All boards are pre-drilled for your convenience.
Boards MUST be attached in the following order:
bottom, top, and then the two sides, red-painted side
out. The top and bottom board should each have a hang
tag attached. Leave them attached for referral for the
nishingoperation.
• Attach the bottom board to the bottom of the outer
replacecanwithenclosedscrews,ensuringtheboard
iscentered.DO NOT remove hang tags.
• Centerandattachthetopboardtotheoutercanand
framingmembers. DO NOT remove hang tags.
• Using the Super Calstick, run a light bead (1/8 in.
minimum) between the metal surface of the replace
andthebuttedgesofthetopboard.SeeFigure3.9.
• Ensuringthetopofthesidepiecesandthetopboard
align,attachthesidepiecestotheoutercanandframing
members.
NOTICE: 1/8 in. of the facing material may be visible
afternishing materialsareapplied.This1/8in.must
be painted or the red will show.
Figure 3.9 Apply Non-combustible Materials
Side
Board
Bottom
Board
Side
Board
Top
Board
DO NOT
remove hang
tags
Apply bead of
Super Calstick to
edge here
15
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
H. Outside Air Kit
Anoutsideairkitmustbeusedforcombustion.Hearth&
HomeTechnologiesrecommendsyouutilizetheshortest
ductruntooptimizetheperformanceoftheoutsideair
kit.Theoutsideairinlethoodshouldbepositionedina
mannerthatwillnotallowsnow,leaves,etc.toblockthe
inlet.Insomeinstallationstheairductmayneedtoberun
vertically.Insuchaninstallation,a3ft(914mm)height
differencemustbemaintainedfromthetopoftheupper-
mostchimneysectiontotheoutsideairinlethood.
RefertoFigures3.10and3.11whenplacingtheoutside
airinlethood.
Theoutsideairkitisinstalledontherighthandsideofthe
replace.SeeFigure3.12forhandlelocation/operation.
• Cuta6in.(152mm)holeinoutsidewalltoaccommodate
airpiping.
• Use6in.(152mm)metalexorrigidpiping(notsupplied)
todirectlyconnectoutsideairtoreplaceintake.Insulate
thepipetopreventfrostcondensation.
• Usethesuppliedoutsideairinlethood.
• Seal between the wall and the pipe with silicone to
preventmoisturepenetrationandairleaks.
• Sealbetweentheoutsideairinlethoodandthehouse
withsiliconetopreventairinltration.
CAUTION! Risk of Cuts/Abrasions. Wear protective
gloves and safety glasses during installation. Sheet metal
edges are sharp.
CAUTION! Risk of Fire or Asphyxiation! DO NOT draw
outsidecombustionairfromwall,oororceilingcavity,or
enclosed spaces such as an attic or garage.
• DO NOT place outside air inlet hood close to exhaust
vents or chimneys. Fumes or odor could be drawn into
theroomthroughthereplace.
• Locateoutsideairinlethoodtopreventblockagefrom
leaves, snow/ice, or other debris. Blockages could cause
combustion air starvation.
16 Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
3 ft. (91cm) min. from
top of uppermost
chimney section to
outside air inlet.
Locate outside air inlet
to prevent blockage
from leaves, snow/ice,
or other debris.
Attic insulation shield
must be used to keep
insulation away from
chimney.
Ceiling firestop
on floor of attic
Outlet blocked by
snow, leaves, etc.
NO
Garage or
combustible
liquids storage
NO
Attic space
NO
Outlet placed
higher than 3 ft
below the
termination cap
NO
UL181 Listed Class 0
or Class 1 metal flex or
rigid duct
Figure 3.11 Outside Air Installation
Figure 3.10 Outside Air Inlet Locations
17
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
I. Auxiliary Convection Air System
Note: Boththeoutsideairandauxiliaryairkitsareinstalled
ontherighthandsideofthereplace.
Theauxiliaryconvectionairsystemallowstheoptionat
thetimeofinstallationofthereplace,toruna6inch
(152mm)diameterducttotheoutsideofthehome,and
bringoutsideairoverthefanswhereitisheatedandthen
distributedintotheroom.Thisproducesapostivepres-
sureinsidethehome.
Figure 3.13 Auxiliary Convection Air Duct
Alternatively,a6inch(152mm)ductcanberuntoan-
otherlocationinthehomeandusedasacoldairreturn
withinthehomeanddistributedintotheroomwherethe
replaceislocated.SeeFigure3.13.
Ifnoductingisinstalled,thefanswillpullairfromthe
roomandre-circulateheatedairbackintotheroom.
Figure 3.12 Outside Air
Termination
Caps supplied
with fireplace
UL 181 Listed Class 0 or Class
1 metal flex or rigid duct
Outside Air
intake
Auxiliary
Convection
Air
Open/Close
Knob for
outside air
OUTSIDE AIR
OPEN
CLOSED
18 Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
Auxiliary Convection Air Lever
Theauxiliaryconvectionairleverislockedfromthefac-
tory.Ifyouaregoingtousethisfunctionforairmove-
mentyoumustremovethelock.
Afterremovingthefascia,removetheonescrewand
platetoallowthehandletobemovedinthefullmotion
righttoleft.SeeFigure3.14.
Discardtheplateandscrew.Replacefascia.
The auxiliary convection lever is located underneath
thefrontlowerpanelasshowninFigure3.14.
Figure 3.14 Auxiliary Convection Air Lever
8-32 Screw
Convection Lock Bracket
19
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
DUCT RUN REQUIREMENTS
MAXIMUMDuctRun=40-ft.(12m)
MINIMUMDuctRun=36in.(914mm)
DUCTING MATERIAL
6in.(152mm)B-VentOnly
DONOTductintoexistingfurnaceplenum
MINIMUM CLEARANCE TO COMBUSTIBLES
1in.(25mm)fromtheB-Vent
1
/2in.(13mm)fromtop&bottomofoutletbox
0in.(0mm)fromthesidesofoutletbox
12in.(305mm)fromwallregistertoceiling
RefertoFigure3.15.
CAUTION! ALLwiringshouldbedonebyaqualiedelec-
trician and shall be in compliance with local codes and
with the National Electric Code NFPA/NEC No. 70-current.
CSC22.1 Canadian Electric Code.
Possible Air Duct Runs / Locations
Figure 3.15 Minimum Clearances to Combustibles
Ceiling Register
Wall Register
Floor Register
Two Duct Kits
Ceiling Register
12 in. (305mm) minimum clearance
from register to ceiling
J. Heat Zone Kit (Optional)
TheHeat-Zoneaccessorykitconveyswarmairfromthe
replacethroughairduct(s)toremotelocationsinthe
sameroomorotherroomsofthebuilding.Youmayinstall
1or2Heat-Zonekitsonthereplace.Installationofthis
kitMUSTbeperformedbyaqualiedservicetechnician.
Ifanypartsaremissingordamaged,contactyourlocal
dealerbeforestartinginstallation.DONOTinstalladam-
agedkit.
Thiskitistestedandsafewheninstalledinaccordance
withthisinstallationmanual.Itisyourresponsibilityto
readallinstructionsbeforestartinginstallationandtofol-
lowtheseinstructionscarefullyduringinstallations.
TheHeat-Zone®Woodkitiscarefullyengineeredand
mustbeinstalledonlyasspecied.Ifyoumodifyitorany
ofitscomponentsyouwillvoidthewarrantyandyoumay
possiblycausearehazard.Installationmustbedone
accordingtoapplicablelocal,state,provincialand/or
nationalcodes.
Planthelocationofthereplaceandwarmairductrun(s).
20 Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48