Quadrafire Pioneer II Wood Fireplace Installation guide

Category
Fireplaces
Type
Installation guide
R
EPA CERTIFIED WOODBURNING
FIREPLACE
O-T L
Tested and
Listed by
Portland
Oregon USA
OMNI-Test Laboratories, Inc.
C
US
Model(s):
Installation Manual
Installation and Fireplace Setup
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
NEVER allow children to touch glass
Keep children away
CAREFULLY SUPERVISE children in same room as
replace.
Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable
materials.
• Keep clothing, furniture, draperies and other ammable
materials away.
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
PIONEER-II-BK
NOTICE: DO NOT discard this manual!
DO NOTstoreorusegasolineorotheram-
mablevaporsandliquidsinthevicinityofthis
or any other appliance.
DO NOToverre.Overringwillvoidyour
warranty.
Comply with all minimum clearances to com-
bustiblesasspecied.Failuretocomplymay
causehousere.
WARNING: If the information in these
instructions is not followed exactly, a re
or explosion may result causing property
damage, personal injury, or death.
Fire Risk.
WARNING
For use with solid wood fuel only.
Other fuels may overre and generate poisonous
gases (i.e. carbon monoxide).
Installationandserviceofthisapplianceshouldbeperformedby
qualifiedpersonnel.Hearth&HomeTechnologiesrecomendsHHT
FactoryTrainedorNFIcertifiedprofessionals.
1
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
Safety Alert Key:
DANGER! Indicatesahazardoussituationwhich,ifnotavoidedwill result in death or serious injury.
WARNING!Indicatesahazardoussituationwhich,ifnotavoidedcould result in death or serious injury.
CAUTION! Indicatesahazardoussituationwhich,ifnotavoided,couldresultinminorormoderateinjury.
NOTICE:Indicatespracticeswhichmaycausedamagetothereplaceortoproperty.
Table of Contents
1 Product Specic & Important Safety Information
A.ApplianceCertication/MobileHomeApproved 4
B.GlassSpecications 5
C.Non-CombustibleMaterials 5
D.CombustibleMaterials 5
E.ElectricalCodes 5
2 Getting Started
A.TypicalFireplaceSystem 6
B. Design and Installation Considerations 7
1. Selecting Fireplace Locations 7
2.LocatingFireplace&Chimney 8
C.ToolsandSuppliesNeeded 9
D.InspectFireplaceandComponents 9
E.FireplaceSystemRequirements 9
3 Framing and Clearances
A. Fireplace Dimensions 10
B. Clearances 11
1.MinimumClearances 12
C. Construct the Chase 13
D.FrametheFireplace 14
E.SecureandLeveltheFireplace 14
F. ProtectiveMetalHearthStrips 15
G.FacingMaterial 15
H.OutsideAirKit 16
I. HeatZoneKit(Optional) 18
4 Electrical Wiring 21
5 Chimney and Termination Requirements
A.ChimneyRequirements 22
B.Offsets/Returns 23
C.TerminationRequirements 24
6 Chimney Installation
A.TypicalChimneySystem 25
B.AssembleChimneySections 26
C.InstallChimneyAirkit(CAK4A) 26
D.SecureOffset/Return 28
E.InstallCeilingFirestops 28
F. InstallAtticInsulationShield 29
G. Roof Penetration 30
H.ManufacturedHomeInstallation 30
I. InstallChase/ChaseTop 31
J. TerminationCapRequirements 32
K.InstallTerminationCap 32
7 Finishing
A.Template 34
B FinishtheWall 34
1.Stone,BrickFinish 34
2.Tile,Granite,MarbleFinish 34
C.MantelandWallProjections 35
D.FinishingtheHearthExtension 35
E.SealingofNon-CombustibleBoard 37
8 Fireplace Setup
A.FirebrickPlacement 38
B.BafeandBlanketPlacement 39
9 Reference Materials
A.ChimneyComponents 40
2
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
Customer:
Lot/Address
Model (circle one):
Pioneer-II-BK
Fireplace Install Section 3 (Pg.10)
YES IF NO, WHY?
Verifiedthatthechaseisinsulatedandsealed.(Pg.13)
Requirednon-combustibleboardisinstalled.(Pg.15)
Verifiedclearancestocombustibles.(Pg.11)
Fireplaceisleveledandsecured.(Pg.14)
Hearthextensionsize/heightdecided.(Pg.14&35)
Outsideairkitinstalled.(Pg.16)
OptionalHeatZonehasbeeninstalledbyaqualifiedservicetechnician.(Pg.18)
Chimney Section 5 (Pg. 22)
Chimney configuration complies with diagrams.
Chimney installed, locked and secured in place with proper clearance.
Chimney air kit installed.
Firestops installed.
Attic insulation shield installed.
Roofflashing/stormcollarinstalledandsealed.
Terminationsinstalledandsealed.
Electrical Section 4 (Pg. 21)
Switch wires properly installed.
Finishing Section 7 (Pg. 34)
Combustiblematerialsnotinstalledinnon-combustibleareas.
Verifiedallclearancesmeetinstallationmanualrequirements.
Mantelsandwallprojectionscomplywithinstallationmanualrequirements.
Protectivehearthstripsandhearthextensioninstalledpermanualrequirements.
Fireplace Setup Section 8 (Pg. 38)
Allpackagingandprotectivematerialsremoved.
Firebrick,baffleandceramicblanketinstalledcorrectly.
Facia and door properly installed.
Allpackagingmaterialsareremovedfrominside/underthefireplace.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your file.
• That this checklist remain visible at all times on the fireplace until the installation is complete.
Commentscommunicatedtopartyresponsible
Part 4181-982 • Rev A • 7/1/16
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Thisstandardworkchecklististobeusedbytheinstallerinconjuctionwith,notinsteadof,theinstructionscontainedinthisinstallation
manual.
Date Installed:
Location of Fireplace:
Installer:
Dealer/Distributor Phone #
Serial #:
__________________________by______________________on_________
(Builder/Gen.Contractor)(Installer)(Date)
Comments:Furtherdescriptionoftheissues,whoisresponsible(Installer/Builder/OtherTrades,etc.)andcorrectiveactionneeded:
_________________________________________________________________________________________________
WARNING! Risk of Fire or Explosion! Failure to install fireplace acording to these instructions can lead to a fire or
explosion.
Manualbagandallofitscontentsareremovedfrominside/underthefireplaceand
giventothepartyresponsibleforuseandoperation.
________________________________________________________________________________________________________
________________________________________________________________________________________________________
3
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
1
Product Specic & Important Safety Information
1
Product Specic & Important Safety Information
A. Appliance Certication
Thisreplacesystemhasbeentestedandlistedinaccor-
dance with UL127-2011 and ULC-S610-M87 (A1998)and
(UM)84-HUDstandardsforinstallationandoperationinthe
UnitedStatesandCanadaasdescribedinthismanual.
Checkwithyourlocalbuildingcodeagencybeforeyoube-
gin your installation to ensure compliance with local codes,
including the need for permits and follow-up inspections.
BesurelocalbuildingcodesdonotsupersedeULspeci-
cationsandalwaysobtainabuildingpermitsothatinsur-
anceprotectionbenetscannotbeunexpectedlycancelled.
Quadra-Fireis aregisteredtrademarkofHearth &Home
Technologies.
Model: Pioneer II-BK
Laboratory: OMNITestLaboratories,Inc.
Report No: 061-S-50-2
Type: Wood Fireplace
Standard: UL127-2011 and ULC-
S610-M87(A1998)and(UM)
84-HUD,ManufacturedHome
Approved.
BTU & Efciency Specications
TheQuadra-FirePioneerIImeetstheU.S.Environmental
ProtectionAgency’scrib wood emission limits for wood
heaterssoldafterMay15,2015.
EPACertication#: 569
EPACertiedEmissions: 3.3 grams per hour
*LHVTestedEfciency: 77.2 %
**HHVTestedEfciency: 71.5%
***EPABTUOutput: 11,300to51,200/hr.
****PeakBTU/HourOutput: 74,900
VentSize: 8inches
ChimneySize: 8inches
HHT: SL300 Series
DuraVent: DuraPlus
FireboxSize: 2.7cubicfeet
RecommendedLogLength: 22 inches
Fuel Seasoned Cord Wood
*Weighted average LHV (Low Heating Value) efciency using
DouglasFirdimensionallumberanddatacollectedduringEPA
emissiontest.LHVassumesthemoistureisalreadyinavapor
statesothereisnolossinenergytovaporize.
**WeightedaverageHHV(HighHeatingValue)efciencyusing
DouglasFirdimensionallumberanddatacollectedduringEPA
emissiontest.HHVincludestheenergyrequiredtovaporizethe
water in the fuel.
***ArangeofBTUoutputsbasedonEPADefaultEfciencyand
theburnratesfromthelowandhighEPAtests,usingDouglas
Firdimensionallumber.
****ApeakBTUoutoftheappliancecalculatedusingthemaxi-
mumrst hourburnrate fromtheHighEPATestand the BTU
contentofcordwood(8600)timestheefciency.
Mobile Home Approved
Thisapplianceisapprovedformobilehomeinstal-
lations when not installed in a sleeping room and
whenanoutsidecombustionairinletisprovided.
The structural integrity of the mobile home oor,
ceiling,andwallsmustbemaintained.
The appliance must be properly grounded to the
frame of the mobile home with #8 copper ground
wire.
OutsideAirKitmustbeinstalledinamobilehome
installation.
WARNING: This product and the fuels
used to operate this product (wood and
wood pellets), and the products of combus-
tion of such fuels, can expose you to chemi-
cals including carbon black, which is known
to the State of California to cause cancer
and carbon monoxide, which is known to
the State of California to cause birth defects
or other reproductive harm. For more infor-
mation go to: www.P65Warnings.ca.gov.
4
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
E. Electrical Codes
NOTICE: This replace must be electrically wired and
grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code ANSI/
NFPA 70-latest edition or the Canadian Electric Code
CSA C22.1.
• A110-120VACcircuitforthisproductmustbeprotected
with ground-fault circuit-interrupter protection, in
compliancewiththeapplicableelectricalcodes,when
it is installed in damp locations.
WARNING! Improper installation, adjustment, alteration,
service or maintenance can cause injury or property dam-
age.
D. Combustible Materials
• Materialsmadeoforsurfacedwithanyofthefollowing
materials:
- Wood - Compressed paper
- Plantbers - Plastic
- Plywood/OSB - Sheetrock(drywall)
• Anymaterialthatcanigniteandburn;ameproofedor
not, plastered or un-plastered
C. Non-Combustible Materials
• Materialswhich will not ignite and burn, composed of
anycombinationofthefollowing:
- Steel - Iron
- Brick - Tile
- Concrete - Slate
- Glass - Plasters
• MaterialsreportedaspassingASTM E 136, Standard
Test Method for Behavior of Metals, in a Vertical Tube
Furnace at 750° C
B. Glass Specications
Thisreplaceisequippedwith5mmceramicglass.Re-
placeglassonlywith5mmceramicglass.Pleasecontact
your dealer for replacement glass.
NOTICE: This installation must conform with local codes. In
the absence of local codes you must comply with the UL127-
2011, (UM) 84-HUD and NFPA211 in the U.S.A. and the ULC
610-M87 (A1998) and CAN/CSA-B365 Installation Codes in
Canada.
WARNING! Risk of Fire! Hearth & Home Technologies
disclaims any responsibility for, and the warranty and agen-
cy listing will be voided by the following actions.
DO NOT:
install or operate damaged replace
modify replace
install other than as instructed by Hearth & Home
Technologies
operate the fireplace without fully assembling all
components
overre
install any gas log set
install any component not approved by Hearth & Home
Technologies
install parts or components not Listed or approved
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied
installer, service agency or your dealer.
WARNING! Risk of Fire!
Hearth & Home Technologies is not responsible for
discoloration, cracking or other material failures of
nishing materials due to heat exposure or smoke.
Choose nishing materials carefully.
5
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
2
Getting Started
A. Typical Fireplace System
Figure 2.1 Typical Fireplace System
Non-combustible
roof flashing maintains
minimum clearance
around chimney
Additional lateral
support for chimney
above roof (or enclosed
in chase) if needed
Enclosed space above
and around fireplace
Support straps
on rafter supports
chimney (not shown)
Outside
combustion air
Outside
combustion air
Termination Cap
Chimney penetrates roof
preferably without affecting
roof rafters
Storm Collar
Offset/Return
(with hanger straps)
Attic insulation shield
must be used here to
keep insulation away
from chimney if
attic is insulated
Framing headed
off in ceiling joists
Mantel
Decorative facing
and trim
Factory-built fireplace
Chimney system
Combustible
framing/header
on top of V-shaped
standoffs (spacers)
Hearth extension
Protective metal
hearth strip(s)
Chimney Air kit required for
SL chimney
Ceiling firestop on floor of attic
6
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
D
C
A
E
F
A
H
G
B
A
B
B
A
I
In an exterior chase
or projecting into a
garage
Across a corner
Along a wall
As a
room
divider
24 in.
(610mm)
24 in.
(610mm)
24 in.
(610mm)
48 in.
(1219mm)
*If interior of chase will be drywalled,
add the thickness to this
measurement.
°Faceplate to sidewall
24 in.
(610mm)
I
A
*
*
*
*
Figure 2.2 Fireplace Locations
NOTICE:
Illustrations and photos reect typical installations and
are FOR DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
Actual installation/appearance may vary due to individual
design preference.
Hearth & Home Technologies reserves the right to alter
its products.
NOTICE: In addition to these framing dimensions, also
reference the following section:
Clearances (Section 3).
NOTICE:
A minimum 1 in. air clearance at the back and a
minimum 1 in. air clearance to the sides of the
replace assembly must be maintained.
Chimney sections at any level require a 2 in. mini-
mum air space clearance between the framing
and chimney sections.
B. Design and Installation Considerations
NOTICE: Check building codes prior to installation.
• InstallationMUSTcomplywithlocal,regional,stateand
national codes and regulations.
• Consultinsurancecarrier,localbuildinginspector,re
ofcialsorauthoritieshavingjurisdictionoverrestrictions,
installation inspection and permits.
1. Selecting Fireplace Locations
Thisreplacemaybeusedasaroomdivider,installed
alongawall,acrossacornerorusedinanexteriorchase.
See Figure 2.2.
Locatingthereplaceinabasement,nearfrequently
opened door, central heat outlets or returns, or other loca-
tionsofconsiderableairmovementcanaffecttheperfor-
mance.
Outsideairmustbeusedforcombustion.ThePioneerII
comesequippedwithanoutsideairinlettofeedcombus-
tion air from outside the home, along with an outside air
terminationcap;therigidmetalductisrequiredbutnot
supplied.Considerationshouldbegiventothesefactors
beforedecidingonalocation.
Model # A B C D E F G H I
Pioneer(dimensionsfor
nishedwalls)
in. 42-1/2 16 89-1/2 63-5/16 22-7/16 44-3/4 14-1/16 56-9/16 54-1/2
mm 1080 406 2273 1608 570 1137 357 1437 1384
7
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
2. Locating Fireplace & Chimney
Locationofthereplaceandchimneywillaffectperfor-
mance.
• Installwithinthewarmairspaceenclosedbythebuilding
envelope.Thishelpstoproducemoredraft,especially
duringlightinganddie-downofthere.
• Penetratethehighestpartoftheroof.Thisminimizes
the effects of wind loading.
Locate termination cap away from trees, adjacent
structures,unevenrooflinesandotherobstructions.
• Minimizetheuseofchimneyoffsets.
• Considerthereplacelocationrelativetooorandceiling
and attic joists.
• Takeintoconsiderationtheterminationrequirementsin
Sections5and6.
Marginal Location:
• Below peak
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Multi-level Roofs
Windward
Leeward
Recommended Location:
• Above peak
Recommended:
• Insulated exterior chase
in cooler climates
Recommended Location:
• Above peak
• Inside heated space
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Marginal Location:
Wind loading possible
Locating the appliance in a basement or in a location of considerable air
movement/negative pressure can cause intermittent smoke spillage from
appliance.
DO NOT locate appliance near:
-Frequently Opened Doors
-Central Heat Outlets or Returns
Figure 2.3 Recommended Chimney Locations
• Installtheoutsideairkitwiththeintakefacingprevailing
winds during the heating season.
Ensure adequate outdoor air for all combustion
appliancesandexhaustequipment.
• Ensurefurnaceandairconditioningreturnventsarenot
locatedintheimmediatevicinityofthereplace.
• Avoidinstallingthereplaceneardoors,walkwaysor
small isolated spaces.
• Recessedlightingshouldbea“sealedcan”design.
Attic hatches weather stripped or sealed.
Attic mounted duct work and air handler joints and seams
taped or sealed.
8
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
C. Tools and Supplies Needed
Beforebeginningtheinstallationbesurethefollowing
toolsandbuildingsuppliesareavailable:
Reciprocating saw Framing material
Pliers Non-combustiblesealant
Hammer Gloves
Phillipsscrewdriver Framingsquare
Flatbladescrewdriver Electricdrillandbits
Plumbline Safetyglasses
Level Tapemeasure
1/2-3/4in.length,#6or#8self-drillingscrews
Misc.screwsandnails
D. Inspect Fireplace and Components
WARNING! Risk of Fire and/or Explosion! Damaged
parts could impair safe operation. DO NOT install dam-
aged, incomplete or substitute components. Keep re-
place dry.
• Removereplaceandcomponentsfrompackagingand
inspect for damage.
Vent system components are shipped in separate
packages.
Report to your dealer any parts damaged in shipment.
Read all the instructions before starting the
installation. Follow these instructions carefully
during the installation to ensure maximum safety
and benet.
E. Fireplace System Requirements
Thereplacesystemrequirementsconsistofthefollow-
ing:
• Fireplace
- Firebrick(includedwithreplace)
- Door(includedwithreplace)
- Non-combustible facing material (included with
replace)
- Protectivemetalhearthstrip(includedwithreplace)
- HearthExtension
• OutsideAir System (hood and collars included with
replace)
• Fascia(includedwithreplace)
Chimney System
- Chimneyairkit(includedwithreplace,requiredwith
SL300serieschimney)
- AtticInsulationShield(includedwithreplace)
• Non-combustiblenishmaterial
Optionalcomponentsinclude:
Lintel Bar
• HeatZoneKit
• Template
• OutsideAirElbowKit
9
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
3
Framing and Clearances
A. Fireplace Dimensions
Figure 3.1 Fireplace Dimensions
584
3
[76]
10
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
B. Clearances
WARNING! Risk of Fire!
You must comply with all minimum air space clearances to combustibles as specied in Figure 3.2. DO NOT pack required
air spaces with insulation or other materials. Framing or nishing material used on the front of, or in front of, the replace
closer than the minimums listed must be constructed entirely of non-combustible materials (i.e., steel studs, concrete board,
etc.). Failure to comply may cause re.
Figure 3.2 Clearances to Combustible Materials
2 in. (51 mm) min.
Attic
Insulation
Shield
Ceiling Firestop
(ceiling)
(roof)
(attic)
(ceiling)
Ceiling Firestop
Offset/Return with
hanger straps
Storm Collar
Roof Flashing
2 in. (51 mm) min.
2 in. min.
(51 mm)
Must have 2 in. (51 mm)
minimum clearance
to header
2 in. (51 mm) min.
2 in. (51 mm) min.
2 in. (51 mm) min.
1 in. (25mm) to side of appliance
(except at nailing flanges where it is 1/2 in. [13 mm])
1 in. (25 mm) to back
of appliance
0 in.
to floor
0 in. to level
of standoffs
2 in.
(51 mm)
min.
36 in. (914 mm)
standoffs to ceiling
Chimney air kit required
with SL chimney
11
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
1. Minimum Clearances
Position combustible mantel 60 in.
(1524 mm) from base of fireplace.
12 in.
(305 mm)
44 in.
(1118 mm)
24 in.*
(610 mm)
48-1/2 in.
(1232 mm)
42-1/2in.
(1080 mm)
The finished cavity depth must be no
less than 24 in. (610 mm) from the
finished backwall to the outside of
front wall framing.
2 x 4s must be used for the
header and framing above
the header to maintain pipe
clearances.
Double studs to catch
non-combustible board
and wall facing material.
*If interior of chase will be drywalled, add the thickness to this measurement.
12 in.
(305 mm)
When installing the
outside air with an
elbow/bend, allow a
minimum cavity of 12 in.
(305mm)
14 1/2 in. (368 mm) for
SL300 Chimney
16 in. (406 mm) for
DuraPlus Chimney
Position non-combustible mantel 46 in.
(1168 mm) from base of fireplace. Must
use non-combustible framing and Durock
above the fireplace to ceiling or 8 foot up
with a vaulted ceiling.
Figure 3.3 Framing the Fireplace
WITHIN ENCLOSURE AREA
Fireplacetobackwall 1in.(25mm)
Fireplace to sidewall 1in.(25mm)
Ductbootstoframing 0in.(0mm)
Topstandoffstoheader 0in.(0mm)
Door opening to sidewall 22-7/8in.(581mm)
EXPOSED SURFACES
Faceplate to sidewall 16in.(406mm)
Heatzoneairgrillstoceiling 12in.(305mm)
MANTEL
Non-combustiblemantel
(Non-combustibleframing
materialsabovethereplace
toceiling) 46in.(1168mm)
Combustiblemantel
(Combustibleframing
materialsabovethereplace
toceiling) 60in.(1524mm)
Maximummanteldepth 12in.(305mm)
12
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
C. Construct the Chase
Achaseisaverticalboxlikestructurebuilttoenclosethe
replaceand/oritsventsystem.Verticalchimneysthat
runontheoutsideofabuildingmustbeinstalledinsidea
chase.
Incoldclimates,Hearth&HomeTechnologiesrecom-
mendsthatthechasebewellinsulatedusingbatttype
insulationbetweenthejoists.
Constructionofthechasemayvarywiththetypeofbuild-
ing.Theseinstructionsarenotsubstitutesfortherequire-
mentsoflocalbuildingcodes.LocalbuildingcodesMUST
bechecked.
Chasesshouldbeconstructedinthemannerofalloutside
wallsofthehometopreventcoldairdraftingproblems.
Thechaseshouldnotbreaktheoutsidebuildingenvelope
inanymanner.Allouterwallsneedtobeinsulated.
Buildingcodesrequirefalseceilingandceilingrestops/
atticshieldsateachoorofthechaseorevery10ft(3048
mm)ofclearspacetocontrolspreadofre.
Walls,ceiling,baseplateandcantileveroorattherst
levelofthechaseshouldbeinsulated(seeFigure3.4.)
Vaporandairinltrationbarriersshouldbeinstalledinthe
chase as per regional codes for the rest of the home. Ad-
ditionally,Hearth&HomeTechnologiesrecommendsthat
theinsidesurfacesbedrywalledandtaped(ortheuseof
anequivalentmethod)formaximumairtightness.
Holesandotheropeningsshouldbecaulkedwithhigh
temperaturecaulkorstuffedwithunfacedberglass
insulation.
Ceiling
Firestop
Metal Chase Top
Round Termination Cap
False Ceiling
Insulation in the
outside walls
of the chase
Attic
Insulation
Shield
Chimney
Ceiling
Firestop
Tabs
False Ceiling
False Ceiling
Insulation
Insulation
Storm Collar
Figure 3.4 Chase Assembly
1 2 3
All outside walls should be insulated.
Figure 3.5 Chase Constructions
1. Fireplaceandchimneyenclosedinanexteriorchase.
2. Chimneyoffsetthroughexteriorwallandenclosedinchase.
3. Chase constructed on roof.
• Thechaseisconstructedusingframingmaterialsmuch
thesameasthewallsinyourhome.Avarietyofsiding
materials may be used including brick, stone, veneer
brick,orstandardsidingmaterials.
• In constructing the chase, several factors must be
considered:
- Maintain a 2 in. (51 mm) air space around the
chimney.
- The chase top must be constructed of non-
combustiblematerial.
- Incoldclimates,arestopspacerandatticinsulation
shieldshouldbeinstalledinaninsulatedfalseceiling
at the 8 ft. (2438 mm) level above the replace
assembly.Thisreducesheatlossthroughthechase.
- In cold climates, the walls of the chase should be
insulatedtothelevelofthefalseceilingasshownin
Figure3.4.Thiswillhelpreduceheatlossfromthe
homearoundthereplace.
ThreeexamplesofchaseapplicationsareshowninFig-
ure3.5.
WARNING! You must install false ceilings and ceil-
ing restops at each oor of the chase or every 10 ft
(3.05 m) to control spread of re.
WARNING! Risk of Fire! DO NOT seal area between re
stop opening and chimney pipe except where they enter
the attic or leave the warm air envelope of the home (use
600° F sealant).
WARNING! Risk of Fire! You must maintain a minimum
2 in. (51 mm) air space clearance to insulation and other
materials surrounding the chimney system.
Insulation and other materials must be rmly secured to
prevent accidental contact with chimney system.
The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with replace or chimney.
Failure to prevent contact between insulation or other
materials and chimney system may cause overheating
and re.
13
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
D. Frame the Fireplace
NOTICE: Hearth extension design must be determined
beforeinstallationofreplace.
Ifthereplaceisplacedontheoorthemaximumheight
ofanishedraisedhearthis5-3/4”,ifyouwantahigher
raisedhearththereplacemustbeplacedonaplatform.
NOTICE: Wiring for fans must be done before framed
enclosure is completed. If using a Heat Zone Kit, it
also must be installed before enclosure is complete.
WARNING! Risk of Fire! You must comply with all
minimum air space clearances to combustibles. DO NOT
pack required air spaces with insulation or other materi-
als.
WARNING! Risk of Fire! Comply with all minimum clear-
ances specied.
A minimum 1 in. (25 mm) air clearance must be
maintained at the back and 1 in. (25 mm) to the sides
of the replace assembly.
Chimney sections at any level require a 2 in. (51 mm)
minimum air space clearance between the framing and
chimney section.
Figure3.3showsatypicalframing(using2x4lumber)
ofthereplace,assumingcombustiblematerialsare
used.Allrequiredclearancestocombustiblesaroundthe
replacemustbeadheredto.SeeFigure3.2.Anyframing
acrossthetopofthereplacemustbeabovethelevelof
thetopstandoffs.(Norecessabovestandoffs.)
The
nished cavity depth must be no less than 24 in.
(610mm)fromthenishedbackwalltotheoutsideoffront
wallframing.Framingmustextendstraightupalltheway
to the ceiling.
CAUTION! Risk of Cuts/Abrasions. Wear protective gloves
and safety glasses during installation. Sheet metal edges
are sharp.
WARNING! Risk of Fire! Prevent contact with sagging,
loose insulation.
DO NOT install against vapor barriers or exposed
insulation.
Secure insulation and vapor barriers.
Provide minimum air space clearances at the sides and
back of the replace assembly as outlined in Section 3.
E. Secure and Level the Fireplace
Thisreplacemaybeplacedoneitheracombustibleor
noncombustiblecontinuousatsurface.Followthein-
structionsforframinginSection3.Slidethereplaceinto
position.Besuretoprovidetheminimum1in.airclear-
anceatthesidesand1in.atthebackofthereplace.
Thereplaceshouldbepositionedsothefaceofthenon-
combustiblematerialonthereplacewillbeushwiththe
faceofthedrywallonthewalls.SeeFigure3.6.
Levelthereplaceandshimasnecessary.Securethe
replace(usingthepalletmountingbracketslocatedon
eithersideofthereplace)tothesuboor.
These surfaces
must be even!
Drywall Non-combustible
facing material
Figure 3.6 Drywall - Non-combustible Facing Material
Standoffs are attached to the replace.
Theappliancecanbepositionedwiththestandoffstouch-
ingcombustiblewallsorframingbutDONOTpackinsula-
tionor other materials in theairspacebetweenthere-
place and wall.
14
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
1in. (25 mm) Overlap
Metal strips 2 in. (51 mm) under edge of Fireplace
and Hearth Extension and extended 2 in. (51 mm)
beyond both sides of fireplace opening.
Nail or screw metal strips in place.
Pallet Mounting/Floor
Brackets
Raised Platform
Floor
2 in.
(51 mm)
1 in. (25 mm) min.
overlap
2 in.
(51 mm)
Top piece must overlap
bottom piece
Figure 3.8 Protect the Front of an Elevated Platform
F. Protective Metal Hearth Strips
Figure 3.7 Position the Protective Metal Hearth Strips
• Locatethetwoprotectivemetalhearthstripsmeasuring
approximately26in.x4in.(660mmx102mm)included
withthisreplace.
• Slideeachmetalstrip2in.(51mm)underfrontedgeof
replace.
• Overlapstripsinthemiddleofreplaceopeningby1in.
(25mm)minimum.
• Metal strips must extend beyond the front and sides
of the replace opening by at least 2 in. (51 mm),
Figure3.7).
• Protectthefrontofaplatformelevatedabovethehearth
extensionwithmetalstrips(notincludedwithreplace)
per Figure 3.8. See Section 6 for hearth extension
instructions.
WARNING! Risk of Fire! Protective metal hearth
strips MUST be installed on combustible surfaces. DO
NOT cover metal strips with combustible materials.
Sparks or embers may ignite ooring.
WARNING! Risk of re! High temperatures, sparks,
embers or other burning material falling from the
replace may ignite ooring or concealed combustible
surfaces.
Protective metal hearth strips MUST be installed.
Hearth extensions MUST be installed exactly as
specied.
WARNING! Risk of Fire!
Follow these instructions exactly.
Facing materials must be installed properly to prevent
re.
No materials may be substituted without authorization by
Hearth & Home Technologies
G. Facing Material
TOOLS NEEDED: Powered drill with #2 Phillips head bit;
caulking gun.
Onlynon-combustiblematerials(suppliedwithreplace)
maybeusedtocoverthemetalreplacefront.
NOTE: All boards are pre-drilled for your convenience.
Boards MUST be attached in the following order:
bottom, top, and then the two sides, red-painted side
out. The top and bottom board should each have a hang
tag attached. Leave them attached for referral for the
nishing operation.
• Attach the bottom board to the bottom of the outer
replacecanwithenclosedscrews,ensuringtheboard
is centered. DO NOT remove hang tags.
Centerandattachthetopboardtotheoutercanand
framingmembers. DO NOT remove hang tags.
• Using the Super Calstick or equivalent 1000°F high
temperaturesealant,runalightbead(1/8in.minimum)
betweenthemetalsurfaceofthereplaceandthebutt
edgesofthetopboard.SeeFigure3.9.
• Ensuringthetopofthesidepiecesandthetopboard
align, attach the side pieces to the outer can and framing
members.
Figure 3.9 Apply Non-combustible Materials
Side
Board
Bottom
Board
Side
Board
Top
Board
DO NOT
remove hang
tags
NOTICE: 1/8 in. of the facing material may be visible
after nishing materials are applied. This 1/8 in. must
be painted or the red will show.
Apply bead of Super
Calstick or equiva-
lent 1000°F high
temperature sealant
to edge here
15
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
H. Outside Air Kit
Anoutsideairkitmustbeusedforcombustion.Hearth&
HomeTechnologiesrecommendsyouutilizetheshortest
duct run to optimize the performance of the outside air
kit.Theoutsideairinlethoodshouldbepositionedina
mannerthatwillnotallowsnow,leaves,etc.toblockthe
inlet.Insomeinstallationstheairductmayneedtoberun
vertically.Insuchaninstallation,a3ft(914mm)height
differencemustbemaintainedfromthetopoftheupper-
most chimney section to the outside air inlet hood.
Refer to Figures 3.10 and 3.12 when placing the outside
air inlet hood.
Theoutsideairkitisinstalledontherighthandsideofthe
replace.SeeFigure3.13forhandlelocation/operation.
Cut a 6-1/2 in. (165 mm) hole in outside wall to
accommodate air piping.
• Use6in.(152mm)metalexorrigidpiping(notsupplied)
to directly connect outside air to fireplace intake.
Insulating the pipe isn’t required but will help prevent
frost condensation.
Use the supplied outside air inlet hood.
• Seal between the wall and the pipe with silicone to
preventmoisturepenetrationandairleaks.
• Sealbetweentheoutsideairinlethoodandthehouse
withsiliconetopreventairinltration.
CAUTION! Risk of Cuts/Abrasions. Wear protective
gloves and safety glasses during installation. Sheet metal
edges are sharp.
CAUTION! Risk of Fire or Asphyxiation! DO NOT draw
outside combustion air from wall, oor or ceiling cavity, or
enclosed spaces such as an attic or garage.
DO NOT place outside air inlet hood close to exhaust
vents or chimneys. Fumes or odor could be drawn into
the room through the replace.
Locate outside air inlet hood to prevent blockage from
leaves, snow/ice, or other debris. Blockages could cause
combustion air starvation.
Figure 3.10 Outside Air Inlet Locations
Attic insulation shield
must be used to keep
insulation away from
chimney.
Ceiling firestop
on floor of attic.
3 ft min. from top of
uppermost chimney
section to air inlet.
OA-RD-6 Outside Air Elbow Kit - Optional
Canbeusedwhenspaceisanissue.
1. Iftheoutsideaircollarisontheapplianceremoveit.
2. Attachthecollartotheelbowkit.
3. Attachedtheelbowkittotheappliancewiththescrews
providedinthecorrectorientationneeded.SeeFigure
3.11.
7-3/8”
(187mm)
Figure 3.11 Outside Air Elbow Kit
16
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
Outlet blocked by
snow, leaves, etc.
NO
Garage or
combustible
liquids storage
NO
Attic space
NO
Outlet placed
higher than 3 ft
below the
termination cap
NO
UL181 Listed Class 0
or Class 1 metal flex or
rigid duct
Clear area
outside
house or in
ventilated
crawl space
YES
Figure 3.12 Outside Air Installation
Figure 3.13 Outside Air
Termination Cap
supplied with
fireplace
UL 181 Listed Class 0 or
Class 1 metal flex or rigid
duct
Open/Close
Knob for
outside air
CLOSE
OPEN
17
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
DUCT RUN REQUIREMENTS
MAXIMUMDuctRun=40-ft.(12m)
MINIMUMDuctRun=36in.(914mm)
DUCTING MATERIAL
6in.(152mm)B-VentOnly
DONOTductintoexistingfurnaceplenum
MINIMUM CLEARANCE TO COMBUSTIBLES
1in.(25mm)fromtheB-Vent
1
/2in.(13mm)fromtop&bottomofoutletbox
0in.(0mm)fromthesidesofoutletbox
12in.(305mm)fromwallregistertoceiling
Refer to Figure 3.13.
CAUTION! ALL wiring should be done by a qualied elec-
trician and shall be in compliance with local codes and
with the National Electric Code NFPA/NEC No. 70-current.
CSC22.1 Canadian Electric Code.
Possible Air Duct Runs / Locations
Figure 3.14 Minimum Clearances to Combustibles
I. Heat Zone Kit (Optional)
TheHeat-Zoneaccessorykitconveyswarmairfromthe
replacethroughairduct(s)toremotelocationsinthe
sameroomorotherroomsofthebuilding.Youmayinstall
1or2Heat-Zonekitsonthereplace.Installationofthis
kit MUSTbeperformedbyaqualiedservicetechnician.
If any parts are missing or damaged, contact your local
dealerbeforestartinginstallation.DONOTinstalladam-
aged kit.
Thiskitistestedandsafewheninstalledinaccordance
withthisinstallationmanual.Itisyourresponsibilityto
readallinstructionsbeforestartinginstallationandtofol-
low these instructions carefully during installations.
TheHeat-Zone®Woodkitiscarefullyengineeredand
mustbeinstalledonlyasspecied.Ifyoumodifyitorany
ofitscomponentsyouwillvoidthewarrantyandyoumay
possiblycausearehazard.Installationmustbedone
accordingtoapplicablelocal,state,provincialand/or
national codes.
Planthelocationofthereplaceandwarmairductrun(s).
Ceiling Register
Wall Register
Floor Register
Two Duct Kits
Ceiling Register
12 in. (305mm) minimum clearance
from register to ceiling
17 in. (432mm) minimum
clearance to allow for
venting
18
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
Installation
• Removetheknockoutorcoverplatefromthetopofthe
replaceanddiscardit.SeeFigure3.15.
• Cuta3in.(76mm)holeintheinsulationboardasper
thedimensionsshowninFigure3.15.
Adapter
Mounting
Plate
Starter Pipe
Knockout
3-13/16 in.
(97 mm)
3-1/8 in. (79 mm)
C
L
Run Length Cut Pipe
20 - 40 ft (6-12 m) 2 in. (51 mm)*
*A minimum of 2 in. (51 mm) pipe must be used to
cover the raw insulation to prevent it from blowing
out through the return air grille.
10 - 20 ft (3 - 6 m) 8 in. (203 mm)
3 - 10 ft (1 - 3 m) No cut needed**
**Use full 16 in. (406 mm) as supplied
Determine the necessary length of starter pipe from the
Table3.1andcutasrequired.
Figure 3.15
• Slide the starter pipe into the replace, matching the
holesintheplatetotheholesinthereplace.
Place the adapter on the mounting plate lining up holes.
Using four sheet metal screws included in the kit, secure
the adapter and mounting plate into replace.After
securingtothereplace,tapedowntheadapteredges
tothetopofthereplacewithaluminumtapetoprevent
leakage.
Determine the location for the air register and fan
housingassembly.Cuta7-5/8in.x13-5/8in.(143mm
x346mm)holebetweenframingmembers(wallstuds
oroorjoists).Thebracketscanberotated180°and
mountedtothebacksideofthe2x4ifnecessary.See
Figure 3.17.
NOTICE: The fan and electrical connections must be
accessible for servicing per local code requirements.
NOTICE: If the fan housing is installed in a 2 x 4 wall,
the front of the housing will protrude approximately 1/4
in. (6 mm) from the nished wall.
• Attachenough 6 in. (152 mm) B-Vent asrequired for
your installation to the fan housing. A maximum of (4)
90° elbows is recommended. Securely twist lock the
B-Vent to the adapter.
AlsoscrewtheB-Venttotheoutletboxonthefan
housing. See Figure 3.17.
Supportductatintervals
ofnogreaterthan4ft(1m)asrequiredbylocalcode.
Figure 3.16
WARNING! Risk of Fire! Comply with all minimum
clearances specied.
A minimum 1 in. (13 mm) air clearance must be
maintained at the back and 1 in. (25mm) to the sides
of the replace assembly.
NOTE: It is important the pipe length be adhered to
or it will affect the performance of your replace.
• Onthemountingplate,handbendthetabsdownward.
Slidethetabsovertheoutsideofthestarterpipe.Secure
with four sheet metal screws included in fasteners
package.Figure3.16.
Table 3.1
19
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
Securely Twist
Lock B-Vent to
Adapter
Secure B-Vent to Fan Housing
with sheet metal screws
Return Air Grille
Install with Louvers
pointed down
Bracket
Can rotate
180
o
2 x 4 Wall
Fan Housing
1/2 in. (13mm)
clearance to
combustibles
must be
maintained.
2 x 4 wall
Sheet Rock
Leave 1/4" (6mm) clearance
from all 4 outer edges
Seal grille using gasketing supplied with the kit
• Installthevariablespeedwallrheostat(withsettingon
“OFF”)inaconvenientlocation.Thisswitchwillcontrol
theHeat-Zonefanoperation.
• Remove the junction box. Wire 110 VAC service TO
the wall rheostat and FROM the wall rheostatto the
fanjunctionbox.Usewirenutstosecurethe110VAC
servicewirestothehot(black)andneutral(white)fan
wires and screw the 110 VAC ground wire to the junction
box.SeeFigure3.20.
Secure the return air grille to the fan housing making
sure it is ush.The grille must be installed with the
louverspointingdown.
NOTICE: DO NOT USE ADJUSTABLE REGISTERS.
Junction Box Removed
Wire Clamp
Wire Nuts
Junction Box
Black
White
NOTICE: Secure the duct so that clearance to the re-
place outer wrap is maintained. Tape all seams with alumi-
num tape 1-1/4 in. (32 mm) minimum width or as specied
by local codes.)
Seal all the way around the inside of the return air grille to
preventhotairbeingdrawnbackintotheventingsystem
usinggasketingsuppliedwiththekit.Leave1/4in.(6
mm)clearancefromallfourouteredges.Trimexcess
gasketing.SeeFigure3.19.
Figure 3.17
Figure 3.18
Figure 3.19
Figure 3.20
20
Quadra-Fire • PIONEER II • 4181-901 Installation Manual • Rev I • 08/19
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44