Q-tran Q-TRAN QTM-eLED+DALI-DT6 LED Power Supply Installation guide

Type
Installation guide

This manual is also suitable for

INSTALLATION LED POWER SUPPLY - QTM-eLED+DALI-DT6
© 2021 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-11-15-22
LOW VOLTAGE LIGHTING SYSTEM
CLASS: 3425-15
3425-95
COMPLIANT
Wear rubber shoes and work on a sturdy wooden or fiberglass ladder.
This power supply must be installed according to the National Electric
Code and local codes and ordinances.
This power supply is to be installed and serviced only by an licensed
electricians.
This power supply is to be installed so that it is not likely to be contacted
by people.
To avoid a hazard to children, account for all parts and destroy all
packaging materials.
Do not install in wet locations.
Must be installed by licensed electrician.
INSTALLATION LED POWER SUPPLY - QTM-eLED+DALI-DT6
© 2021 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-11-15-22
HORIZONTAL VERTICAL RECESSED MOUNT
Plenum Door Required
Horizontal
Vertical
SURFACE SPACING SURFACE STACKING ROD SUSPENSION
9.5" O.C.
16" O.C.
19" O.C.
9.5" O.C.
9.5" O.C.
More Units can be stackedMore Units can be stacked
More Units can be stacked
NOTE: Rods not included.
RECESSED
SURFACE
ROD SUSPENSION
(Horizontal)
ROD SUSPENSION
(Vertical)
Double Sided
Key Hole
1/4" Rod Thru Hole
3/8" Rod Thru Hole
NOTE: Bracket can also be mounted (Top & Bottom)
for Vertical Mounts.
0.875" KNOCKOUT 9X
(FOR 1/2" FITTINGS)
4.00"
BOTTOM VIEW
14.5"
8.00" 4.00"
ISOMETRIC VIEW
8.00"
Mounting Options
Housing
INSTALLATION LED POWER SUPPLY - QTM-eLED+DALI-DT6
© 2021 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-11-15-22
WARNING: Risk of electrical shock. May result in serious injury or death. Disconnect power before servicing or installing.
CAUTION: The device may only be connected and installed by a qualified electrician. All applicable regulations, legislation and building codes
must be observed. Incorrect installation of the device can cause irreparable damage to the device and the connected LEDs.
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
LED
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
LED
Primary Wiring
Control Wiring: DALI Connections
Secondary Wiring
NEU
GND
HOT
LED DRIVER
(120-277V)
V-
V-
V+
V+
+
R-
G-
B-
W-
D1+
D2+
D1-
D2-
LED groups 12-36VDC IN
D2-
D1-
D2+
D1+
V+
V+
V-
V+
V-
B-
R-
G-
W-
LED groups 12-36VDC IN
DALI Signal
in/out
V-
V-
V+
V+
+
R-
G-
B-
W-
D1+
D2+
D1-
D2-
LED groups 12-36VDC IN
DALI Signal
in/out
DALI Signal
in/out
DALI
Controller
D1+
D2+
D1-
D2-
DALI
IN
DALI
OUT
2-Wire default is 1 address 3-Wire default is 2 address
Connecting and Configuring the DALI-DT6 Decoder
To DALI Controller
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
D1+
D2+
D1-
D2-
{
12-36VDC IN
-+2
10.2-1.5 mm2
0.35 inch
0.5-1.5 mm2
AWG 20-16
0.35 inch
AWG 24-16
VDC and LED connectors: Other connectors:
LED
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
DALI
Controller
*By Others
DALI Bus
Power Supply
*By Others
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC IN LED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
DALI
OUT
DALI
IN
DALI
Controller
*By Others
DALI Bus
Power Supply
*By Others
-
+24V
-+
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
D1+
D2+
D1-
D2-
12-36VDC IN LED groups
DALI Signal
in/out
DALI
OUT
DALI
IN
DALI
Controller
*By Others
DALI Bus
Power Supply
*By Others
Warm
Cool
+24V
+24V W C
3-Wire2-Wire
2A - 2 Addresses1A - 1 Addresses
NOTE:
2-Wire default is 1 address
3-Wire default is 2 addresses
For customization or pre-programming
contact a local sales rep.
DALI commissioning to be performed by
a third party at time of installation.
INSTALLATION LED POWER SUPPLY - QTM-eLED+DALI-DT6
© 2021 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-11-15-22
Other Features
0-6 0-9
1 2
Manual set button
Digital display
1. Set address manually:
(tens) (ones)
00~63
1 2
Press and hold either button
Use the buttons to set address
1 2
Set Address
(5 sec)
2. Set LED groups:
Changing LED group
1A-SW
2A-TW
1 2
Press and hold both button
Use the first button to set the
amount of addresses
(5 sec)
1. Locking the configuration:
Confirm
1 2
Press and hold either button
(5 sec)
2. Reset to factory defaults:
Reset
1 2
1 2
Set Address
Press and hold either button
(5 sec)
Use the buttons to set address
DT6 Dimming Feature:
NOTE: DT6 color type of the dimmer can be SW, WD, or TW.
Manual Configuration
INSTALLATION LED POWER SUPPLY - QTM-eLED+DALI-DT6
© 2021 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-11-15-22
C
LED DRIVER 2
(120 - 277V)
B
LED DRIVER 2
(120 - 277V)
LED DRIVER 2
B
NEU
GND
HOT
DALI
IN
DALI
OUT
V-
V-
V+
V+
+
1(-)
2(-)
3(-)
4(-)
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
V-
V-
V+
V+
+
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
V-
V-
V+
V+
+
12-36VDC INLED groups
D1+
D2+
D1-
D2-
DALI Signal
in/out
SECONDARY
PRIMARY
DA -
DA +
Red = +24V
Black = Negative
LEAD WIRE
1(-)
2(-)
3(-)
4(-)
1(-)
2(-)
3(-)
4(-)
NEU
GND
HOT
DA +
DA -
Red
Blue
-+-+-+
To next
power supply
LEDLED LED
DALI
Controller
*By others.
DALI Bus
Power Supply
*By others.
NEU
GND
HOT
LED DRIVER
(120-277V)
Wiring Installation
INSTALLATION LED POWER SUPPLY - QTM-eLED+DALI-DT6
© 2021 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-11-15-22
This product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
CE PRODUIT DOIT ÊTRE INSTALLÉ SELON LE CODE D'INSTALLATION
PERTINENT, PAR UNE PERSONNE QUI CONNAÎT BIEN LE PRODUIT ET
SON FONCTIONNEMENT AINSI QUE LES RISQUES INHÉRENTS.
LOW VOLTAGE
LIGHTING SYSTEM
Q-TRAN, INC.
MILFORD, CT U.S.A.
(203) 367-8777
WWW.Q-TRAN.COM
Type Ic Recessed, Inherently Protected
Type IC ENCASTRE, PROTECTION INHÉRENTE
For Supply Connections Use Wire Rated for At Least 60C.
Pour les connexions d'alimentation, utilisez des fils
calibrés pour au moins 60C.
Suitable For Damp Locations
CONVIENT AUX EMPLACEMENTS HUMIDES
Class 2
Classe 2
CLASS: 3425 - 95
3402 - 95
QTM-eLED-100+DALI
QTM-eLED-200+DALI
QTM-eLED-300+DALI
0.95 / 0.40
1.90 / 0.80
2.85 / 1.20
50/60
50/60
50/60
24
24
24
100
200
300
120 / 277
120 / 277
120 / 277
Model Input Voltage
(V)
Frequency Nominal Output
Voltage (VDC)
Nominal Output
Wattage (W)
Input Current
(A)
120V - 277V
INPUT VOLTAGE OUTPUT VOLTAGE
24V
CONTROL TYPE
DT8
DT6
6.00"
3.15"
QTM-eLED+DALI
QTM-eLED+DALI
C/US
Suitable for indoor use
This power supply must be installed according to the National Electric Code and local codes and ordinances and in accordance with
applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
Wear rubber shoes and work on a sturdy wooden or fiberglass ladder.
This power supply is to be installed in a location where it is not likely to be contacted by non-electricians.
To avoid a hazard to children, account for all parts and destroy all packaging materials.
CSA Requirements
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

Q-tran Q-TRAN QTM-eLED+DALI-DT6 LED Power Supply Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI