DI21 - DI24 Menu
Measurements AKL Error When "ON", there is an alarm message. See page 8.
DI21 State Status of input. ON = input energised
DI21 Count Counter registering the number of changes from OFF to ON on the input
DI21 Hours Counter adding up the number of hours the input has been ON
DI..... As above for DI22 to DI24
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
DI21 Select The input is defined with the following settings:
0: Input not used
1: Input used as alarm input (230 V = OK. 0 V = alarm)
1: Input used for registration of time of defrost“
(230 V = defrost, 0 V = no defrost)
1: The input is used for suppression of alarms
(230 V = alarm option, 0 V = no alarms)
(If the input has been defined for “Defrost signal” or “alarm suppression” the setting in this
menu will be overwritten by “1”.)
DI21 Delay Time delay for alarm
(If the input is connected to a temperature input, the setting will automatically return to 0.
Cf. "S1 /DI Link")
DI21 Reset Resetting of the two counters (the counters are reset by changing OFF to ON, after which
the setting will automatically return to OFF)
DI..... As above for DI22 to DI24
Power meters
Measurements AKL Error When "ON", there is an alarm message. See page 8.
A PulseCnt Pulse counter A (Can be zeroset with “A ResetCnt” and “A puls/ kWh”)
B PulseCnt Pulse counter B (Can be zeroset with “B ResetCnt” and “B puls/ kWh”)
AConsm.kWh Energy measurement counter A (Can be reset with “A ResetCnt” and “A puls/kWh”)
BConsm.kWh Energy measurement counter B (Can be reset with “B ResetCnt” and “B puls/kWh”)
A Load kW Load measurement counter A (averaged over the period “LoadPer.m”)
B Load kW Load measurement counter B (averaged over the period “LoadPer.m”)
A yDay kWh Energy consumption during past 24 hours (from 00.00 to 24.00 hrs)
B yDay kWh Energy consumption during past 24 hours (from 00.00 to 24.00 hrs)
AlWeek kWh Energy consumption during past whole week (from Monday 00.00 hrs to Sunday 24.00 hrs)
BlWeek kWh Energy consumption during past whole week (from Monday 00.00 hrs to Sunday 24.00 hrs)
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
A ResetCnt If you select pos. ON, pulse counter A and energy measurement A will be zeroset (“A
PulseCnt” and “AConsm.kWh” = 0)
B ResetCnt If you select pos. ON, pulse counter B and energy measurement B will be zeroset
("B PulseCnt" and "BConsm.kWh" = 0)
A puls/kWh Set number of impulses corresponding to one kWh (counter A)
B puls/kWh Set number of impulses corresponding to one kWh (counter B)
AOffset kWh Displacement of energy measurement counter A
(display in “AConsm.kWh” is displaced with this setting)
BOffset kWh Displacement of energy measurement counter B
(display in “”BConsm.kWh” is displaced with this setting)
LoadPer.m Updating period for the “Load measurement” displays
If the setting in the next function “Load Func” is put in pos. ON, the updating period will be
overwritten by the period registered on input CT2
LoadFunc. Definition of counter function
OFF: Both counter circuits are used. The updating period “LoadPer.m” must be set.
ON: One counter circuit is used. The updating period is received on the CT2 input.