Danfoss Monitoring unit type AKL 111A. Vers. 2.0x. AKM Installation guide

Type
Installation guide
Software version 2.0x
Monitoring unit
AKL 111A
ADAP-KOOL
®
Menu operation via AKM
RC.1H.60.02 ® RC.1H.61.02 10-2000
2 Menu operation RC.1H.61.02 © Danfoss 10/2000 AKL 111A Version 2.0x
Menu list This menu function can be used together with system software type AKM. The description is
divided up into function groups that can be displayed on the PC screen. Within each group it
is now possible to show the measured values, or settings. Regarding the use of AKM,
reference is made to the AKM Manual.
Validity This menu operation (dated October 2000), applies to controller type AKL 111A, code
number 084B6039 with programme version 2.0x.
Function groups
The operation is divided up into several
function groups. When a selection has been
made, push “OK”, and you may continue to
the next display. By way of example, “
M0 -
M8 MAIN MENU
has been selected here.
From the measure line the different values
can be read. The values are constantly
updated.
In the list of settings the set values can be
seen. If a setting has to be changed, select
the parameter and proceed via OK.
Measurements The various measurements can be read directly. If a graphic display of the measurements is
required, up to eight of them can be shown. Select the required measurements and push
Trend.
Settings There are four kinds of settings, ON/OFF settings, settings with a variable value, time settings
and reset alarms.
Enter the new value or move the sliding scale up or
down. The new value will apply, when OK is pushed.
Set the required value and push
OK
AKL 111A Version 2.0x Menu operation RC.1H.61.02 © Danfoss 10/2000 3
Alarms
M0 - M8 Main menu
Measurements AKL Error When "ON", there is an alarm message. See page 8.
AKA14 Show Signal from the switch determining the signal to be shown on the AKA 14 display
1 = input 1
2 = input 2 osv.
The switch can only make the display show the mentioned inputs, if the unit has been set
for it, cf. "AKA 14 Sel.".
S1 °C Signals for outputs 1 to 8 are shown here:
- If a temperature signal is registered, the value will be indicated in °C
(e.g. S1 °C 10) (any set off-set will be included in the display)
DI1 - If a contact signal is monitored, the value will be shown with
ON or OFF (e.g. DI 1 ON)
ON = no alarm
OFF = alarm upon expiry of time delay
S..... As above for S2 to S8
D..... As above for DI2 to DI8
See page 8.
Go through the individual functions one by one and make the required settings. When settings
have been made for one controller, the set values may be used as basis in the other
controllers
of the same type
and
with the same software version
. Copy the settings by using
the copy settings function in the AKM programme, and adjust subsequently any settings where
there are deviations.
NB! If a list is required for noting down the individual settings, a printout can be made of it
with a function in the AKM programme. Read the next section, “Documentation”.
Documentation Documentation of the settings of the individual controllers can be made with the print function
in the AKM programme. Select the controller for which documentation of the settings is re-
quired and select the Print Settings function (cf. also the AKM Manual).
Functions Shown below are function groups with corresponding measurements and settings. A printout
of the given settings can be made using the AKM function Print Settings (see above).
4 Menu operation RC.1H.61.02 © Danfoss 10/2000 AKL 111A Version 2.0x
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
AKA 14 Sel. The following can be defined:
0: Determined with this setting is the display of a switch connected to terminals 88-89. (But
if one of the subsequent settings is selected, it will override this switch setting)
1: Display of signal at input 1 (S1/DI1) terminals 90-91
2: Display of signal at input 2 (S2/DI2) terminals 92-93
-
-
8: Display of signal at input 8 (S8/DI8) terminals 106-107
M1 °C/DI Readout of configuration of input M1
0: Input not used
1: Signal received from a temperature sensor
2: Signal received from a contact function
M... °C/DI As above for M2 to M8
M1 - M8 Configuration
Measurements AKL Error When "ON", there is an alarm message. See page 8.
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
M1 °C/DI Set signal to be received at input 1 (S1/DI1) terminals 90-91
The input is defined with the following setting:
0: Input not used
1: Signal received from a temperature sensor
2: Signal received from a contact function
S1 Hi.Al. Upper alarm limit
S1 Lo.Al Lower alarm limit
S1 / DI Link If change to another time delay for the alarm during defrost is required,
set the high voltage input here that will deliver the defrost signal:
0: No change of time delay
1: Signal received by DI21
2: Signal received by DI 22
3: Signal received by DI23
4: Signal received by DI24
M1 Al Suppr If alarms from a signal input have to be suppressed when the refrigeration appliance is
switched off, the setting must be done in this menu. Here you set which high voltage input
is to supply the signal indicating that the refrigeration appliance has been switched off.
0: Normal operation with alarm
1: Signal received by DI21
2: Signal received by DI 22
3: Signal received by DI23
4: Signal received by DI24
S1 Corr. Offset adjustment of temperature signal received at the input
Delay 1 Time delay for the alarm in minutes
S1 Def.Del Overridden time delay for the alarm when the input has been connected to a defrost
registration with the setting at "S1 / DI Link".
M ... As above for M2 to M8
AKL 111A Version 2.0x Menu operation RC.1H.61.02 © Danfoss 10/2000 5
DI21 - DI24 Menu
Measurements AKL Error When "ON", there is an alarm message. See page 8.
DI21 State Status of input. ON = input energised
DI21 Count Counter registering the number of changes from OFF to ON on the input
DI21 Hours Counter adding up the number of hours the input has been ON
DI..... As above for DI22 to DI24
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
DI21 Select The input is defined with the following settings:
0: Input not used
1: Input used as alarm input (230 V = OK. 0 V = alarm)
1: Input used for registration of time of defrost
(230 V = defrost, 0 V = no defrost)
1: The input is used for suppression of alarms
(230 V = alarm option, 0 V = no alarms)
(If the input has been defined for Defrost signal or alarm suppression the setting in this
menu will be overwritten by 1.)
DI21 Delay Time delay for alarm
(If the input is connected to a temperature input, the setting will automatically return to 0.
Cf. "S1 /DI Link")
DI21 Reset Resetting of the two counters (the counters are reset by changing OFF to ON, after which
the setting will automatically return to OFF)
DI..... As above for DI22 to DI24
Power meters
Measurements AKL Error When "ON", there is an alarm message. See page 8.
A PulseCnt Pulse counter A (Can be zeroset with A ResetCnt and A puls/ kWh)
B PulseCnt Pulse counter B (Can be zeroset with B ResetCnt and B puls/ kWh)
AConsm.kWh Energy measurement counter A (Can be reset with A ResetCnt and A puls/kWh)
BConsm.kWh Energy measurement counter B (Can be reset with B ResetCnt and B puls/kWh)
A Load kW Load measurement counter A (averaged over the period LoadPer.m)
B Load kW Load measurement counter B (averaged over the period LoadPer.m)
A yDay kWh Energy consumption during past 24 hours (from 00.00 to 24.00 hrs)
B yDay kWh Energy consumption during past 24 hours (from 00.00 to 24.00 hrs)
AlWeek kWh Energy consumption during past whole week (from Monday 00.00 hrs to Sunday 24.00 hrs)
BlWeek kWh Energy consumption during past whole week (from Monday 00.00 hrs to Sunday 24.00 hrs)
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
A ResetCnt If you select pos. ON, pulse counter A and energy measurement A will be zeroset (A
PulseCnt and AConsm.kWh = 0)
B ResetCnt If you select pos. ON, pulse counter B and energy measurement B will be zeroset
("B PulseCnt" and "BConsm.kWh" = 0)
A puls/kWh Set number of impulses corresponding to one kWh (counter A)
B puls/kWh Set number of impulses corresponding to one kWh (counter B)
AOffset kWh Displacement of energy measurement counter A
(display in AConsm.kWh is displaced with this setting)
BOffset kWh Displacement of energy measurement counter B
(display in “”BConsm.kWh is displaced with this setting)
LoadPer.m Updating period for the Load measurement displays
If the setting in the next function Load Func is put in pos. ON, the updating period will be
overwritten by the period registered on input CT2
LoadFunc. Definition of counter function
OFF: Both counter circuits are used. The updating period LoadPer.m must be set.
ON: One counter circuit is used. The updating period is received on the CT2 input.
6 Menu operation RC.1H.61.02 © Danfoss 10/2000 AKL 111A Version 2.0x
Extended Functions
Measurements AKL Error When "ON", there is an alarm message. See page 8.
AlarmReset Status of input for acknowledgement of alarm
ON = acknowledgement (230 V on the input)
AlarmRelay Reading of alarm relays actual position
ON = relay switch cut in = no alarm
OFF = alarm
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
Language Selection of language.
0: English 3: Danish 6: Swedisch
1: German 4: Spanish
2: Franch 5: Italian
NB! If this setting is changed, another Upload must be made of the controller's data for the
AKM programme. You do it this way:
- Select one of the available languages.
- Close the menu
- Proceed to menu Configuration - Advanced Configuration - Delete descriptionfile
- Push file type Default
- Select controller's code number and software version
- Push OK
- Proceed to menu Configuration - Upload
- Complete the fields Network, Net configuration and AKC description
- Push OK
Texts will now be obtained from the controller in the required language.
Man. Ctrl. ON: Manual setting permitted
AlarmRelay Forced control of alarm output
ON = relay switch cut in = no alarm
OFF = alarm
AKL 111A Version 2.0x Menu operation RC.1H.61.02 © Danfoss 10/2000 7
Alarm destinations
Measurements AKL Error When "ON", there is an alarm message. See page 8.
Settings Main Switch Function switchs: 1: Regulation
0: Controller stopped
-1: Service function
Network ON: When alarms are registrated via PC or Gateway printer
OFF: When alarm are registrated via AKA 21, only
Set the priority for the following alarm texts (choose between 1, 2, 3 or 0. They have the following meaning:)
1: Relay output + relay output on master gateway must draw
+ as a message on DANBUSS
2: As a message on DANBUSS
3: Relay output must draw + as a message on DANBUSS
0: No activity (no alarm function)
StandbyMod (Regulation has stopped)
Dest. 1 Alarm from input 1
Dest. 2 Alarm from input 2
Dest. 3 Alarm from input 3
Dest. 4 Alarm from input 4
Dest. 5 Alarm from input 5
Dest. 6 Alarm from input 6
Dest. 7 Alarm from input 7
Dest. 8 Alarm from input 8
DI21 Dest. Alarm from input DI21
DI22 Dest. Alarm from input DI22
DI23 Dest. Alarm from input DI23
DI24 Dest. Alarm from input DI24
S1 Error Sensor error from input 1
S2 Error Sensor error from input 2
S3 Error Sensor error from input 3
S4 Error Sensor error from input 4
S5 Error Sensor error from input 5
S6 Error Sensor error from input 6
S7 Error Sensor error from input 7
S8 Error Sensor error from input 8
AKM menu "For DANFOSS only"
This menu contains data and setting values for special internal controller functions.
Do not chage the stated values.
8 Menu operation RC.1H.61.02 © Danfoss 10/2000 AKL 111A Version 2.0x
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
AC-RDT
The following alarm messages may occur:
Alarm message Meaning Action/cause
Sx Error Faulty Sx sensor Check sensor connection / sensor resistance
Standby mode Regulation has stopped The function switch (Main Switch) is set in the
position "Service function".
High Air Temp. Too high temperature from Check the function monitored by the input
Sx Sx input
Low Air Temp. Too low temperature from Check the function monitored by the input
Sx Sx input
DI x Alarm Alarm froma x-input Check the function monitored by the input
Alarms may be acknowledged one by one by
selecting one, and then pushing "OK". An Alarm
message will now appear, e.g.:
Push "OK" to acknowledge.
The menu display for alarms shows the active alarms. Dots will appear at the top of the menu for as long as
data is being obtained.
Alarms
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8