Danfoss Monitoring unit type AKL 111A. Vers. 2.0x. AKA 21 Installation guide

Type
Installation guide
RC.1H.50.02 ® RC.1H.51.02 10-2000
Software version 2.0x
Monitoring unit
AKL 111A
ADAP-KOOL
®
Menu operation via AKA 21
2 Menu operation RC.1H.51.02 © Danfoss 10/2000 AKL 111A Version 2.0x
System survey
A refrigerating plant fitted with ADAP-KOOL
®
refrigeration controls will mostly consist of several
controllers or monitoring units, where each controller will regulate its own refrigeration
appliance/cold room.
The system has been designed in such a way that contact can be made to each and every
controller via a data communication system. One specific controller is selected, and it will now
be possible to make settings and readouts for this unit.
The individual monitoring units type AKL 111A can be
operated in two ways:
1. With control panel type AKA 21.
Use this document when operation takes place in this
way.
2. With PC and system software type AKM. Use another
document with literature number RC.1H.6.
Operation
Validity
This menu operation (dated October 2000), applies to AKL 111A with the code number
084B6039 fitted with software version 2.0x.
AKL 111A Version 2.0x Menu operation RC.1H.51.02 © Danfoss 10/2000 3
All controllers that are connected to the same network can be operated with the control panel.
There may be as many as 125 controllers, and they are shown in groups of 16 on the display.
A system is shown here which consists of more than 16 controllers. The meaning of the letters
is, as follows:
A: AKC or AKL controller
E: Controller with active ERROR (on addresses 2, 11 and 12 in this example)
g: Gateway (to addresses 13 and 14 in this example)
G: Gateway with connected printer
: A blank field indicates that there is no unit with this address.
Select the unit that is to be operated by using the “+/On” or “-/Off” key, and push “Enter”. In this
example you select the controller with address 4.
If the system comprises more than 16 units or units with an address code higher than 16, you
may change to the next group by pushing "®".
When a controller has been selected, you can make settings in it. This setting is performed, as
follows:
Shown in the upper right corner of the display is the setting with which the controller is
operating. Below that value a new setting may be made. Use the three keys “+/ON”, “-/OFF”
and “Digit” for setting the new value. This new value will not govern the regulation until you
push the key “Enter”.
Select a controller
Settings of a controller
5
-50 to +50 5
ON
OFF / ON ON
The functions in the controller can be protected by means of an access code. Depending on
the settings to be made, you may gain access in one of the following ways:
User input: Gives access to:
1. Push F1 Display of alarms
2. Push F2 Readout of actual values
3. Code 1 and then F1 Acknowledgement of alarms
Code 1 and then F3 Setting of selected parameters
4. Code 2 Operation of all settings of the entire menu system
(with system software type AKM there is access to
additional functions).
Pages 6 and 7 contain a description of how you gain access to the system via a code.
Access to a controller
1 < 1 > 16
AEAAAAAAAAEEgg A
1 < 4 > 16
AEAAAAAAAAEEgg A
17 < 17 > 32
AAA
4 Menu operation RC.1H.51.02 © Danfoss 10/2000 AKL 111A Version 2.0x
A supporting text is attached to the individual functions. When such a function is shown in the
control panel’s display, the supporting text can be obtained by pushing the key “Help”. The
supporting text is intended as a help to users who no longer use these operating instructions.
In the menus shown below functions with supporting texts are identified with the word “Help”
next to the function.
When an error appears in a system, it can be seen on the control panel’s display which will
show an “E”. If the control panel shows a text from a selected controller, the LED at the word
“Alarm” will flash.
When an error has occurred, first select the controller on which the error is registered. When
the controller has been found, push “F1”, and the error message will appear.
At the end of the document there is a list of all the error messages and a description of how to
acknowledge an alarm.
1 < 2 > 16
AEAAAAAAAAAAgg A
AKL 111A Adr: 2
E Mon-11:27
Standby Mode
When one controller has been selected from the total system, the following display will
appear (the display is the first one shown when you have selected an address from the total
system):
e.g.
AKL 111A Adr: 2
E Mon-11:27
From this position you can freely choose between several forms of operating levels:
1. Display of alarms - push “F1”
2. Display and setting of a few selected functions - push “F2”
3. Display and setting of several selected functions - push “F3”
The function may be protected with a code (code 1)
4. Display and setting of all allowed functions in the controller. The function may be protected
with a code (code 2).
Operation of the individual levels is shown below:
When you push “F1” the alarm messages from the controller in question appear. Only active
alarms are shown. With a push on "¯" you can see whether there are more alarm messages,
and if so, their texts.
When an alarm has been localised and corrected, the alarm is acknowledged (removed from
the system, so that it no longer appears). In large systems where a gateway is also connected
this acknowledgement will take place automatically. In other systems it has to be done
manually, cf. end of the document.
Prior to the acknowledgement of the alarm, the keying of a code is required, see page 6.
Leave the F1 function by pushing "¬".
Supporting text
How to localise an error
Functions of a controller
1. F1
AKL 111A Version 2.0x Menu operation RC.1H.51.02 © Danfoss 10/2000 5
When you push “F2” a number of functions will appear where it is possible to read values.
You can move to and from the individual functions by pushing "" or "¯".
__1_ Signals for inputs 1 to 8 are shown here:
- If a temperature signal is registered, the value will be indicated in °C (e.g. S1°C 10)
(any set off-set will be included in the display)
- If a contact signal is monitored, the value will be shown with
ON or OFF (e.g. DI1 ON)
ON = no alarm
OFF = alarm upon expiry of time delay
(If an input is not used, it will not be shown)
|
|
|
|
|
|
|
__8_
|
DI 21 State Status of digital inputs DI 21 to DI 24
- ON = no alarm or defrost in progress (230 V on the input)
- OFF = alarm upon expiry of time delay
(If an input is not used, it will not be shown)
|
|
|
DI 24 State
|
Alarm Reset Status of input for acknowledgement of alarm
ON = acknowledgement (230 V on the input)
|
AKA 14 Show Signal from the switch determining the signal to be shown on the AKA 14 display
1= input 1
2= input 2 etc.
The switch can only make the display show the mentioned inputs, if the unit has been
set for it, cf. 3:01:01
Leave the F2 function by pushing "¬".
2. F2
6 Menu operation RC.1H.51.02 © Danfoss 10/2000 AKL 111A Version 2.0x
When you push F3, a number of functions will appear which are used when the system is
serviced.
If access code is used (code 1), key it as follows:
- Push the key
- Enter the code by using the three keys +, - and Digit (the code is mentioned later
as code 1, and the factory setting is 40. If code 2 has been set at 0, access code 1
cannot be used).
- Push Enter
- Push F3
Move to and from the individual functions by pushing "" or "¯".
On page 3 you can see how a setting is changed.
DI21 State Status of input
ON = input energised
|
DI21 Count Counter registering the number of changes from OFF to ON on the input
|
DI21 Hours Counter adding up the number of hours the input has been ON
|
DI21 Reset Resetting of the two counters (the counters are reset by changing OFF to ON, after
ON OFF which the setting will automatically return to OFF)
22 The same displays can be seen for the other three inputs
23
24
Main Switch Function switch: 1: Regulation
-1 / 0 / 1 0: Controller stopped
2:02:01 -1: Service function
Leave the function by pushing "¬".
3. F3
AKL 111A Version 2.0x Menu operation RC.1H.51.02 © Danfoss 10/2000 7
4. Access to all
functions
The access to the functions may be protected with a code (code 2).
If access code is used, key it as follows:
- Push the key
- Enter the code by using the three keys +, - and Digit
- Push Enter
- Push "¬"
Move to and from the individual functions by pushing the four arrow keys.
On page 3 you can see how a setting is changed.
When you wish to leave the Access to all functions function, push Clear and then "¬".
List of functions on level 1:
1. Controllers access picture and access to system information
2. Switch and selection of language
3. Configuration of low voltage digital inputs
4. Configuration of high voltage digital inputs
5. Power Meters
6. Forced-control functions for service
Below and on the following pages the individual functions are shown together with a brief
description:
Level 1 Level 2 Level 3 Description
AKL 111A Adr: xxx Controller access display
Mon hh:mm If the code function is used, continue by pushing the "key" key.
Enter Code Entry of access code 1 or access code 2 (cf. also 1:07 and 1:08).
0 - 255 0 Continue by pushing "arrow left"
1:01
AKL 111A Adr: xxx Acces to system information
Mon hh:mm If an E appears in the display, an error has been registered
1
Code No. Reading of the controllers code number and software version
Prog.Ver.
1:02
|
Clock: Setting of controller clock (AKC clock)
MON-00:00
1:03
Clock: Day Setting of day (1 = Monday, 7 = Sunday)
(Mon)1 (Sun)7
1:03:01
|
Clock: Hou
r
Setting of hours
0 23
1:03:02
|
Clock: Min. Setting of minutes
0 59
1:03:03
|
System Address Reading of the controllers system address
Addr. yyy xxx yyy = network No. and xxx = address
1:04 The system address can only be set via PC
|
Alarm report to Reading of the alarm address (end receiver) the alarms are to be sent to
Addr. yyy xxx The alarm address can only be set via PC
1:05
8 Menu operation RC.1H.51.02 © Danfoss 10/2000 AKL 111A Version 2.0x
|
Gateway Address Reading of address of nearest gateway which has to effect alarms
125 The address can only be set via PC
1:06
|
Chg. Code1 Change of code 1. The code gives access to acknowledgement of active
0 255 alarm by means of the F1 key.
1:07 Also access to the selected settings/readouts via the F3 key.
| (Factory setting = 40) (See also code 2)
Chg. Code2 Change of code 2. The code gives access to the whole menu system.
0 255 (Factory setting = 0. Setting = 0 offers free access where neither
1:08 code 1 not code 2 is required)
|
Main Function Main functions
2
Alarm message When there is an alarm, an E appears in the display
(Error register becomes visible)
2:01
For survey of alarm messages, see page 12
2:01:01
|
Main Function Access to function switch
Settings
2:02
Main Switch Function switch: 1: Regulation
-1 / 0 / 1 0: Controller stopped
Help 2:02:01 -1: Service function
|
Language Selection of language:
0 - 6 0: English 3: Danish 6: Swedish
Help 2:02:02 1: German 4: Spanish
2: French 5: Italian
NB! This function must be set prior to any uploading to system
software type AKM.
When the language code has been changed, push "ENTER"
and then "Clear".
|
M0 to M8 Configuration of low voltage digital inputs used for:
Configuration - display selection
3 - sensor input or ON/OFF registration
Display Set measurement to be shown on the external display type AKA 14
Configuration
3:01
AKA 14 Sel. The following can be defined:
0 - 8 0: Determined with this setting is the display of a switch connected to terminals
Help 3:01:01 88-89. (But if one of the subsequent settings is selected, it will override
this switch setting)
1: Display of signal at input 1 (S1/DI1) terminals 90-91
2: Display of signal at input 2 (S2/DI2) terminals 92-93
-
-
8: Display of signal at input 8 (S8/DI8) terminals 106-107
|
M1 Configuration Set signal to be received at input 1 (S1/DI1) terminals 90-91
3:02
M1 °C /DI The input is defined with the following setting:
0 - 2 0: Input not used
Help 3:02:01 1: Signal received from a temperature sensor
2: Signal received from a contact function
AKL 111A Version 2.0x Menu operation RC.1H.51.02 © Danfoss 10/2000 9
1:| | If temperature sensor (at 3:02:01) has been selected
| S1 Hi. Al Upper alarm limit
| -100 140
| 3:02:02
| |
| S1 Lo. Al Lower alarm limit
| -100 140
| 3:02:03
| |
| S1 / DI Link If change to another time delay for the alarm during defrost is required,
| -0 4 set the high voltage input here that will deliver the defrost signal:
Help 3:02:04 0: No change of time delay
| 1: Signal received by DI 21
| 2: Signal received by DI 22
| 3: Signal received by DI 23
| 4: Signal received by DI 24
| |
| M1 Al Suppr If alarms from a signal input have to be suppressed when the refrigeration
| 0 4 appliance is switched off, the setting must be done in this menu. Here you set
Help 3:02:05 which high voltage input is to supply the signal indicating that the refrigeration
appliance has been switched off.
| 0: Normal operation with alarm
| 1: Signal received by DI 21
| 2: Signal received by DI 22
| 3: Signal received by DI 23
| 4: Signal received by DI 24
| |
| S1 Corr. Offset adjustment of temperature signal received at the input
| -10 10
| 3:02:06
| |
| Dest. 1 Alarm definition:
| 0 3 0: No activity (no alarm function)
| 3:02:07 1: Relay output + relay output on master gateway must draw
| + as a message on DANBUSS
| 2: As a message on DANBUSS
| 3: Relay output must draw + as a message on DANBUSS
| |
| Delay 1 Time delay for the alarm in minutes
| 0 600
| 3:02:08
| |
| S1 Def.Del Overridden time delay for the alarm when the input has been connected to a
| 0 600 defrost registration with the setting at 3:02:04
| 3:02:09 (time is set in minutes)
2:| If contact function (at 3:02:01) has been selected
| Open input registered as OFF (= alarm)
| Short-circuited input registered as ON (= no alarm)
|
| Dest. 1 Alarm definition
| 0 3 0: No activity (no alarm function)
| 3:02:02 1: Relay output + relay output on master gateway must draw
| + as a message on DANBUSS
| 2: As a message on DANBUSS
| 3: Relay output must draw + as a message on DANBUSS
| |
| M1 Al Suppr. If alarms from a signal input have to be suppressed when the refrigeration
| 0 4 appliance is switched off, the setting must be done in this menu. Here you set
Help 3:02:03 which high voltage input is to supply the signal indicating that the refrigeration
appliance has been switched off.
| 0: Normal operation with alarm
| 1: Signal received by DI 21
| 2: Signal received by DI 22
| 3: Signal received by DI 23
| 4: Signal received by DI 24
10 Menu operation RC.1H.51.02 © Danfoss 10/2000 AKL 111A Version 2.0x
| |
| Delay 1 Time delay for the alarm
| 0 600
| 3:02:04
|
M2 Configuration The same setting options apply to inputs 2 to 8 (S2/DI2 to S8/DI8)
3:03
|
|
|
M8 Configuration
3:09
|
DI 21 to DI 24 Configuration of high voltage digital inputs that can be used for alarm input or for
Configuration registration of a defrost in progress
4
DI 21 Input DI 21
Configuration
4:01
DI 21 Select The input is defined with the following settings:
0 1 0: Input not used
4:01:01 1: Input used as alarm input (230 V = OK. 0 V = alarm)
1: Input used for registration of time of defrost
(
230 V = defrost, 0 V = no defrost
)
1: The input is used for suppression of alarms
(230 V = alarm option, 0 V = no alarms)
(If the input has been defined for Defrost signal (3:02:04) or
alarm suppression (3:02:05) the setting in this menu will
be overwritten by 1.)
|
DI 21 Dest Alarm definition
0 3 0: No activity (no alarm function)
4:01:02 1: Relay output + relay output on master gateway must draw
+ as a message on DANBUSS
2: As a message on DANBUSS
3: Rela
y
output must draw + as a messa
g
e on DANBUSS
(If the input is connected to a temperature input, the setting will
automatically return to 0. Cf. 3:02:04)
|
DI 21 Delay Time delay for alarm
0 600 (If the input is connected to a temperature input, the setting will
4:01:03 automatically return to 0. Cf. 3:02:04)
|
DI 22 The same setting options apply to inputs DI 22, DI 23 and DI 24
Configuration
4:02
|
|
DI 24
Configuration
4:04
AKL 111A Version 2.0x Menu operation RC.1H.51.02 © Danfoss 10/2000 11
|
Power meters Energy measuements functions
5
Measurements Measurements
5:01
A PulseCnt Pulse counter A
5:01:01 (Can be zeroset with 5:2:1 and 5:2:3)
|
B PulseCnt Pulse counter B
5:01:02 (Can be zeroset with 5:2:2 and 5:2:4)
|
Aconsm kWh Energy measurement counter A
5:01:03 (Can be zeroset with 5:2:1 and 5:2:3)
|
Bconsm kWh Energy measurement counter B
5:01:04 (Can be zeroset with 5:2:2 and 5:2:4)
|
A Load kW Load measurement counter A (averaged over the period LoadPer.m 5:2:7)
5:01:05
|
B Load kW Load measurement counter B (averaged over the period LoadPer.m 5:2:7)
5:01:06
|
A y Day kWh Energy consumption during past 24 hours
5:01:07 (from 00.00 to 24.00 hrs)
|
B y Day kWh Energy consumption during past 24 hours
5:01:08 (from 00.00 to 24.00 hrs)
|
AlWeek kWh Energy consumption during past whole week
5:01:09 (from Monday 00.00 hrs to Sunday 24.00 hrs)
|
BlWeek kWh Energy consumption during past whole week
5:01:10 (from Monday 00.00 hrs to Sunday 24.00 hrs)
Settings Settings
5:02
A ResetCnt If you select pos. ON, pulse counter A and energy measurement A will be zeroset
OFF ON (5:01:01 and 5:01:03 = 0)
5:02:01
|
B ResetCnt If you select pos. ON, pulse counter B and energy measurement B will be zeroset
OFF ON (5:01:02 and 5:01:04 = 0)
5:02:02
|
A puls/kWh Set number of impulses corresponding to one kWh (counter A)
1 1000
5:02:03
|
B puls/kWh Set number of impulses corresponding to one kWh (counter B)
1 1000
5:02:04
|
A Offset kWh Displacement of energy measurement counter A
0 9999 (display in "5:01:03" is displaced with this setting)
5:02:05
|
B Offset kWh Displacement of energy measurement counter B
0 9999 (display in "5:01:04" is displaced with this setting)
5:02:06
|
LoadPer. m Updating period for the Load measurement displays
1 60 If the setting in the next function Load Func is put in pos. ON,
5:02:07 the updating period will be overwritten by the period registered on input CT2
|
LoadFunc. Definition of counter function
OFF ON OFF: Both counter circuits are used. The updating period LoadPer.m(5:02:07 )
5:02:08 must be set.
ON: One counter circuit is used. The updating period is received on the CT2 input.
12 Menu operation RC.1H.51.02 © Danfoss 10/2000 AKL 111A Version 2.0x
AC-RDT
|
Service Mode Service function
6
Alarm message When there is an alarm, an E appears in the display
(Error register becomes visible)
6:01
For survey of alarm messages, see page 12
6:01:01
|
Manual Control Forced control of output (service)
and Measurement (Reading of the input signal values can be arranged via the F2 key)
6:02
Man. Ctrl. ON: Manual setting permitted (cf. 2:02:01)
OFF ON
6:02:01
|
Alarm Relay Forced control of alarm output
OFF ON ON = relay switch cut in = no alarm
6:02:02 OFF = alarm
|
Alarm Relay Reading of alarm relays actual position
6:02:03 ON = relay switch cut in = no alarm
OFF = alarm
Alarm message
The following display read-outs are only visible if there is an active error.
When the error is corrected, the alarm message can be removed by pressing ENTER.
Alarm message Cause Remedy
Sx Error Faulty Sx sensor Check sensor connection/sensor resistance
Standby Mode Regulation has The function switch (Main switch) is set in the position "Service" (see 2:02:01)
stopped
High Air Temp Sx Too high temperature Check the function monitored by the input
from Sx input
Low Air Temp Sx Too low temperature Check the function monitored by the input
from Sx input
DI x Alarm Alarm from x input Check the function monitored by the input
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Danfoss Monitoring unit type AKL 111A. Vers. 2.0x. AKA 21 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI