Wolf WRS-K Configuration manual

Type
Configuration manual
Conguration wizard
WRS-K
WOLF GMBH / POSTFACH 1380 / D-84048 MAINBURG / TEL. +49(0) 87 51 74- 0 / FAX +49(0)87 51 74- 16 00 / www.WOLF.eu
Part no.: 3062933_201707
Subject to technical modications
GB
2
3062933_201707
Contents
Contents ................................................................................................................... 2
Installation / commissioning / operating overview .................................................... 3
Post-conguration, air quality / CO
2
sensor .............................................................. 4
Post-conguration remote control............................................................................. 5
Post-conguration, LON / BacNet / ModBus / Ethernet / KNX interface .................. 6
Post-conguration, pressure control / ow rate control / cooling function ................ 7
New conguration controller ..................................................................................... 8
System conguration .............................................................................................. 12
Conguration for pressure or ow rate control ....................................................... 15
Notes ...................................................................................................................... 19
3
3062933_201707
1 Displaying and acknowledging active fault messages
2 Displaying the system operating data (set / actual values)
3 Access to the main menu
4 Forward scrolling within a menu and increasing values
5 Switching the system ON and OFF, selecting menu points, conrming inputs
6 Backwards scrolling within a menu and reducing values
1. Commissioning
- According to EN 50110-1, only qualied electricians may carry out the installation and commissioning of
the ventilation control unit and connected accessories.
- Observe all regulations stipulated by your local power supply utility and all VDE or local regulations.
- DIN VDE 0100 regulations regarding the installation of high voltage systems up to 1000 V.
- DIN VDE 0105-100 operation of electrical systems.
- Only original Wolf accessories may be used (electric heater bank, condensate pump, servomotors, etc.),
otherwise, Wolf cannot provide a warranty.
Installation / commissioning /
operating overview
1
2
3
4
5
6
Operating overview
4
3062933_201707
2. When retrotting an air quality sensor (mixed gas or VOC, CO
2
) follow the instructions below.
Post-conguration, air quality / CO
2
sensor
Conguration Activation
Other
Air quality sensor
No
Using ↑ ↓ select "Air quality sensor"
and press Enter to activate re-
conguration.
Select "Yes" with and conrm with
Enter
Other
Air quality sensor
available? >Yes
U08 KLM-M/L
Type 0-10V
Version VOC
Use Enter to conrm the input port
"U8" and type "0-10 V"
Use to select the variant "VOC" or
"CO2"
FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENUS
ON/OFF
SET VALUE
Press
EscEsc
button
Select 1234 with
and conrm with
Enter
wolf-heiztechnik.de
Contractor
Password: 1234
Continue with
Select "Heating contractor" with and
conrm with Enter
Main menus
Standard settings
Displays
Time functions
Contractor
DISPLAYSSELECTIONEsc BACK
Alarm management
Service
Other
Contractor - menus
DISPLAYSELECTIONEsc BACK
Select "Other" with and conrm with
Enter
DISPLAYSELECTIONEsc BACK
DISPLAYSAVEEsc BACK
5
3062933_201707
Post-conguration remote control
Backup mode
Night ventilation
Other
Contractor - menus
DISPLAYSELECTIONEsc BACK
Select "Other" with and conrm with
Enter
Select "Remote control" with and
conrm with
DISPLAYSELECTIONEsc BACK
Other...
Remote control
installed? No
Select "Yes" with and conrm with
Enter
DISPLAYSELECTIONEsc BACK
Other...
Remote control
installed? Yes
Switch power supply to control unit OFF
and ON again
The remote control is enabled
Conguration
Restart system
(mains OFF/ON)
System restart
FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENUS
ON/OFF
SET VALUE
Press
EscEsc
button
Select 1234 with
and conrm with
Enter
wolf-heiztechnik.de
Contractor
Password: 1234
Continue with
3. Proceed as follows to re-congure a remote control
Select "Heating contractor" with and
conrm with Enter
Main menus
Displays
Time functions
Contractor
DISPLAYSSELECTIONEsc BACK
6
3062933_201707
FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENUS
ON/OFF
SET VALUE
Press
EscEsc
button
Main menus
Standard settings
Displays
Time functions
Contractor
DISPLAY
SELECTION
Esc BACK
Select "Heating contractor" with and
conrm with Enter
Select 1234 with and conrm with
Enter
Contractor
Password: 1234
Continue with
wolf-heiztechnik.de
4. Proceed as follows for the re-conguration of a LON / BacNet / Modbus / Ethernet / KNX
interface.
Post-conguration, LON / BacNet /
Modbus / Ethernet / KNX interface
Conrm with
Other...
BMS protocol
>LON-Works
Transfer speed
>4800 (RS485/RS422)
BMS address: 001
VALUESAVEEsc CANCEL
Select required connection with
- No proto
- pCO Manager
- LON-Works
- Bac-Net
- Modbus Stave Standard
- Ethernet
- KNX
and conrm with Enter
Other...
Protocol type:
BacNet
VALUESAVEEsc CANCEL
BMS protocol has been set
Hold down
EscEsc
button until you jump to
the standard screen
Select "Other" with
and conrm with
Enter
Alarm management
Service
OtherNight ventilation
Limits
Contractor - menus
DISPLAYSELECTIONEsc BACK
7
3062933_201707
Post-conguration, pressure control /
ow rate control / cooling function
FR
20.03.09
11:02
21.0
11.4°C 18.5°C
PRG OPERATING DATA
Esc MENU
ON/OFF
SET VALUE
5. A new conguration of the control unit must be performed in the rst step for the
re-conguration of a pressure/volume ow control unit or a cooling function.
Please note: The complete system conguration will be deleted and must be re-entered.
Displays
Time functions
Contractor
Step 1
Press
EscEsc
button
Alarm management
Service
Other
Night ventilation
Limits
Contractor - menus
DISPLAYSELECTIONEsc BACK
Select "Other" with and conrm with
Enter
Conrm with
DISPLAYSELECTIONEsc BACK
Other...
Remote control
installed? No
Select "Yes" with and conrm with
Enter
DISPLAYSELECTIONEsc BACK
Other...
Remote control
installed? Yes
Select 1234 with and conrm with
Enter
wolf-heiztechnik.de
Contractor
Password: 1234
Continue with
Select "Heating contractor" with and
conrm with Enter
Main menus
DISPLAYSSELECTIONEsc BACK
8
3062933_201707
Select language:
German, English, French, Dutch, Italian,
Spanish, Portuguese, Hungarian,
Swedish, Danish, Russian, Czech, Slovak,
Slovenian, Polish, Latvian, Lithuanian
Conguration
German
DISPLAYSELECTIONEsc BACK
Please select
language
6. To make an individual control adjustment, you must go through the whole system
conguration process.
Operation (selection) is carried out with
the arrow keys , the selected function
is conrmed with Enter , and then the
next menu is opened automatically.
You can return to a menu with
EscEsc
to
change incorrect settings.
VALUESAVEEsc CANCEL
Conguration
System conguration in preparation
Please wait...
The settings shown under Step 2 must be entered
according to whether pressure control or ow rate
control is selected.
The following selection is possible via
arrow keys:
Ventilation air system
Vent./extr. air system
Conrm selected system type with Enter
VALUESAVEEsc CANCEL
Conguration
System type:
Please select
Factory setting Customer setting
Vent./extr. air system
Select fan speed:
Single stage
Two-stage
Three-stage
Variable
Pressure control
Flow rate control
VALUE
SAVEEsc CANCEL
Conguration
Fan:
Please select
Factory setting Customer setting
Variable
New conguration control unit
9
3062933_201707
Select cooling mode:
No cooling
Cold water pump bank
Direct evap. stage 1
Direct evap. stage 2
Heat pump
Heat pump (Stulz)*
VALUESAVEEsc CANCEL
Conguration
Cooling:
Please select
Factory setting Customer setting
No cooling
Select air dampers:
No air dampers installed
Mixer air dampers
Mixer/vent/ex.air dmpr
Outs./dis. air dampers
vent/ex.air dmpr
Outs./ex.air dmpr
Open/close dampers
CRL damper system*
VALUESAVEEsc CANCEL
Air dampers
Please select
Factory setting Customer setting
Outs./dis. air dampers
New conguration control unit
Select heating mode:
No heating
DHW pump bank
El heater bank stage 1
El heater bank stage 2
El heater bank stage 3
El heater bank stage 4
El heater bank stage 5
El heater bank var.
KGWO
Heat pump
Heat pump (Stulz)*
VALUESAVEEsc CANCEL
Conguration
Heating:
Please select
Factory setting Customer setting
Electric heater bank
variable
DHW pump bank
Depending on
order
Conguration
10
3062933_201707
Select temperature control:
Vent. air control
Room vent. air cascade
Ext./vent. air cascade
VALUESAVEEsc CANCEL
Conguration
Control type:
Please select
Factory setting Customer setting
Ext./vent. air cascade
Select re dampers:
No FD available
1 re damper
VALUE
SAVEEsc CANCEL
Conguration
Number FD:
Please select
Factory setting Customer setting
1 re damper
Select lters:
No lter Vent./extr. air lter
Outside air lter Outside/extr. air tr
Ventilation air lter
Outs./vent/ex. air lter
Extract air lter
Outs./vent. air lter
VALUESAVEEsc CANCEL
Conguration
Filter:
Please select
Factory setting Customer setting
Outside/extr. air tr
New conguration control unit
Select heat recovery system:
No HR available
PHE
RHE
Coil loop without feed
Coil loop + heat feed
Coil loop + cold feed
Coil loop + heat/cold feed
VALUESAVEEsc CANCEL
Conguration
HR:
Please select
Factory setting Customer setting
CKL / CFL PHE
CRL RHE
11
3062933_201707
Select external systems, demand:
None available
Remote start/stop
Remote step control
Remote ON/OFF + stages
VALUE
SAVEEsc CANCEL
Conguration
Ext. demand:
Please select
Factory setting Customer setting
Remote ON/OFF + stages
New conguration control unit
12
3062933_201707
System conguration
Select remote control:
None available
Set value transducer
Remote control
VALUE
SAVEEsc CANCEL
Conguration
Remote control
Please select
Factory setting Customer setting
None available
Select adiabatic cooling:
No adiabatic cooling
Freshwater contact humidier
Recirculating contact humidier
High pressure humidier
Adiabatic cooling
Factory setting Customer setting
No adiabatic cooling
VALUE
SAVEEsc CANCEL
Factory setting Customer setting
None available
VALUE
SAVEEsc CANCEL
Conguration
Please select
Select humidication:
Not available
Isotherm
Adiabatic
Humidif.
Please select
Conguration
13
3062933_201707
The selected conguration is then
displayed in the overview
Changes cannot be made
Continue with Enter
Pre-conguration complete
Select building management system:
No BMS available
pCO Manager
BacNet
LON Works
Nadbus
Ethernet
KNX
VALUE
SAVEEsc CANCEL
Conguration
BMS:
Please select
Factory setting Customer setting
No BMS available
Conguration
Select reheating:
No reheating
DHW pump bank
El heater bank stage 1
El heater bank stage 2
El heater bank stage 3
El heater bank stage 4
El heater bank stage 5
El heater bank, variable
Reheating
Factory setting Customer setting
No reheating
VALUE
SAVEEsc CANCEL
Please select
Conguration
System conguration
14
3062933_201707
Continue with
Continue with Enter
Vent./ex. air syst. w/
Variable speed fan
DHW pump bank
No cooling bank
Outs./dis. air dampers
Continue with
Continue with Enter
Heat recovery PHE
Ext./vent. air cascade
Outside/extr. air tr
1 re damper
Remote start/stop
Continue with
Continue with Enter
Remote control
No BMS available
Conguration complete.
Switch off control unit and switch on again
The conguration is saved.
System restart
Restart
system
(mains OFF/ON)
Overview of the preset conguration
Conguration
Conguration
Conguration
Conguration
System conguration
15
3062933_201707
Conguration for pressure or ow rate control
The following settings should be made on site for pressure control.
Selecting the number of pressure sensors
Standard screen →
EscEsc
→ Select heating contractor → Enter password 1234 → Select pressure/ow rate
(If only one sensor is selected, the differential of the extract fan can be entered on the next screen: overpressure, 0 - −50 %;
underpressure 0 - +50 %.)
Factory setting Customer setting
Number 2
Range 1000
DISPLAYSELECTIONEsc BACK
Pressure/ow rate ctl
Diff. pressure sensor
Number -2-
Type 0/10 V
Range 0/1000 Pa
Factory setting Customer setting
00.0 %
DISPLAYSELECTIONEsc BACK
Pressure/ow rate ctl
Diff. extract fan
00.0 %
The following settings for ow rate control have to be carried out on site:
Select fan type and k-factor
Supply fan
Number 1
k-factor: 0
Fan type: 1
Diff. extract fan
Number: 1
k-factor: 0
Fan type: 1
The selection formula for the corresponding fan type and the k-factor are indicated on the fan.
Select fan type 1 for formula
Select fan type 2 for formula
.
Step 2
DISPLAYSELECTIONEsc BACK
Pressure/ow rate ctl
DISPLAYSELECTIONEsc BACK
Pressure/ow rate ctl
Factory setting Customer setting
Number 1
k-factor 0
Fan type 1
Factory setting Customer setting
Number 1
k-factor 0
Fan type 1
16
3062933_201707
Enter set values for automatic mode
Standard screen →
EscEsc
→ Select time functions → Set values → Select pressure control, supply air → Enter values → Select
pressure control, extract air → Enter values
Factory setting Customer setting
750 Pa
500 Pa
250 Pa
100 Pa
Set values, time program
Pressure control,
ventilation air
DISPLAY
SELECTION
Esc BACK
00000 Pa
00000 Pa
00000 Pa
00000 Pa
Set values, time program
Pressure control,
extract air
DISPLAYS
SELECTIONEsc BACK
00000 Pa
00000 Pa
00000 Pa
00000 Pa
Factory setting Customer setting
750 Pa
500 Pa
250 Pa
100 Pa
Select "Pressure control, ventilation air" → Enter value
Select "Pressure control, extract air" → Enter value
Hold down
EscEsc
until you jump to the standard screen
Factory setting Customer setting
1500 m³/h
1000 m³/h
750 m³/h
500 m³/h
or
Factory setting Customer setting
1500 m³/h
1000 m³/h
750 m³/h
500 m³/h
or
Step 3
Conguration for pressure or ow rate control
17
3062933_201707
Set value for backup mode, heating/cooling
Setting night ventilation and peak ventilation
Standard screen →
EscEsc
→ Select heating contractor → Enter password 1234 → Select backup mode →
Select heating pressure → Enter value
Select "Cooling pressure" → Enter value →
EscEsc
Select "Night ventilation" → Fan pressure → Enter value →
EscEsc
Select "Peak ventilation" → Fan, ventilation air/extract air → Enter value
Factory setting Customer setting
250 Pa
DISPLAYSELECTIONEsc BACK
Backup mode
Heating
Pressure
0000 Pa
Factory setting Customer setting
250 Pa
DISPLAYSELECTIONEsc BACK
Backup mode
Cooling
Pressure
0000 Pa
Factory setting Customer setting
250 Pa
DISPLAY
SELECTION
Esc BACK
Night ventilation
Fan pressure
0000 Pa
Factory setting Customer setting
250 Pa
DISPLAYSELECTIONEsc BACK
Peak ventilation
Fan
Ventilation air 0000 Pa
Extract air 0000 Pa
Hold down
EscEsc
until you jump to the standard screen
1000 m³/h
or
1000 m³/h
or
1000 m³/h
or
1000 m³/h
or
Step 4
Conguration for pressure or ow rate control
18
3062933_201707
Entering a set value for manual mode
Standard screen →
EscEsc
→ Standard settings → Select vent. air fan pressure, manual mode → Set value
Select "Extr. air fan pressure, manual mode" → Set value
DISPLAYSELECTIONEsc BACK
Vent. air fan pressure, set value for
manual mode
Standard setting
000.0 Pa
DISPLAYSELECTIONEsc BACK
Vent. air pressure for external
demand
Stage 3: 0 Pa
Stage 2: 0 Pa
Stage 1: 0 Pa
Standard setting
Select "Vent. air pressure for external demand" → Set value
DISPLAYSELECTIONEsc BACK
Extr. air fan pressure, set value for
manual mode
Standard setting
000.0 Pa
Select "Extr. air pressure for external demand" → Set value
Factory setting Customer setting
100 Pa
1000 m³/h
or
Factory setting Customer setting
100 Pa
1000 m³/h
or
Factory setting Customer setting
300 Pa
200 Pa
100 Pa
2000 m³/h
1500 m³/h
1000 m³/h
or
DISPLAYSELECTIONEsc BACK
Extr. air pressure for external
demand
Stage 3: 0 Pa
Stage 2: 0 Pa
Stage 1: 0 Pa
Standard setting
Hold down
EscEsc
until you jump to the standard screen
Factory setting Customer setting
300 Pa
200 Pa
100 Pa
2000 m³/h
1500 m³/h
1000 m³/h
or
Step 5
Conguration for pressure or ow rate control
19
3062933_201707
Notes
WOLF GmbH
Postfach 1380 · D-84048 Mainburg · Tel. +49-(0)8751/74-0 · Fax +49-(0)8751/741600
Internet: www.wolf.eu
3062933_201707 Subject to technical modications
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Wolf WRS-K Configuration manual

Type
Configuration manual