DECODERS
12
−−−−
sec.4
DIGIVOICE - Technical Manual
TECHNICAL SPECIFICATIONS
Intake in terms of unitary load: 2LU
Power voltage +V, 0V: 16 ÷ 25, 2Vdc
Working temperature range: -5°C + 45°C
T, RES outputs:
Maximum applicable voltage: 30Vdc
Maximum intake current: 10mA
Typical output resistance: 100Ohm
Toggle relay time: 0-59’59” (0 =500ms)
Automatic reading of terminal L:
400ms after relay implementation control
Relay contact: 30Vdc 5A
250Vac 5A
Dimensions (W x H x P): 142 x 108 x 38mm
OPERATION
The various possible applications of the special decoder are described
below.
A. RELAY ENERGISING FOLLOWING EVENT IN THE SYSTEM
The special decoder is capable of storing two events. In the case
of toggle relay conguration, the relay is energised whenever
one of the two events occurs. In the case of bistable relay
conguration,therelaywillbeenergisedbytherststoredevent
and de-energised for the second stored event. A special code for
querying the status of the terminal L from the call module, the
switchboard or the special intercom can be stored in the decoder.
The following special events can be stored:
1) Apartment station door opener button pressed.
2) Priority door opener from switchboard.
3) Switchboard to apartment station call button pressed or special
intercom to apartment station call button pressed.
4) Apartment station auto-on button pressed.
5) Call from calling module, switchboard, or special intercom to a
user in the system.
6) Entry of special code from calling module, switchboard or
special intercom. In the latter case, terminal L can be read
automatically to provide immediate feedback on the operation
carried out.
B. RELAY ENERGISING AND DE-ENERGISING FOLLOWING
PRESSING OF PC AND PR BUTTONS
The special decoder can energise and de-energise the relay
following pressing on the PC and PR buttons. Pressing the PC
button will also generate a call to the switchboard. Pressing the
PR button will also delete this call from the switchboard memory.
The “hospital call” function can consequently be carried out in two
different ways:
1) System with loudspeaker door phones, special decoders and
switchboard: a special decoder is arranged in each room and
a loudspeaker intercom is provided for each patient. Patients
calling the switchboard from the loudspeaker intercom and
special decoder will energise the relay to which a calling light
can be connected. The nurse on duty will enter the room and
operate a key switch connected to the PR terminal of the
special decoder which silences the call and deletes any other
calls from the same room (up to 16) from the switchboard.
2) System with special decoders and switchboard: a special
decoder is arranged in each room and a button is provided
for each patient. Patients calling the switchboard by pressing
the button connected to the special decoder PC terminal will
energise the relay to which a calling light can be connected
and send a call to the switchboard at the same time. The
nurse on duty will enter the room and operate a key switch
connected to the PR terminal of the special decoder which
silences the call and deletes the call from the room on the
switchboard.
NOTE: in the case, the call on the switchboard is signalled by
repeated tones and by a “!” symbol next to the code
associated to the special decoder.
SPECIAL DECODER Ref. 1038/80
TECHNICAL SPECIFICATIONS - OPERATION - INSTALLATION - CONFIGURATION AND PROGRAMMING
SPECIAL DECODER
C. VIDEO SWITCH 1038/69 CONTROL FOR SURVEILLANCE
CAMERA AUTO-ON
This function can be carried out by the special decoder in addition
to the function 1 or 2 described above. The special decoder
associated to a call module in the system will control the signals
T and RES in a suitable fashion. The user can press the auto-on
button on the calling module intercom and see the module camera.
The button can be pressed repeatedly to see all the cameras
connected to the 1038/69 in sequence.
NOTE: this function is also available with special intercom 1138/18
in version 2.0 or higher.
INSTALLATION
The special decoder presents four holes for wall fastening by means
of 6mm diameter bolts (not provided).
Thedecodercanbewallttedwiththewireseitherembeddedornot.
Important: In both cases, the relay will directly control the high voltage
loads. The wires connected to the relay terminal boards must pass in
separate channel with respect to the rest of the system.
The connection to the system is obtained by means of removable
terminal boards.
The connection of the electrical load to be controlled is made by means
of xed terminal boards protected by a plastic cover. The terminal
boards lead to two reciprocally isolated contacts with the following
names:
• NA: Normally open relay contact
• NC: Normally closed relay contact
• C: Common relay contact
Connect buttons without potential to the terminal boards PC/0V, PR/0V,
because these inputs are not isolated from the intercom system. The
contact of a switch or a relay without potential must be connected to
the L/0V terminal board because this input is not isolated from the
intercom system.
CONFIGURATION AND PROGRAMMING
Thespecialdecodermustbeconguredbymeansoftheprogramming
terminal Ref. 1038/56 version 2.0 or higher to dene the operating
parametersandprogrammedtodenetheeventsenergisingtherelay.
Carefullyllinthememolabel(7)onthecoverprotectingtheelectronic
components. This will facilitate maintenance interventions.
WALL
FRAME
DUCT + WIRES
DUCT + WIRES
COVER
WALL
FRAME
COVER
Ref. 1038/80