FläktGroup DC_9201GB 20180403_R0 Specifications are subject to alteration without notice
The cable between the terminal box of the motor and the separate
frequency inverter must be shielded. A safety isolating switch must
be installed between the mains supply and the frequency inverter.
Install the safety isolating switch near the inspection door of the fan.
Before beginning work on the fan, isolate the power supply by
switching off the safety isolating switch.
The LQLK plenum fan can be supplied with an external, factory-fit-
ted frequency inverter, wired to the terminal box of the motor with
a shielded cable. A prefitted safety isolating switch prewired to the
frequency inverter is also available as an accessory.
The LQLK plenum fan can also be supplied with a factory-fitted
shielded cable run to an external shielded terminal box.
MEASURES BEFORE STARTING
The fan must not be started with the damper on the suction or deliv-
ery side closed. However the fan motor may be briefly
energized with the inspection door open for checking that the direc-
tion of impeller rotation is correct.
Check before starting the fan that the impeller rotates freely and
that no objects, which can be drawn in and damage the fan, have
been left in the installation.
If the fan is equipped with steel spring anti-vibration mountings,
the transport locking devices must be removed before starting the
fan.
xxx xxxx xxxxxx xxx
xxxx xxxxxxxx xx
xxx xxxx xxxxx
xxx xxxx xxxxxx
xxxx xxxxxxxx xx
xxx xxxxx xxxxx
xxx xxxx xxxxxx
xxx xxxx xxxxxxx
xxx xxxx xxxxxxx
MAX frequency
Electric wiring must be carried out by a
qualified electrician.
Important!
Isolate the power supply and wait until the im-
peller has stopped rotating (approx. 1 minute)
before inspecting and servicing the fan.
There may be designs of duct systems that
causes wind milling which prevents the impel-
ler from being stopped. The wind milling must
then be prevented;
1) turn off the power to the fan
2) close the dampers.
INSTALLATION OF SEPARATELY SUPPLIED
FREQUENCY INVERTER
The frequency inverter and motor shall be installed by a qual-
ified electrician with adequate knowledge on how to install
speed-controlled drive systems (frequency inverters) and EMC
safety.
The following recommendations shall be regarded as a
com-plement to the manufacturer’s installation instructions. If
the content of the instructions differ, the instructions furnished
by the manufacturer shall have priority over those stated
below, to enable compliance with the guarantee liability terms
of the manufacturer of the equipment.
GENERAL
A continuous, shielded 4-wire cable designed for EMC installa-
tion to motorized drives should be installed between the motor
and the frequency inverter. The optical density of the cable shield
shall be at least 80 %, e.g. NCY or Olflex Classic. The shield must
be in 360 º contact with the casing both in the motor and in the
frequency inverter in order to achieve maximal surface contact.
It is not advisable to install a safety isolating switch or junction
boxes between the frequency inverter and the motor.
FREQUENCY INVERTER
The shielded cable must be led either through an EMC approved
cable gland in the casing of the frequency inverter or through a
cap intended for this purpose.
The shielded cable must not be connected to an earth screw.
Warning!
FIf the frequency inverter is not installed
correctly, this may damage the motor bearings.
FläktGroup’s policy stipulates that we agree
to accept guarantee liability only if the motor
and frequency inverter have been supplied
and installed by us.
Guarantee liability will not be accepted by
Fläkt Group if the motor has been connected/
wired to a frequency inverter by another fitter,
i.e. one who is not employed by or commis-sio-
ned by FläktGroup.
Note!
The frequency converter have been optimized
for the duty point. The power could thus be
lower than the motors rated power.