Installation and maintenance instructions
3
FläktGroup DC_10402GB 20230203_R2 Specifications are subject to alteration without notice
MEASURES BEFORE STARTING
The fan must not be started with the damper on the suction or delivery
side closed. However the fan motor may be briefly
energized with the inspection door open for checking that the direction
of impeller rotation is correct.
Check before starting the fan that the impeller rotates freely and that
no objects, which can be drawn in and damage the fan, have been left
in the installation.
The manometer reading, Δp, which is the difference between the
pressure in the suction chamber by the fan inlet and the pressure
inside the inlet cone, can be read with a manometer (pressure
range of up to 6000 Pa) which should be connected with a 4 mm
dia. tube to 2 externally located pressure tappings. The value of the
constant k is specified in the table below.
A flow indicator with built-in pressure transducer STAZ-23, STBZ-
23 (available as an accessory) should be connected by means of
tubes to the external pressure tappings. This instrument converts the
mano-meter pressure reading to a flow (m3/s) which is shown on a
display screen and transmits a 0–10 V output signal, linear with the
flow.
Important!
For EQLZ-42 U-tube manometers, use only the
blue manometer fluid supplied with the instrument.
Never use any other type of fluid. Precision-adjust
the zero point with the zero adjustment screw.
1
2
3
1
2
3
brown
white
blue
green/yellow
PE PE
PE
2
1331
2
PE
Male Female
24V
10V
D1
E1
DC Out
DC Out
GND
Digital In
Analog In
A (D+)
B (D-)
ID1
ID2
GND
PORT 1 PORT 2
Adressing
Adressing
GND
MODBUS
(RS-485)
A (D+)
B (D-)
MODBUS
(RS-485)
NC
max. AC
250V / 2A
12
CO
11
NO
14
K1
L1 L2 L3
Note: Port1 or port2 can be used.
GND Ref
A (D+) A+
B (D-) B-
Modbus connection
D1 (start signal) GND
E1 Analog In Ctrl signal (0-10V)
0-10V
K1 Relay
During operation Relay energized
Failure Relay de-energized
Motor 1
Port 1 Port 2
Motor 2
Port 1 Port 2
M12 Cable
"In case of two fans, connect M12 cable from port2 in motor1 to port1 in motor2."
AIRFLOW MEASUREMENT
The EQLC has equipment for measuring the airflow.
The airflow, q, can be measured by applying a manometer
reading of Δp (Pa), and a constant, k, using the following formula:
NB!
In the case of air handling units supplied with a
control system, the pressure tappings in the end
connection panels of the unit are not connected to
the airflow sensor of the fan.
If you still want to read the manometer pres-
sure with an external manometer, you can connect
the tubes from the airflow sensor of the fan across
T-nipples to the pressure tap-pings in the end
connection panel of the air handling unit.
If this external means of measuring flow will not
be permanent, the tubes must be restored to their
original condition.
If the air handling unit is supplied with a control system, the flow
can be read directly in the control panel display.
q = 1 · Δp
k m3/s