DANLERS CESRA PIR Installation guide

Type
Installation guide
Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1andBSEN55015.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.a10ampcircuitbreakerandvoltagesurgeprotection.
Pleaseensurethatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Ceiling Surface PIR absence switch (round)
CESRA PIR
DANLERSceilingsurfacepassiveinfra-redabsenceswitch(CESRAPIR)
canbemounteddirectlyontosolidceilingsorontoarangeofdifferent
mounting boxes.TheCESRAPIRincorporatesapassiveinfra-redquad
sensortodetectmovementofawarmbodywithinitsdetectionzone
(diagramA)andaphotocelltomonitortheambientlightlevel.
Whenenteringtheroom,iftheambientlightisdarkenough,thelights
canbeactivatedbypressingamomentarylightswitchforlessthan2
seconds. The ambient threshold can be set by the user to between
approximately 30 lux and innite lux (photocell inactive) via the LUX
adjuster(diagram B). Ifno moremovement isdetected withina pre-
selectedtime,thentheCESRAPIRwillswitchtheloadoff.Thistime
lagcanbe set viatheTIME adjusterto10seconds, 20seconds,40
seconds,80seconds,2m30s,5m,10m,20mor40minutes(diagramB).
Pressingandholdingthemomentaryswitch(for2secondsormore)
(whileCESRAPIRisinitsONstate)willoveridethecontrolenabling
theloadto beswitchedOFF.Thisisusefulwhena darkenedroom
isrequiredoriftheuserdoesnotwishthetimelagperiodtoelapse.
Allow a minimum of 1 second to elapse after the lights have gone off before
repressing the momentary switch (allowing CESRA PIR to reset).
Loading
Theswitchshouldonlybeconnectedtoa230V50HzACsupply.
ThesePIRswitchescanswitchupto:
6amps(1500W)ofresistiveloads.
6amps(1500W)ofuorescentloads.
3amps(750W)ofelectronicandwirewoundtransformerloads.
2amps(500W)ofCFL,2Dlamps,LEDDriversandLEDlamps
andttings.
1amp(250W)offans
Minimumload2Wresistive,suitableformostenergysavinglamps,
LEDsandemergencyttings.
15/12/15 INS227 CESRA PIR
Troubleshooting
The load will not switch on when the momentary switch is operated:
• TheLUXadjusterissettoolowandisinhibitingtheswitch.
The Absence detector switches off when the room is occupied:
• Theoccupationisoutsideofthedetectionzone(seediagramA),
movementsaretoosmallortooinfrequent.IncreasetheTIMEadjuster.
Momentary switches
DANLERScansupplyarangeofMomentary/Retractiveswitches-
push to make or break:
MOMSWMP-PlatedgreymetalnishwithPRESSpreprintedonswitch.
MOMSWM-Platedgreymetalnishwithblankswitch.
MOMSWWHP-PlatedwhitenishwithPRESSpreprintedonswitch
MOMSWWH-Platedwhitenishwithblankswitch.
MOMSWPMOD-GridmodulesuitableforMKGridPluswithPRESS
preprintedonswitch.
MOMSWMOD-GridmodulesuitableforMKGridPluswithblankswitch.
Installation procedure
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
2.
POSITIONING:TheCESRAPIRshouldbeinstalledtoachievecorrect
coverageofthearea,seediagramA.
Ifthephotocelloverridefacility
isrequired,theswitchmustbelocatedaboveanareawheredaylight
cangivegreaterilluminationthanthearticiallight.Avoidlocatingthis
productwhereitisexposedtowindyordraftyconditions(exposed
lobbies,open ceilingvoids ornear ventilationfans) ornear heat
sources.TocoverlargeareasCESRAPIRsshouldbespacedina
5metregridformation.
3.
ThegreatestenergysavingswillbemadeifeachCESRAPIRcontrols
anindependentsetoflamps.Theycanbewiredinparallelbutthis
should ideally be limited to three, see diagram D.
4.Makesurethepowerisisolatedfromthecircuit.
TheCESRAPIRshouldbeconnectedasshownindiagramsC&D:
L-Livein.N-Neutralin.SW1-Switchinput.SL-SwitchedLineout.
5.Knockoutordrilltheappropriateholesonthemountingplatefor
attachingtheplatetotheceilingorbackbox(ifapplicable).Feed
cablesthroughtheappropriate(sideorrear)entryhole.Screwthe
backmountingplatetotheceilingorbackboxviathemounting
holes. Wire the cables into the sensor head block terminal. Push
the sensor head onto the mounting plate and align the side clips
withtheslotsonthesensorheads.
Start-up mode
WhentheCESRAPIRispoweredup,itwillswitchontheloadfor1
minute,theloadwillthenswitchoffandtheCESRAPIRwillenterits
OperatingMode.
Time and Lux set-up
Forconvenience,ensurethattheTIMEissettotheminimumwhen
settinguptheLUXlevel.AfterwardssettheTIMEtoavaluesuitable
fortheapplication,makingreferencetodiagramB.
TheLUXisbestsetupwhenthelocalambientlightisatapproximately
theminimumdesiredworkinglightlevel.WiththeLUXsetfullyclockwise
waitfortheCESRAPIRtoswitchoff.SteptheLUXadjusterslowly
anticlockwise(- to+), at each position operate the momentarywall
switchandcontinuinguntilthelampsswitchon.
L
N
load
A few
CESRA PIR
230 VAC
L
N
load
CESRA PIR
Single CESRA PIR
230 VAC
A few CESRA PIR wired in parallel
Wiring diagrams
Mains rated
retractive wall
switch
L
L
SW1
SL
Mains rated
retractive wall
switch
L
N
SL
SW1
Typical settings
TIME
min max
LUX
max min
30 LUX
1000 LUX
PHOTOCELL
INACTIVE
40m
20m
10m
5m
2.5m
80s
10s
20s
40s
up to 5m
up to 7m
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
For optimum coverage
recommended mounting
height: 2.4 to 5m
L
N
load
A few
CESRA PIR
230 VAC
L
N
load
CESRA PIR
Single CESRA PIR
230 VAC
A few CESRA PIR wired in parallel
Wiring diagrams
Mains rated
retractive wall
switch
L
L
SW
1
SL
Mains rated
retractive wall
switch
L
N
SL
SW
1
A: Detection diagram
D: Wiring diagram, multiple Absence Detectors
B: Adjusting time and lux C: Wiring diagram, single Absence Detector
  • Page 1 1
  • Page 2 2