BC-HM VI.74.D2.02 © Danfoss 11/96 9
j) Setting reduced temperature level
If reduced temperature is required the
time switch channels of the respective
circuits are to be set in P8.4.
Factory setting:
Circuit 1: no time control
Circuit 2: no time control
Reduced temperature level can be set at
a fixed value (1 - 8) or at an outdoor
temperature-dependent value (AUTO).
When a room temperature sensor is
connected both circuit 1 (P9.2) and circuit
2 (P9.3) can be selected for reduced
temperature operation. When the setting
is 0 the temperature will not be reduced.
Factory setting of reduced temperature
setting is 5. Each scale graduation
corresponds to about 1 room
temperature degree. In setting >|< , the
potentiometer is overridden to 5.
Reduced temperature
Reduced room temperatures appear from
above figure. Different settings are given
(–2, –4, –6, –8, and AUTO). The figure
shows that the room temperature
reduction is cancelled at outdoor
temperatures -15 °C. This value can be
changed in P1.3 within the range –29 °C
to +10 °C.
h) Hot water service temperature
setting or parallel displacement of
heat curve in circuit 2
Hot water service temperature setting
Hot water service temperature can be
set with potentiometer h) when hot water
service function is selected with
potentiometer i)
Setting range is 30-110 °C.
Mid-setting corresponds to 70 °C.
Factory setting is 50 °C.
Note:
hot water service temperature can
be read in P4.1.
Parallel displacement
When circuit 2 controls heating system,
flow temperature can be increased or
reduced (parallel displacement) with
potentiometer h). The potentiometer
must be turned towards + (clockwise) if
temperature is too low.
Heat curve slope affects magnitude of
parallel displacement. See "Temperature
setting". Setting range is ±8.
i) Hot water service function or setting
heat curve slope in circuit 2
Hot water service function
Hot water service function can be
selected by turning potentiometer fully
counterclockwise, to hot water service
symbol . This cuts out weather
compensation.
Heat curve slope
When circuit 2 is used for heating system
control, heat curve slope can be set
within range 0.4 - 3.4. Heat curve is
factory-set at 1.8, but can be overridden
with potentiometer e) in setting >|< to
1.8.