6 VI.73.L1.02 Danfoss 6/92 BC-HSP
Control settings
User settings
a) Program clock (analog or digital)
b) Display
c) Temperature setting
d) Function switch
e) User instructions
a) Program clock
The program clockis must be set in the
required normal and reduced
temperature periods by pushing riders for
reduced temperature setting towards the
center of the clock.
b) Display
On turning the switch concealed behind
the cover plate, the display will show the
operating condition and system
temperature (see function testing and
installer settings).
c) Temperature setting
The function of this knob depends on the
setting in P8.4 (see section on digital
settings). Selection can be made
between weather compensation and
adaptive reference room control in P8.4.
Weather compensation
The flow temperature in both boiler
circuit and mixing circuit can be
increased and decreased (parallel-
displaced) by turning the knob. Turning
towards +8 increases the flow
temperature.
Since the parallel displacement depends
on the slope of the heat curve, the
change can be different in the two
heating circuits.
With ESMR/F connected, the flow
temperature is reduced when the set
max. room temperature is exceeded.
The value is factory-set at 22 °C, but can
be changed in P5.2 (see digital settings).
The amplification factor can be changed
in P9.2.
Adaptive reference room control
The heat curve is automatically adapted
to the heat requirement. The room
temperature can be increased or
decreased with knob d).
The knob must be turned towards +8 if
the room temperature is too low. The
room temperature setting range is
factory-set at 22 ±8°C. The knob mid-
point can be set in P5.2 (see digital
settings).
The amplification factor can be changed
in P9.2.
d) Function switch
/ Burner and circulation pumps
stopped and valve in mixing circuit
closed, but with system frost-
protected. Hot water service heating
still possible with ECL 3550.
Time program overridden and
constant control in accordance with
reduced temperature.
Automatic changeover between
normal and reduced temperature as
set on clock.
Time program overridden and
constant control in accordance with
normal temperature.
Manual operation
Burner and all circulation pumps
constantly cut in. All control
functions off and burner controlled
exclusively by boiler thermostat.
Valve can be controlled manually.
>|< Heating system regulated in
accordance with preset values. All
installer settings (under cover plate)
overridden. Preset values are given
in the section “Installer settings” in
the column marked >|<.
The best heating economy can be
achieved at the lowest possible flow
temperature and by using radiator
thermostats.