4 VI.73.T1.02 4/93 BC-HM
Tip out and remove the control cover
plate with a screw driver and another 3
functions are accessible.
Installer settings
d) Max. boiler temperature
Potentiometer for max. boiler
temperature setting at hot water service
demand. When set max. temperature is
exceeded, burner is cut-out.
Setting range 70 - 90°C
Ex factory setting 80°C
e) Pump re-run
Time set pump re-run transferring
excess heat to hot water tank to avoid
boiler overheating after hot water service
demand. After re-run circulating pump is
cut in again.
Setting range: 30 sec. to 10 min.
Note: Re-run time settings influence
circulating pump re-run, as circulating-
pump re-run setting is always double as
high as adjustable hot water pump re-
run setting.
Ex factory re-run is set to 4 min.
f) Hot water service priority control
Ex factory ECL 3050 is set for hot water
service priority-control. At hot water
service demand the circulating pump is
cut-out and the hot-water pump is cut-in.
Priority control can be cancelled by
pushing the miniswitch downwards.
Then circulating pump will not cut-out at
hot water service demand and system
temperature will follow boiler
temperature.
Boiler difference between cut in and cut
out is fixed at approx. 6 K.
Programming
Set arrow opposite actual day (7-day
clock only) and time. Set reduced-
temperature time in pushing riders
towards the center of the clock dial.
Analog clock
Analog clock is additional equipment for
reduced hot water service temperature
control and can be ordered at your
distributor.
Mounting
Dismount blank cover and mount analog
clock
Sensor test
Boiler and hot water service temperature
sensors can be tested by measuring the
ohmic value at a certain temperature
10°C .....................................23414 Ohm
20°C .....................................14881 Ohm
30°C .......................................9745 Ohm
40°C .......................................6556 Ohm
50°C .......................................4520 Ohm
60°C .......................................3187 Ohm
70°C .......................................2293 Ohm
80°C .......................................1681 Ohm