Danfoss ECL Comfort 300 - C25 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 300 - C25 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Before you start
How to use this guide
This guide is divided into two parts:
• Daily Use (Turn the guide over)
Yellow sections 01 - 09
• Installation and maintenance:
Grey sections 10 and onwards
Save energy - save money - improve your comfort
temperature
The ECL Comfort controller is designed by Danfoss for
temperature control of heating systems.
The ECL Comfort controller ensures you of the following;
Room and hot water temperatures will be adjusted to
your personal settings.
Lower temperatures and lower energy consumption
reduce costs and ensure optimum use of energy
resources.
The automatic pump motion program protects the
circulation pump against blocking.
Sketch an outline of your heating system
The ECL Comfort controller is designed for a wide range of
heating systems with different configurations and
capacities.
If your heating system differs from the diagrams shown in
section 10, you may want to sketch an outline of the system
about to be installed. This makes it easier to use the
Installer’s Guide, which will guide you step-by-step
from installation to the final adjustments before the end-
user takes over.
Note! The controller is pre-programmed with factory
settings which are shown in the relevant sections of this
guide.
VI.7C.I2.02
Identifying the system type
10
In this section you find the most frequently used systems. If
your system is not quite as shown below, find the diagram
which has the best resemblance to your system and make
your own combinations.
Heating system type 1
Line 51 Water pump / diverting valve
Setting
OFF
Heating system type 2
Line 51 Water pump / diverting valve
Setting
ON
Heating system type 3
Note!
The system diagrams in this instruction are principal drawings
and do not contain all the components which are necessary in
heating systems.
Installation
Installation
Mounting the ECL Comfort
controller
11
For easy access, you should mount the ECL Comfort
controller near the heating unit. Select one of the three
following methods:
Mounting on a wall
Mounting on a DIN rail
Mounting in a panel
Screws and rawlplugs are not supplied.
Mounting in a panel
Connector set: Order code No. 087B1148.
The panel plate thickness must not exceed 3 mm.
Prepare a cut-out with the dimensions 92 x 138 mm. Pull off
the right side of the lid by means of a screwdriver.
Insert the controller into the panel cut-out and fix it with the
two locks which are placed diagonally in two corners of the
controller.
Mounting on a DIN rail
Mounting kit: Order code No. 087B1145.
A mounting kit is necessary to mount the box with the
controller on a DIN rail.
Mounting on a wall
Socket for mounting on wall: Order code No. 087B1149.
Mount the terminal box on a wall with a smooth surface.
Establish the electrical connections and position the
controller in the box. Secure the controller with the fixing
screw.
Installation
Installation
Connecting the sensors
Establish the jumper from 16 to common terminal
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Connecting the 230 V a.c. units
12
Electrical connections -
230 V a.c.
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m.
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted in each screw
terminal.
Jumper from 1 to 10
Jumper from 10 to 12
Jumper from 12 to 14
Jumper from 2 to common N-terminal
Establish these jumpers:
Installation
Installation
Terminal Description Max. load
1 L Voltage supply 230 V a.c.
2 N Voltage supply 230 V a.c.
9 P1 Circulation pump for boiler 4(2)A 230 V a.c.
10 230 V a.c. supply for
pump relay R1
11 P2 Circulation pump/diverting
valve for hot water 4(2)A 230 V a.c.
12 230 V a.c. supply for
pump relay R2
13 P3 Burner 4(2)A 230 V a.c.
14 230 V a.c. supply for
burner relay R3
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESMT
18 and 16 Room sensor (S2)
circuit I ESMR
20 and 16 Return sensor (S4) ESMU/ESMA/ESMC
21 and 16 Boiler sensor (S5) ESMU/ESMB/ESMA
22 and 16 Hot water sensor
(S6) circuit II ESMU/ESMB
Terminal Description Type (recommended)
Connecting the sensors
Establish the jumper from 16 to common terminal.
Cable cross section for sensor connections: Min. 0.4 mm
2
Total cable length: Max. 50 m (sensors and bus).
NOTE! Cable lengths above 100 m may cause noise sensibility
(EMC).
Connecting the 24 V a.c. and 230 Va.c. units
13
Electrical connections -
24 V a.c.
Jumper from 1 to 10
Jumper from 10 to 12
Jumper from 12 to 14
Jumper from 2 to common N-terminal
Establish these jumpers:
Cable cross section for voltage conductor: 0.75 - 1.5 mm
2
Cable length: Max. 50 m.
Electrical connections
Max. 2 x 1.5 mm
2
cables can be inserted in each screw
terminal.
Installation
Installation
Terminal Description Max. load
1 L Voltage supply 24 V a.c.
2 N Voltage supply 24 V a.c.
9 K1 Circulation pump for boiler 4(2)A 230 V a.c.
10 24 V a.c. supply for
pump relay R1
11 K2 Circulation pump/diverting
valve for hot water 4(2)A 230 V a.c.
12 24 V a.c. supply for
pump relay R2
13 K3 Burner 4(2)A 230 V a.c.
14 24 V a.c. supply for
burner relay R3
15 and 16 System device bus
17 and 16 Outdoor sensor (S1) ESMT
18 and 16 Room sensor (S2)
circuit I ESMR
20 and 16 Return sensor (S4) ESMU/ESMA/ESMC
21 and 16 Boiler sensor (S5) ESMU/ESMB/ESMA
22 and 16 Hot water sensor
(S6) circuit II ESMU/ESMB
Terminal Description Type (recommended)
14
Placing the temperature
sensors
It is important that the sensors are mounted in the
correct position in your heating system. Special attention
should be paid to the following sensors:
Room temperature sensor
(ESMR, ECA 60 and 61 remote control)
Place the room sensor in the room where the temperature
is to be controlled. Do not place it on outside walls nor
close to radiators, windows or doors.
Boiler sensor
(ESMU, ESMA or ESMC types)
Place the sensor according to the boiler manufacturers
specification.
Do not move the sensor after it has been fastened in
order to avoid damage to the sensor element.
Return temperature sensor
(ESMU, ESMA or ESMC types)
The return sensor should always be placed in/on a pipe
with return water flow.
Hot water temperature sensor
(ESMU or ESMB types)
Place the hot water sensor according to the
manufacturers specification.
Outdoor temperature sensor
(ESMT type)
The outdoor sensor should be mounted on that side of the
building where it is less likely to be exposed to direct
sunshine. It should not be placed close to doors, windows
or air outlets.
Installation
Installation
15
Inserting the ECL Card
How to insert your ECL Card the first time
After the power has been switched on, open the lid on the
front side of the controller.
Place the ECL Card with the yellow side facing you. This
enables the controller to read the ECL Card data. The
controller immediately starts to copy the factory settings
and the heating system type from the ECL Card. After
copying, the display will show the heating system type the
controller is set up to control. After approx. 10 sec. the dis-
play will change to display line C.
The controller is now ready to be set to control your
heating system.
Desired room
temperature
Line
Circuit
Time
C
C99
Y
0
P
C52
01 01
1
8
0 3 6 9 12 15 18 21 24
1
91
3
5
C
3
Outdoor
temperature
Understanding the ECL Card
The ECL Card contains factory settings for a standard
heating system. If the actual heating system differs from
the standard system, the controller must be adjusted
accordingly. After the adjustment, the new settings should
be stored on the ECL Card.
For ECL Card copying and daily use including
adjustment of temperatures and time periods, insert the
ECL Card with the yellow side facing you.
For system set-up adjustments, the grey side of the ECL
Card - the installers side - must be facing you.
As a main rule, the ECL Card should always remain in
the controller during service, maintenance and settings.
If the card is removed please note that:
The controller settings are locked after approx. 10 min.
The ECL Card must not be exposed to direct heat or
sunshine
If several controllers are installed in the heating system
you can write a title on the ECL Card with a permanent
ink pen.
Installation
Installation
17
Setting the time and date -
Line A
In case of a power failure which lasts longer than 12
hours, the time and date have to be set again.
All other settings are stored as programmed.
The grey side of the ECL Card.
Go to line A.
09
01
5609
5
A
3
1
Actual time
Month, day
Year
Use the shift button to switch between minutes,
hours, year, month and day.
Set the correct time and date.
Use the yellow side of the ECL Card to enter the day
plan settings.
See the Users Guide, section 4.
16
Adjusting the ECL Card
settings
Update of the ECL Card after maintenance and service
All new settings can be stored on the ECL Card. For details
about copying see section 34. Insert the ECL Card with the
yellow side facing you.
When the copying is finished display line C will appear.
You can make other changes in the day plan, set time
and date or change settings
(see Users Guide).
C
C99
Y
0
P
8
0 3 6 9 12 15 18 21 24
1
91
3
5
C
3
When the controller is connected and operating you will be
able to check and adjust maybe all or some of the basic
settings on the grey side of the ECL Card, if necessary.
General principles
Use the arrow buttons to move from line to line
on the ECL Card, for example to line 2:
Line
Settings to
be adjusted
Value in
range indicator
09
2
04
1
ON
ON
1
ON
Circuit
Use the minus/plus buttons to adjust the
settings.
In some displays more than one setting or value
can be adjusted. Use the shift button to switch
between the possibilities.
The circuit selector shifts between circuit I and II.
You can adjust all settings and service param-
eters individually in both circuits.
Go to line 9 (bottom line).
Accept to copy as indicated. No other keys are
active.
Basic set-up
Basic set-up
19
Manual control - Line B
The grey side of the ECL Card.
Go to line B
Shift to manual mode .
Select the unit you want to control. The
selected unit symbol is flashing.
Burner and pumps are switched on
or off when the relevant button is pressed.
1
ON
ON
Monitoring temperatures and
system units - Line B
18
Go to line B.
When the burner and the circulation pump are operating, it
is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display
will indicate it as
- -.
If the sensor is short-circuited, the display will indicate it as
- - - .
If in doubt, remove the controller and check the ohmic
value between the relevant terminals.
The grey side of the ECL Card.
5 036
B
1
ON
ON
1
ON
Controlled
units
Return
temperature
Flow
temperature
State
indicator
Relationship between temperature and ohmic value
-10°C 961 Ohm
0°C 1000 Ohm
10°C 1039 Ohm
20°C 1078 Ohm
30°C 1117 Ohm
40°C 1156 Ohm
50°C 1195 Ohm
60°C 1234 Ohm
70°C 1273 Ohm
-50
800
900
1000
1100
1200
1300
1400
1500
1600
-25 0 25 50 75 100 125 150
Temperature
Ohm
Push the shift button to see:
- the calculated flow temperature
- the return temperature set points
5 036
B
1
ON
ON
1
ON
Controlled
units
Controller
mode
Shift away from manual mode.
Basic set-up
Basic set-up
-20 -10 0 10 20-30
10
20
30
40
50
60
70
80
90
1,8
1,2
0,6
0,2
2,2
C
C
Circuit Setting range Typical setting
Slope
Circuit Setting range Typical setting
I -9 ... +9 0
Parallel displacement
I 0.2 ... 3.4 1.0
Floor heating systems
This controller is factory set for radiator systems, which are
typically high flow temperature systems.
To control floor heating systems, which are typically low flow
temperature systems, you need to change the heat curve
according to your type of system.
Setting the heat curve - Line C
20
Circuit Setting range Factory setting
I 0.2 ... 3.4 1.8
Slope
Circuit Setting range Factory setting
I -9... +9 0
Parallel displacement
The grey side of the ECL Card.
Go to line C.
The symbol for the slope of the heat curve
will flash.
8
C
1
0
1
ON
ON
1
ON
Displacement
Slope
Adjust the slope of the heat curve, if required.
If you want to adjust the parallel displacement
of the heat curve, push the shift button. The
symbol for the parallel displacement will flash.
Make your adjustment.
Basic set-up
Basic set-up
Flow temperature limits -
Line 2
22
Circuit Setting range Factory setting
I 10 ... 110 °C min. 40 °C / max. 90 °C
2 Boiler temperature min.-, max. limits
The grey side of the ECL Card.
The left end of the range indicator flashes.
Adjust the min. limit of your heating system.
Select the max. limit. The right end of the range
indicator flashes.
Adjust the max. limit.
Max. flow
temperature
Temperature
range for flow
temperature
09
2
04
1
ON
ON
1
ON
Min. flow
temperature
Go to line 2.
Heating cut out - Line 1
21
8
1
1
1
ON
ON
2
ON
Circuit Setting range Factory setting
I 10 ... 30 °C 18 °C
1 Limit for heating cut-out
The grey side of the ECL Card.
Go to line 1.
Set the outdoor temperature limit at which you
want the heating system to stop.
This function can save energy by stopping the heating
system when the outdoor temperature gets above a set limit.
The heating system is activated again when the actual
outdoor and the accumulated temperatures get below the set
limit.
The accumulated Tout symbolises the heat stored in the
building.
18°C
Temp
Actual T
out
Accumulated T
out
Time
Heating Heating off Heating
Basic set-up
Basic set-up
Room temperature
influence - Line 3
23
The grey side of the ECL Card.
+
÷
0
1
1
ON
2
0-4
3
3
ON
The room sensor in the reference room registers
the difference between the desired and the ac-
tual room temperature. The flow temperature ref-
erence will be corrected to eliminate this differ-
ence.
B: Reference room control
Used if your heating system is not equipped with radiator
thermostats and you select the room with room sensor as a
temperature reference for the rest of the rooms.
(However, should you have a few radiator thermostats
installed, make sure that they are fully open).
Set a positive value for min. influence and a
negative value for max. influence.
+
÷
set
Influence
Min. limitation
Max. limitation
T
ROOM
This section is only relevant if you have installed a room
sensor. There are two basic principles for control of the
room temperature influence:
The max. influence determines how much the
room temperature should influence the flow
temperature.
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a
max. limitation of the room temperature. The controller will
allow for free heat gains, i.e. solar radiation or heat from a
fire place, etc.
Go to line 3.
Select the max. influence.
The bar below the range indicator flashes in the
right side of the display.
Adjust the max. influence.
T
ROOM
set
Influence
Max. limitation
Circuit Setting range Factory setting
I 0 ... 99/-99 ... 0 min. 0 max. -40
3 Room temperature influence
Min.
influence
Max.
influence
Example
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to -40.
The influence at min. limitation (left corner of the display) is
set to 0.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x -40 x 0.1 x H = -14.4 degrees.
Example
The actual room temperature is 2 degrees too low.
The influence at max. limitation (right corner of the display) is
set to 20.
The influence at min. limitation(left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x 20 x 0.1 x H = 7.2 degrees.
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to -35.
The influence at min. limitation(left corner of the display) is set
to 20.
Heat curve H is 1.8.
Result:
The flow temperature reference is changed by
2 x (-35) x 0.1 x H = -12.6 degrees.
Basic set-up
Basic set-up
Boiler control - Line 4
24
The burner is switched on and off to maintain the
desired mean boiler temperature. Set the difference
between cut-in and cut-out temperature.
4
OFF
1
ON
ON
1
ON
Circuit Setting range Factory setting
I OFF/1 ... 50 OFF
4 Boiler temperature difference
The grey side of the ECL Card.
Go to line 4.
OFF: The boiler temperature difference is set
automatically according to the momentary load
of the boiler and the temperature conditions in
the heating system.
1...50: The boiler temperature difference is set
manually to a fixed value according to the boiler
manufactorers specification.
Basic set-up
Basic set-up
Set the difference between the cut-in and the cut-out
temperature for the hot water service.
The grey side of the ECL Card.
Select circuit II.
Go to line 2.
Charging temperature difference
Hot water difference
Charging temperature
Desired hot water temperature
Set the hot water temperature difference.
Hot water controller -
Line 1-2
27
Example:
Desired hot water temperature 60 °C
Hot water temperature difference 15 K
Charging temperature
(60+15=) 75 °C
Set the difference between the charging temperature
and the desired hot water service temperature.
Circuit Setting range Factory setting
II 1 ... 30 K 15 K
1 Charging temperature difference
5
1
1
1
ON
ON
1
ON
Note! A too high charging temperature might cause deposits
in the heat exchanger
The grey side of the ECL Card.
Select circuit II.
Go to line 1.
Set the difference. Set a high value if you want
the hot water system to reach the desired
temperature in a short period of time.
Circuit Setting range Factory setting
II 1 ... 30 K 6 K
2 Hot water temperature difference
Basic set-up
Basic set-up
Adapting the ECL Comfort controller to the heating
system
29
Check list
Turn the ECL Card so that the grey side faces
you.
Set the time and the date (Line A)
See section 17.
Check all settings on the grey side of the
ECL Card
See sections 20 to 27.
To ensure that you have the correct settings refer to
section 10 for examples of different heating systems.
If your heating system differes from the diagram shown on
the overleaf of the cover, you should check and
perhaps alter the following service parameters in
circuit II:
Line
51 Water pump/diverting valve
29
Check list
Is the ECL Comfort controller ready for use?
Make sure that the power supply is connected to
terminals 1 (Live) and 2 (Neutral).
See section 12 or 13.
Check that burner and pumps are connected to
the correct terminals.
See section 12 or 13.
Check that all sensors are connected to the
correct terminals.
Mount the controller, and switch on the power.
Insert the ECL Card with the yellow side facing
you and push
, if necessary.
See section 15.
Select manual operation in the controller mode.
See section 2
in the Users Guide.
Check that the burner and the pumps start
and stop when operated manually.
See section 19.
Check that the temperatures shown in display
A and B match the actual sensors, both for
circuit I (heating) and circuit II (hot water).
See section 1
in the Users Guide.
Control & overviews
Control & overviews
ECL Card settings
(circuit II: Hot water service)
30
Setting range Factory setting Your settings
See sections 16 & 17
See sections 18 & 19
1
Charging temperature difference
1 ... 30 K 15 K
The difference between desired tank
temperature and charging temperature,
see section 27.
2
Hot water temperature difference
1 ... 30 K 6 K
The difference between cut-in temperature
and cut-out temperature during hot water
charging, see section 27.
A Time and date
B System information
C
ECL Card settings
(circuit I: Heating)
30
Heat curve - Slope
0.2 ... 3.4 1.8
Set the slope of the heat curve,
see section 20.
Heat curve -Parallel displacement
-9 ... +9 0K
Set the parallel displacement of the heat
curve, see section 20.
1
Limit for heating cut-out
10 ... 30 °C 18 °C
Saves energy by stopping the heating
system when the outdoor temperature gets
above a certain limit, see section 21.
2
Boiler temperature min.-/max. limits
10 ... 110 °C min. 40, max. 90 °C
The limits of the min. - and max. flow
temperature, see section 22.
3
Room temperature influence
0 ... +99 / -99 ... 0 min. 0, max. -40
The room temperatures influence on the
flow temperature control, see section 23.
4
Boiler temperature difference
OFF/1 ... 50 OFF
Set the difference beteween cut-in and
cut-out temperature, see section 24.
A Time and date
B System information
C Heat curve
Setting range Factory setting Your settings
See sections 16 & 17
See sections 18 & 19
See section 20
Control & overviews
Control & overviews
circuit
II
Service parameters
31
Circuit II (Hot water service)
Line Setting range Factory setting Your setting
min
40 Charging pump - postrun
0 ... 9 min 1
51 Charging pump/diverting valve
ON/OFF ON
circuit
Service parameters
31
10 Choice of time control unit
0 ... 5 0
11 Reduced temperature dependent
on outdoor temperature
OFF/-29 ... +10° C -15° C
12 Boost
0 ... 99% 0%
14 Optimising time constant
OFF/10 ... 59 OFF
15 Adaptive function of room
temperature
OFF/1 ... 30 OFF
17 Temperature reference feed back
OFF/1 ... 20 OFF
20 Optimisation based on room/
outdoor temperature
ON/OFF OFF
21 Total stop
ON/OFF OFF
22 Pump motion
ON/OFF ON
25 Pump stop in boiler circuit
ON/OFF OFF
27 Boiler protection
ON/OFF OFF
30 Return temperature limiter
10 ... 110° C 40 °C
35 Return temperature influence-max
-9.9 ... 0 ... +9.9 0 °C
36 Return temperature influence-min
-9.9 ... 0 ... 9.9 +2 °C
37 Adaptive function of return limitation
OFF/1 ... 50 25
71 Min on-time of burner
0 ... 9 min 1
196 Service pin LON
ON/OFF OFF
197 LON reset
ON/OFF ON
198 Summer time change
ON/OFF ON
199 Slave address
0 ... 9 15
Circuit I (Heating)
Line Setting range Factory setting Your setting
°C
%
°C
°C
°C
min
Control & overviews
Control & overviews
32
Service parameters 10-11
OFF: The reduced temperature setting will be
constant at all outdoor temperatures.
Dedicates the unit for the time control of the comfort and
reduced temperature periods
Circuit Setting range Factory setting
I 0 ... 5 0
10 Choice of time control unit
The limit of the outdoor temperature at which the
reduced temperature setting is switched off.
Circuit Setting range Factory setting
I OFF / -29 ... +10 °C -15 °C
11 Reduced temperature dependent on outdoor
temperature
The grey
side of the
ECL Card.
ECL Comfort controller - day plan circuit I
Room panel ECA 60 or remote control
ECA 61 on address A
Room panel ECA 60 or remote control
ECA 61 on address B
Select between
0
1
2
Note! The time control of the hot water circuit is always
dedicated to the day plan of circuit II
-29 to +10°C
The setting of reduced temperature depends
on the outdoor temperature, when the outdoor
temperature is higher than the set limit.
The lower the outdoor temperature the less
the temperature reduction. When the outdoor
temperature is lower than the set limit, there is
no temperature reduction.
32
Adjusting the service
parameters
In addition to the settings in line 1 to 7 on the grey side
of the ECL card, there is an extended service menu
from line 10 and onwards.
When you have entered all your personal settings, turn
the ECL Card over so that the yellow side faces you.
If you want to copy the new settings to the ECL Card
(recommended by Danfoss), see section 34 Copying
data with the ECL Card.
Make a note of your new settings on the parameter list
in section 31.
Push repeatedly to reach the lines
numbered 10 and onwards.
Now you can move to any line of your choice.
Set the parameter value.
You can select any of the two circuits no
matter what line you are in. You will not
necessarily enter the same line number.
See the service parameters in section 31.
Line
number
Value
Range
indicator
0
01
100%
0%
-20 -10-29 0 10 2015
Reduction
Outdoor
Temp
o
C
Extended service
Extended service
Extended service
32
Service parameters 14-15
Optimises the start and stop times for the reduced temperature
period to obtain the best comfort at the lowest
Circuit Setting range Factory setting
I OFF / 10 ... 59 OFF
14 Optimising constant
The grey
side of the
ECL Card.
32
Service parameter 12
In order to shorten the heating-up period after a reduced
temperature period, the flow temperature can be increased
temporarily.
If a room sensor is installed the boost stops when the
optimising period is over or the room temperature has
been reached.
Shortens the heating-up period by increasing the flow tempera-
ture by the percentage you set.
Circuit Setting range Factory setting
I 0 ... 99 % 0%
12 Boost
The grey
side of the
ECL Card.
Set the percentage at which you want the flow
temperature to be changed temporarily.
The adaptive function will eliminate the difference
between the required and the actual room temperature by
integrating the difference and adjusting the reference for
the flow temperature.
Dimensioning temperature: The lowest outdoor
temperature at which the heating system can obtain
the desired temperature.
OFF: The adaptive function is cancelled.
1 : The desired temperature is adapted
quickly.
30 : The desired temperature is adapted
slowly.
Controls how fast the room temperature adapts to the
desired temperature.
Circuit Setting range Factory setting
I OFF / 1 ... 30 OFF
15 Adaptive function of the room temperature
OFF: No optimisation. The heating starts and stops at
the times set in the week plan.
41
25
Adjust the optimising time constant. The value
consists of a number of two digits. You can select
the following values:
11, 12, ..... 59.
The two digits have the following meaning:
1. digit (system type and heat accumulation of
the building)
1
2
3
4
5
light
medium
heavy
medium
heavy
1. digit Heat accumulation System type
of the building
Radiator
system
Floor heating
system
2. digit (capacity of the heating system)
2. digit Dimensioning Capacity
temperature
large
.
.
normal
.
.
small
-50 °C
.
.
-25 °C
.
.
-05°C
0
.
.
5
.
.
9
Extended service
Extended service
Extended service
32
Service parameter 21
The grey
side of the
ECL Card.
32
Service parameters 17-20
The grey
side of the
ECL Card.
Select total stop function.
ON: Total stop function is ON. At total stop the
flow temperature reference is lowered to
10°C, and the minimum setting of the flow
temperature limit of line 2 (see section
22) is overruled in the reduced
temperature period.
OFF: No total stop
T
REF
Time
Ref. Temp
T
MIN
10 C
T
REF
Time
Ref. Temp
T
MIN
10 C
Select calculation method:
Calculation based on room
temperature (only if a room sensor is
used).
Calculation based on outdoor
temperature. Use this setting if you
have no room sensor.
ON:
OFF:
Circuit Setting range Factory setting
I ON / OFF OFF
The optimised start and stop time calculation can be based on
either the room temperature or on the outdoor temperature.
20 Optimisation based on room/outdoor temperature
Circuit Setting range Factory setting
I ON / OFF OFF
Decide whether you want a total stop during reduced
temperature period.
21 Total stop
OFF: The temperature reference in circuit I is
not influenced by any other controller.
1 - 20: The temperature reference in circuit I will
always at least correspond with the value
of the set number + the highest
temperature reference degree of an
external controller.
T
ref
(l)
T
ref
(ll)
Setting line 17
Time
°C
This function is used if circuit I is the main supply for toher
mixing circuits.
The temperature reference in heating circuit I can be influenced by
another external. The set number determines the influence of the
flow temperature reference in circuit I or the reference signal by
any other connected controller.
Circuit Setting range Factory setting
I OFF / 1 ... 20 OFF
17 Temperature reference feedback
Extended service
Extended service
/