Vantage RS8-L-DIN Installation guide

Type
Installation guide
1
RS8-L-DIN
Country of Origin: Made in China
OVERVIEW
The Relay Station Lighting - DIN, model number RS8-L-DIN,
features eight isolated latching relay channels, designed to control
lighting. The station’s relays switch from 0 to 277 volts and up to
10amps at each load* position. Relays are singlepole, single throw,
offering a set of eight latching contacts.
Each relay has a manual actuator button on the front which toggles
the relay and is useful for testing wiring and operation without
programming the system. This station may also be used as a low-
voltage relay station**. LEDs indicate relay state. Relays latch to
retain the last state in the event of a power interrupt.
* The station does not produce any power ** Generally, high-voltage and low
SPECIFICATIONS
General
Dimensions, HWD 85.7mm x 157.2mm x 61.9mm (3.38” x 6.19” x 2.44”)
Weight 403g
Max. Voltage @ Relay 277VAC / 440VDC
Min. Voltage @ Relay 0VAC / 0VDC
Max. Current @ Relay 10A
Load Types Resistive, Constant-Speed Motors, Ballast, Incandescent
Number of Loads 8
Relay Actuators 8
Lightning Surge Protection High-Voltage ITU-T K.20
LED Indicators Status and Load State
Mounting 35 mm DIN Rail (EN 50 022: 1977)
Station Bus Connections 24V / 36V Station Bus
Station Bus Specication 2C, 16AWG / 1.31mm2, twisted, nonshielded, <30pF per foot. Separate a
minimum of 12” / 30.5cm from other parallel communication and/or
high-voltage runs.
Station Equivalent InFusion 0.7W on IC-24 / 1.1W on IC-36
Station Wiring Conguration Daisy-chain, Star, Branch
Ambient Operating Temperature 0-40°C / 32-104°F
Ambient Operating Humidity 5-95% non-condensing
Certications UKCA, CE, FCC, UL, cUL, EN 55032, EN 55035, EN 61000-3-2,
EN 61000-3-3
DIN Relay Lighting Station
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: IS-0509 – rev. 2 9/23
2
IS-0509 – Rev. 2
SOFTWARE/FIRMWARE
This station is compatible with InFusion Design Center software. For new projects it is recommended that rmware and software be
kept to the most current release.
INSTALLATION AND STATION SETUP IN SOFTWARE
Installation of Vantage products should be performed or supervised by a Certied Vantage Installer. Do not use this Relay Station to
control an outlet/plug. High-voltage DIN products must be installed inside of a properly vented and covered DIN enclosure. There are
two methods of connecting the Station Bus to this station:
1. Use the 2 wire pigtail connection located on the top of the DIN relay station, and
2. Use the pins on the side of the Station, to pass Station Bus between DIN stations, part #VDC-0197, (note: the VDC-0197 Station
Bus connector is not supported on all DIN products).
Mount DIN relay station on a standard 35 mm DIN Rail (EN 50022: 1977).
All voltage connections to the RS8-L-DIN relays are wired to removable screw terminal connectors. These relays may be given
custom names in software to facilitate their use in Design Center programming.
INFUSION
First select the room, then click on Vantage Objects in the Object Explorer and expand Stations, WireLink. From the list of stations
double-click on the DIN Relay Station Lighting-DIN to place it in the room. In the Object Editor name the station and make sure it is
assigned to the correct Station Bus.
PROGRAMMING THE RELAY STATION
Because they are relays the eight buttons on the RS8-L-DIN cannot be programmed directly. Programmed Tasks, Time Controls or
Host Commands are used to control the relays. The relays are accessed by selecting them in programmed tasks.
CONFIGURATION
When the station is rst connected to the Station Bus, the diagnostic LED will blink twice followed by a pause, meaning that the
station is connected correctly but not yet congured. From Design Center, click on the Congure Stations button on the toolbar.
Highlight the RS8-L-DIN station. The Status LED will blink 5 times followed by a pause and the button LEDs will blink rapidly
indicating that the station is in conguration mode. To nish conguring press any button on the Station 3 times. The station may also
be congured by typing the serial number in the project le, using this method the station will automatically be congured when the
system is programmed. Once congured the Status LED will blink evenly and the buttons stop blinking.
DIAGNOSTIC LED (STATUS)
The LED blinks steady on and off or 2, 3, 4, or 5 blinks followed by a pause:
One Even Blink: The Station is operating correctly and is congured
Two Blinks: The Station is operating correctly but is not congured
Three Blinks: The Station is not communicating with the Controller. Check Station Bus Wire connections
Four Blinks: Factory problem. Please contact the factory
Five Blinks: The Station is in conguration mode
WIRING DIAGRAM
Strip back insulation
0.25” (6.5mm) RECOMMENDED WIRE TYPE FOR SCREW TERMINALS
LOADS:
Stranded - 0.75 - 3.31mm2 / 18-12 AWG,
copper wire; must match breaker wire gauge
STATION BUS:
Vantage Station Bus (see specications table)
3.4”
85.7mm
2.44
61
.9mm
6.19
157. 2mm”
1 7 82 3 4 5 6
STATUS
RELAY STATION LIGHTING - DIN
SET
RS8-L-DIN
Serial Number
STATION
BUS
CLASS 2
SET
COM
SET
COM
SET
COM
SET
COM
1357
SET
COM
2
SET
COM
4
SET
COM
6
SET
COM
8
RS8-L-DIN
APPLIANCE CONTROLS
35PT
Wire Gauge Max.
Screw Torque Max.
Enclosure
Ambient Temperature Max.
Line Feeds Max.
Load Resistive Max.
Load Motor Max. (FLA)
Load Ballast Max.
Load Incandescent Max.
12 AWG
4.4 in/lb.
Type 1 | IP20
104°F | 40°C
8
10 A | 277 V
10 A | 277 V
10 A | 277 V
10 A | 277 V
RS8-L-DIN
APPLIANCE CONTROLS
35PT
Wire Gauge Max.
Screw Torque Max.
Enclosure
Ambient Temperature Max.
Line Feeds Max.
Load Resistive Max.
Load Motor Max. (FLA)
Load Ballast Max.
Load Incandescent Max.
12 AWG
4.4 in/lb.
Type 1 | IP20
104°F | 40°C
8
10 A | 277 V
10 A | 277 V
10 A | 277 V
10 A | 277 V
MULTI-VIEW LINE DRAWINGS
No. IS-0509 – rev. 2 9/23
© Copyright 2023 Legrand All Rights Reserved.
© Copyright 2023 Tous droits réservés Legrand.
© Copyright 2023 Legrand Todos los derechos reservados.
Vantage warranties its products to be free of
defects in materials and workmanship for a period
of five (5) years. There are no obligations or
liabilities on the part of Vantage for consequential
damages arising out of, or in connection with,
the use or performance of this product or other
indirect damages with respect to loss of property,
revenue or profit, or cost of removal, installation
or reinstallation.
Vantage garantit que ses produits sont exempts
de défauts de matériaux et de fabrication pour
une période de cinq (5) ans. Vantage ne peut être
tenu responsable de tout dommage consécutif
causé par ou lié à l’utilisation ou à la performance
de ce produit ou tout autre dommage indirect lié
à la perte de propriété, de revenus, ou de profits,
ou aux coûts d’enlèvement, d’installation ou de
réinstallation.
Vantage garantiza que sus productos están libres
de defectos en materiales y mano de obra por un
período de cinco (5) años. No existen obligaciones
ni responsabilidades por parte de Vantage por
daños consecuentes que se deriven o estén
relacionados con el uso o el rendimiento de este
producto u otros daños indirectos con respecto a
la pérdida de propiedad, renta o ganancias, o al
costo de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
800.555.9891
www.legrand.us/vantage
FRONT VIEW
TOP VIEW
BOTTOM VIEW
SIDE LABEL ENLARGED
SIDE VIEW
  • Page 1 1
  • Page 2 2
  • Page 3 3

Vantage RS8-L-DIN Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages