!DEA
Maximum thermal ow rate kW 25,5 25,5 26,5
Minimum thermal ow rate kW 11,5 11,5 11,5
Effective nominal output kW 22,9 23,1 23,9
Minimum effective output kW 9,9 10,3 10,1
Combustion efciency with nominal load (100%) % 91,0 91,0 92,7
Combustion efciency with reduced load % 88,0 88,6 89,5
Heat loss at casing (min.-max.) % 1,68 - 1,12 0,6 - 0,42 1,64 - 2,51
(*) Flue gas temperature tf-ta (max.) °C 107,5 107,5 91,7
Flue gas mass ow rate (min.-max) g/s 16,76 - 8,85 16,76 - 8,85 16,91 - 19,36
Excess λ air % 122,1 122,1 109,96
CO
2
% 2,4 - 5,0 2,4 - 5,0 2,5 - 5,3
CO at Minimum Heat Input with 0% of O2
ppm 37 - 94 37 - 94 24 - 91
NOx Class 2 2 2
Heat loss at chimneywithburneron(min.-max.) % 11,97 - 9,02 11,4 - 9,02 10,48 - 7,31
Heat loss at chimney with burner off % 0,59 0,59 0,51
Available head at the base of the chimney Min. / Max.
Pa - - -
Notes: (*) Room Temperature = 20°C
Data detected with appliance running on Methane gas (G20)
Description Symbol Unit !DEA
Nominal Heat Output Pnominale kW 23 23 24
Seasonal space heating energy
efciency
ƞ
s % 78 79 79
heating mode
C C C
Useful Heat Output in high-tempera-
ture regime
(Tr 60 °C / Tm 80 °C)
P
4 kW 22,9 23,1 23,9
Useful efciency at nom. heat output
in high-temperature regime
(Tr 60 °C / Tm 80 °C
ƞ
4 % 81 81,6 81,3
Useful heat output at 30% of nom.
heat output in low-temperature
regime (Tr 30 °C)
P
1 kW 6,84 7,0 7,2
Useful efciency at 30% of nom. heat
output in low-temperature regime
(Tr 30 °C)
ƞ
1 % 80,6 82,5 81,7
Range-rated boiler: YES / NO NO NO NO
Auxiliary electricity consumption
At full load elmax kW 0,058 0,058 0,058
At part load elmin kW 0,055 0,055 0,055
In stand-by mode P
SB kW 0,001 0,001 0,001
Other items
Stand-by heat loss P
stb kW 0,1676 0,1676 0,1349
Emissions of nitrogen oxides NOx Mg/kWh 184 184 153
Declared load prole M M L
Energy efciency in DHW production
mode
ƞ
wh % 64 60 59
Daily electricity consumption Qelec kWh - - -
Daily fuel consumptionl Qfuel kWh 9,19 9,69 19,89
Inside sound power level Lwa dB (A) 56,4 56,3 51,4
B B B
For the adjustment data: NOZZLES - PRESSURE - DIAGRAMS - FLOW RATES - CONSUMPTION refer
to the paragraph ADAPTATION TO OTHER TYPES OF GAS.