Unical !DEA Installation guide

Category
Fireplaces
Type
Installation guide
ITALIANOENGLISH
ISTRUZIONI PER L’INSTALLATORE E IL MANUTENTORE
INSTALLATION AND SERVICING MANUAL
AC 23 - AR 23 - AC 23 PLUS
CS 18 - RS 18
CS 24 - RS 24 - CS 24 PLUS
CS 28 - RS 28 - CS 28 PLUS
CS 32 - RS 32 - CS 32 PLUS
9
Caratteristiche Tecnhiche
ITALIANO
2
CARATTERISTICHE TECNICHE
E DIMENSIONI
2.1 - CARATTERISTICHE TECNICHE
2.2 - VISTA CON L’INDICAZIONE DEI COMPONENTI PRINCIPALI E DIMENSIONI
!DEA AC 23
!DEA AC 23 Plus
Vista dall’alto
Vista da sotto
!DEA AC 23 - !DEA AR 23 - !DEA AC 23 Plus
NOTA!
Maggiori info nella sezione
‘Info Tecniche’ alla pagina della

30
ATTENZIONE!
Funzione riservata esclusivamente ai
Centri di Assistenza Autorizzati Unical
AG S.p.A.
Alcuni parametri di servizio possono
essere modifcati dal pannello comandi:
4.2 - PARAMETRI MODIFICABILI DA PANNELLO COMANDI
x 10’’
service
MAX
M
I
N
service
MAX
M
I
N
service
MAX
M
I
N
service
OK
OK
1 ATTIVAZIONE
Premendo il pulsante (D) per 10 secondi, si
attiva la funzione quando la chiave compare sul
display in modo lampeggiante
POTENZA MASSIMA DI RISCALDAMENTO
VALORI
DA A STANDARD
0 (Min) 99 (Max) 99
TEMPERATURA DELLA SONDA ESTERNA
VALORI
DA A STANDARD
- 20°C) + 10°C) 20 (0°C)
LIMITATORE DEL NUMERO DI ACCENSIONI
VALORI
DA A A STANDARD
 1 (minuto) 15 (minuti) 0
(*) A ISTERESI VARIABILE
POST CIRCOLAZIONE DELLA POMPA
VALORI
DA A STANDARD
0 (5 min) 1 (SEMPRE) 0 (5 min)
SELEZIONE
Ruotare la manopola RISCALDAMENTO ‘’B’
MODIFICA VALORE
Ruotare la manopola SANITARIO ‘’C’’
Il valore lampeggia sul display.
CONFERMA SELEZIONE
Confermare il parametro da modicare premendo
il tasto di sblocco
CONFERMA VALORE
Confermare il valore premendo il tasto di sblocco
SELEZIONE PARAMETRO
Tornare al punto 2.
DISATTIVAZIONE
Per uscire dall’elenco
parametri attendere 20”
o ruotare rapidamente la
manopola sanitaria ‘‘C’.
2
4
3
5
6
7
MAX
MIN
MAX
MIN
service
2
Provisions for proper disposal of the product in accordance with Directive 2002/96/EC
At the end of its life cycle the product must not be disposed of as urban waste. It can be taken to
a special recycling centre managed by the local authorities, or to a dealer who offers this service.
Separate disposal of a domestic appliance avoids possible negative consequences for the
environment and human health deriving from inappropriate waste handling and allows the recovery
of the materials of which it is made, in order to obtain signicant energy and resource savings.
http://www.unicalag.it/prodotti/domestico-50/standard-gas/75/dea
3
Installation Instructions
Technical Features
General information
Maintenance instructions
ENGLISH
Attention: this manual contains instructions for the exclusive use of the professionally qualied installer
and/or maintenance technician in compliance with current legislation.
The user is NOT qualied to intervene on the boiler.
The manufacturer will not be held liable in case of damage to persons, animals or objects resulting from
failure to comply with the instructions contained in the manuals supplied with the boiler.
2 TECHNICAL FEATURES AND DIMENSIONS ................................................................................................ 10
2.1 Technical features .................................................................................................................................10
2.2 Main components view and dimensions ................................................................................................10
2.3 Available ow rate / pressure diagram ..................................................................................................13
2.4 Operation data .......................................................................................................................................14
2.5 General features ....................................................................................................................................14
4 MAINTENANCE INSTRUCTIONS ..................................................................................................................28
4.1 Inspection and maintenance instructions ..............................................................................................28
4.2 Parameters that can be edited from the control panel ..........................................................................30
4.3 Adaptation of the power to the heating system .....................................................................................31
4.4 Important notes .....................................................................................................................................32
4.5 Wiring diagram ......................................................................................................................................32
4.6 Error codes ............................................................................................................................................ 34
3 INSTALLATION INSTRUCTIONS ................................................................................................................... 15
3.1 General warnings ..................................................................................................................................15
3.2 Installation standards ............................................................................................................................15
3.3 Preventive system verication and adjustment operations ...................................................................15
3.4 Packaging ..............................................................................................................................................16
3.4 Positioning the boiler .............................................................................................................................17
3.6 Flue gas exhaust pipe connection ......................................................................................................... 18
3.7 Connections ..........................................................................................................................................21
3.8 Filling the system ...................................................................................................................................21
3.9 Electrical connections ............................................................................................................................22
3.10 Commissioning ................................................................................................................................... 23
3.11 Measurement of combustion efciency during installation ....................................................................24
3.11.1 Unblock button with calibration function .................................................................................... 24
3.11.2 Probes positioning ....................................................................................................................24
3.12 Burner adjustment .................................................................................................................................25
3.12.1 Electric minimum adjustment .................................................................................................... 27
3.12.2 Adaptation of the power to the heating system .........................................................................27
1 GENERAL INFORMATION ...............................................................................................................................4
1.1 General warnings ....................................................................................................................................4
1.2 Symbols used in the manual ...................................................................................................................5
1.3 Appropriate use of appliance ...................................................................................................................5
1.4 Information for system manager ..............................................................................................................5
1.5 Safety warnings ....................................................................................................................................... 6
4
1
GENERAL INFORMATION
Any product repairs must be performed solely by
personnel authorised by Unical, using original spare
parts only. Failure to comply with the above can
compromise the safety of the appliance and void
the warranty.
To guarantee appliance efciency and its correct
operation, yearly maintenance must be performed
by qualied personnel.
Should you decide not to use the appliance, parts
entailing potential sources of hazard must be made
safe.
Before commissioning an appliance that has not
been used, wash the domestic hot water production
system, making the water ow until it has been fully
replaced.
Should the appliance be sold or transferred to a new
owner or if you move and leave the appliance, always
make sure that the instruction booklet accompanies
it in order to be consulted by the new owner and/or
installer.
Only original accessories must be used for all appli-
ances with optionals or kits (including electric).
This appliance is intended solely for the use for which
it was expressly designed.
Any other use is to be considered improper and
therefore dangerous (*).
1.1 - GENERAL WARNINGS
The instruction booklet is an integral and essential
part of the product and must be kept by the user.
Read the warnings contained in this instruction
booklet carefully as they provide important guidelines
regarding installation, use and maintenance safety.
Keep the booklet with care for further consultation.
Your appliance must be installed and serviced in
compliance with the standards in force according
to the manufacturer instructions, up to standard
and by legally qualied and certied personnel.
Systems for the production of domestic hot wa-
ter MUST be constructed entirely with compliant
materials.
By professionally qualied personnel we mean:
personnel with specic technical skill in the eld
of heating system components for civil use, do-
mestic hot water production and maintenance.
Personnel must have the qualications provided
for by current legislation.
Incorrect installation or improper maintenance
can cause damage to persons, animals or objects
for which the manufacturer is not responsible.
Before performing any cleaning or maintenance,
disconnect the appliance from the energy mains by
acting on the switch of the system and/or through
the specic cut-off devices.
Do not obstruct the terminals of the intake/exhaust
ducts.
In the event of failure and/or malfunctioning of the
appliance, switch it off and do not try to repair it or
intervene on it directly. Contact only personnel qual-
ied in compliance with law.
5
1.2 - SYMBOLS USED IN THE MANUAL
Pay special attention when reading this manual to the parts marked by the symbols:
NOTE!
Tips
for the user
ATTENTION!
Possible dangerous
situation for the product
and the environment
DANGER!
Serious danger
to safety
and health
1.3 - APPROPRIATE USE OF APPLIANCE
The !DEA boiler has been built according to the current level of engineering and ac-
knowledged technical safety rules.
Nonetheless, if improperly used, dangers could arise for the safety and life of the user
and other persons or damage to the equipment or other objects.
The appliance is designed to work in heating systems, with hot water circulation, for
the production of domestic hot water.
Any other use must be considered improper.
UNICAL AG S.p.A. will not be held liable for any damage resulting from improper use.
Use according to the intended purposes also includes strict compliance with the in-
structions in this manual.
The user must be instructed concerning the use and operation of his heating system, in particular:
Deliver these instructions to the user, as well as other documents concerning the appliance
inserted in the envelope inside the packaging. The user must keep this documentation
safe for future consultation.
Inform the user about the importance of the air vents and the ue gas exhaust system, high-
lighting their essential features and the absolute prohibition of modifying them.
Inform the user concerning controlling the system's water pressure as well as operations to
restore it.
Inform the user concerning correct temperature control, control units/thermostats and radiators
for saving energy.
Please note that, in compliance with the standards in force, the inspection and maintenance of
the appliance must be carried out in compliance with the regulations and frequency indicated
by the manufacturer.
Should the appliance be sold or transferred to a new owner or if you move and leave the ap-
pliance, always make sure that the instruction booklet accompanies it in order to be consulted
by the new owner and/or installer.
The manufacturer will not be held liable in the event of damage to persons, animals or
objects resulting from failure to comply with the instructions contained in this manual.
1.4 - INFORMATION PROVIDED TO THE USER
NOTE!
For further details
refer to the Technical Information:
http://www.unicalag.it/prodotti/
domestico-50/standard-gas/75/dea
6
1.5 - SAFETY WARNINGS
ATTENTION!
The boiler cannot be used by children.
The boiler can be used by adults and only after having carefully read the users ma-
nual. Children should be supervised to ensure that they do not play or tamper with
the device.
ATTENTION!
The appliance must be installed, adjusted and maintained by professionally qualied
personnel, in compliance with the standards and provisions in force. Incorrect instal-
lation can cause damage to persons, animals and objects for which the manufacturer
cannot be held responsible.
DANGER!
NEVER attempt performing maintenance or repairs on the boiler on your own initiative.
Any work must be done by professionally qualied personnel. We recommend stipulat-
ing a maintenance contract.
Insufcient or irregular maintenance can jeopardise the operating safety of the appli-
ance and cause damage to persons, animals and objects for which the manufacturer
cannot be held responsible.
Changes to the parts connected to the appliance (once the appliance installation is complete)
Do not modify the following parts:
- the boiler
- the gas, air, water and electricity supply lines
- the ue gas pipe, the safety valve and the exhaust pipe
- the construction parts which affect the operating safety of the appliance
Attention!
To tighten or loosen the screwed ttings, use only appropriate xed spanners.
Incompliant use and/or inappropriate tools can cause damage (e.g. water or gas leakage).
ATTENTION!
Indications for propane gas-red appliances
Make sure that the gas tank has been deaerated before installing the appliance.
For state-of-the-art tank venting, contact the LPG supplier or person qualied in compliance
with the law requirement.
If the tank has not been professionally deaerated, ignition problems could arise.
In that case, contact the supplier of the LPG tank.
Smell of gas
Should a smell of gas be perceived, follow these safety guidelines:
- do not turn electric switches on or off
- do not smoke
- do not use the telephone
- close the gas shut-off valve
- air out the area where the gas leakage has occurred
- inform the gas supplier or a company specialised in installation and maintenance of heating
systems.
Explosive and easily ammable substances
Do not use or store explosive or easily ammable materials (e.g. petrol, paints, paper) in the
room where the appliance is installed.
DANGER!
Do not use the appliance as a supporting base for objects.
In particular, do not place receptacles containing liquids (Bottles, Glasses, Jars or Detergents)
on top of the appliance.
If the appliance is installed inside a housing, do not insert or rest other objects inside this housing.
7
General information
ENGLISH
1.6 - TECHNICAL DATA PLATE
CE marking
The CE marking certies that the boilers meet:
- The essential requirements of the gas appliance
directive (directive 2009/142/EEC)
- The essential requirements of the electromagnetic
compatibility directive (2004/108/EEC)
- The essential requirements of the efciency di-
rective (92/42/EEC)
- The essential requirements of the efciency di-
rective (directive 2006/95/EEC)
KEY:
1 = CE monitoring body
2 = Type of boiler
3 = Boiler model
4 = Number of stars (directive 92/42 EEC)
5 = (S.N°) Serial Number
6 = P.I.N.ProductIdenticationNumber
7 = Typesofapproveduegasexhaustcongurations
8 = (NOx)NOxClass
A = Heatingcircuitcharacteristics
9 = (Pn) Effective nominal output
10 = (Pcond) Effective output in condensation
11= (Qmax)Maximumheatoutput
12= (AdjustedQn)Adjustedforratedheatoutput
13= (PMS)Max.heatingoperatingpressure
14= (Tmax)Max.heatingtemperature
B = Domestichotwatercircuitcharacteristics
15= (Qnw)Ratedheatoutputindomestichotwaterfunction
(if different to Qn)
16= (D)SpecicD.H.W.owrateaccordingtoEN625-EN
13203-1
17= (Rfactor)No.oftapsaccordingtothedeclaredamountof
water(EN13203-1)
18= (Ffactor)No.ofstarsaccordingtothedeclaredqualityof
thewater(EN13203-1)
19= (PMW)Max.domestichotwateroperatingpressure
20= (Tmax)Max.domestichotwatertemperature
C = Electricalcharacteristics
21= Electricalpowersupply
22 = Consumption
23 = Protection rating
D = Countries of destination
24 = Direct and indirect countries of destination
25 = Gas category
26 = Supply pressure
E = Factory settings
27 = Adjusted for gas type X
28 = Space for national brands
The technical data plate is located
inside the boiler on the back at the
bottom
8
1.7 - WATER TREATMENT
The treatment of the supply water
allows to prevent inconveniences
and maintain the functionality and
efciency of the generator over time.
The ideal water pH in heating systems
must be within:
To minimise corrosion, it is crucial to
use a corrosion inhibitor; in order for
it to work properly, the metal surfac-
es must be clean.
(see system protection ACCESSO-
RIES sect. in domestic price list)
ATTENTION (*) see general warnings
1.1:
The heating only models are NOT
suitable for the production of water
for human consumption according
to Ministerial Decree D.M. 174/2004.
ATTENTION!
ANY DAMAGE TO THE BOILER
CAUSED BY THE FORMATION OF
FOULING OR BY CORROSIVE WA-
TER WILL NOT BE COVERED BY THE
WARRANTY.
1.8 - BOILER ANTIFREEZE
PROTECTION
To activate the antifreeze function, position
the two knobs as shown in the gure.
MAX
M
I
N
MAX
MIN
This protection can intervene only if
the electricity and gas supplies are
connected.
If one of the two is not available and upon
reset 11 (SR) a temperature of < 2 °C is
detected, the appliance will behave as
described in tab. pos 2.
The heating system can be protected
effectively from frost by using antifreeze
products with inhibitor for heating
systems.
Do not use car engine antifreeze
products as they could damage the
water gaskets.
VALUE MIN MAX
PH 6.5 8
Hardness [°fr] 9 15
NOTE!
Further details in the section
‘Technical Information’ on the boiler
page of the www.unicalag.it website
P
O
S
ANTIFREEZE FUNCTION
Power supplies 11 - SR (*) Status
function
antifreeze
Actions
Electric Gas
1
ON ON < 6 °C ON - Burner and Pump ON until T > 14°C
2
ON OFF
< 2 °C ON
Only when both the power supplies are ON:
- Burner and Pump OFF until T > 5°C
- When T > 5°C then Burner and Pump
ON until T > 14°C.
OFF ON
OFF OFF
(*) Sensor 11 par. 2.2
9
Technical Features
ENGLISH
2
TECHNICAL FEATURES
AND DIMENSIONS
2.1 - TECHNICAL FEATURES
2.2 - VIEW WITH THE INDICATION OF THE MAIN COMPONENTS AND DIMENSIONS
!DEA AC 23
!DEA AC 23 Plus
View from above
View from below
!DEA AC 23 - !DEA AR 23 - !DEA AC 23 Plus
NOTE!
Further details in the section
‘Technical Information’ on the boiler
page of the www.unicalag.it website
10
!DEA CS 18 - !DEA RS 18 - !DEA CS 24 - !DEA RS 24 - !DEA CS 24 Plus
View from above
View from below
!DEA CS 24 Plus
!DEA CS 18 - CS 24
11
Technical Features
ENGLISH
!DEA CS 28 / 32 Plus!DEA CS 28 - !DEA CS 32
!DEA CS 28 - !DEA RS 28 - !DEA CS 28 Plus - !DEA CS 32 - !DEA RS 32 - !DEA CS 32 Plus
View from above
View from below
12
2.3 - DIAGRAM OF FLOW RATE/PRESSURE AVAILABLE FOR
INSTALLATION
KEY
No. C.E. S.E. Description
1 db SS Domestic hot water temper-
ature sensor
2 FLS Flow switch with cold water
lter
3 VG Gas valve
4 Fd E.
ACC/RIL
Ignition/detection electrode
5 Burner
6 Combustion chamber
7 AF TF Flue gas anti-overow ther-
mostat
8 Expansion vessel
9 FR
HT
Heat exchanger
10 HL TL Safety thermostat
11 Hb SR Heating temperature sensor
12 Ht P Pump
13 Lp DK Water deciency pressure
switch
14 Boiler drain valve
15 Filling valve
16 Diverter valve
17 Plate heat exchanger
18 FL
FH
VM Fan
19 AF
AS
PV Flue gas pressure switch
20 Safety valve
21 Automatic by-pass
C Domestic hot water
outlet
G ½
G Gas inlet G ¾
F Cold water inlet G ½
M Heating system ow G ¾
R Heating system re-
turn
G ¾
Rc Filling valve
Sc Boiler drain
Svs Safety valve drain
C.E. = ERROR CODES see
par. 4.6
S.E. = WIRING DIAGRAM
KEY see par. 4.5
Flow rate (l/h)
Avaible Head (m.c.a.) metres of water
13
Technical Features
ENGLISH
2.5 - GENERAL FEATURES !DEA
2.4 - OPERATING DATA ACCORDING TO UNI 10348 !DEA
For the adjustment data: NOZZLES - PRESSURE - DIAGRAMS - FLOW RATES - CONSUMPTION refer
to the paragraph ADAPTATION TO OTHER TYPES OF GAS.
Attention: should the boilers be used to heat systems at low temperature (e.g. radiant panels), a mixer valve is required to avoid
condensation forming.
!DEA AC23/AR23 CS18/RS18 CS24/RS24 CS28/RS28 CS32/RS32
Maximum thermal ow rate kW 25.5 20.5 26.5 30.1 34.5
Minimum thermal ow rate kW 11.5 9.0 11.5 11.5 13.5
Effective nominal output kW 22.9 18.5 24.6 28 31.6
Minimum effective output kW 9.9 7.8 10.1 10.2 11.6
Effective efciency at nominal load (100%) % 89.9 90.4 92.92 93.18 91.69
Effective efciency required (100%) % 89.72 89.54 92.78 92.9 90.0
Effective efciency at 30% load % 89.43 90.23 90.23 90.42 90.42
Effective efciency required (30%) % 87.08 86.80 90.17 90.34 87.5
Number of stars (according to 92/42 EEC)
no.
Combustion efciencywithnominalload(100%) % 91 91.57 93.72 94.46 93.59
Combustion efciency with reduced load % 88 83.41 88.92 88.78 87.16
Heat loss at casing (min.-max.) % 1.68-1.11 2.78-1.17 0.86-0.80 0.27-1.28 0.61-1.90
(*) Flue gas temperature tf-ta (max.) % 107.5 121.5 109 103.5 120.9
Flue gas mass ow rate (min.-max) g/s 16.76-8.85 14.32-13.0 14.21-13.89 14.7-14.6 17.2-16.6
Excess λ air % 122.09 80.61 46.94 35.3 33.84
CO
2
% 2.4-5 2.3-6.2 3.0-7.7 2.9-8.4 2.9-8.5
NOx(WeightedvalueaccordingtoEN297/A3orEN483) mg/kWh 189.2 178.59 178.59 186.6 178.21
NOx Class 2 2 2 2 2
Heat loss at chimneywithburneron(min.-max.) % 11.97-9.02 8.43-16.59 11.08-6.28 11.2-5.5 12.8-6.4
Heat loss at chimney with burner off % 0.657 0.457 0.354 0.32 0.280
Available head at the base of the chimney Min. / Max. Pa 2 / 50 2 / 50 2 / 50 2 / 50
2 / 50
Notes: (*) Room Temperature = 20°C Data detected with appliance running on Methane gas (G20)
!DEA
AC 23 AR23 CS 18 RS18 CS 24 RS24 CS 28 RS28 CS 32 RS32
Appliance category
II
2H3P
II
2H3P
II
2H3P
II
2H3P
II
2H3P
Minimum heat. circuit output (∆t 20 °C)
l/min
7.12 5.56 7.26 7.3 8.28
Minimum heating circuit pressure
bar
0.5 0.5 0.5 0.5 0.5
Maximum heating circuit pressure
bar
3 3 3 3 3
Primary circuit content
l
3 3 3 3.5 3.5
Maximum operating temperature in heat.
°C
78 78 78 78 78
Minimum operating temperature in heat.
°C
45 45 45 45 45
Expansion vessel total capacity
l
6 6 6 8 10
Expansion vessel pre-load
bar
1 1 1 1 1
Maximum system capacity (maxtemp.calc.)
l
138 138 138 184 230
Minimum domestic hot water circuit ow rate
l/min.
2.5 - 2.5 - 2.5 - 2.5 - 2.5 -
Minimum domestic hot water circuit pressure
bar
0.5 - 0.5 - 0.5 - 0.5 - 0.5 -
Maximum domestic hot water circuit pressure
bar
6 - 6 - 6 - 6 - 6 -
Domestic hot water specic ow rate (∆t 30 °C)
l/min.
10.5 - 8.5 - 11.5 - 13.5 - 15.2 -
Domestic hot water ow rate limiter
l/min.
10 - 8 - 10 - 12 - 14 -
Production of D.H.W. in continuous operation with ∆t 45 K
l/min.
7.8 - 8 - 7.6 - 8.9 - 9.9 -
Production of D.H.W. in continuous operation with ∆t 40 K
l/min.
8.8 - 6.3 - 8.6 - 10.1 - 11.1 -
Production of D.H.W. in continuous operation with ∆t 35 K
l/min.
10 - 7.2 - 9.8 - 11.5 - 12.7 -
Production of D.H.W. in continuous operation with ∆t 30 K
l/min.
11.7 - 8.4 - 11.4 - 13.4 - 14.9 -
Production of D.H.W. in continuous operation with ∆t 25 K (*)
l/min.
14.1 - 10.1 - 13.7 - 16.1 - 17.8 -
Temperature adjustable in domestic hot water mode
°C
35-57
-
35-57
-
35-57
-
35-57
- 35-57 -
Voltage/Frequency electric power supply
V-Hz
230/50 230/50 230/50 230/50 230/50
Fuse on the power supply
A (F)
2 2 2 2 2
Maximum absorbed output
W
85 138 138 138 150
Protection rating
IP
X4D X5D X5D X5D X5D
Net weight
kg
27.1 24.6 29.6 28.1 29.6 28.1 34.7 33.2 35.7 34.7
Gross weight
kg
30 27.6 32.5 31 32.5 31 38 36.2 39 37.2
(*) mixed
14
2.6 - GENERAL FEATURES !DEA Plus
OPERATING DATA ACCORDING TO UNI 10348 !DEA Plus
Attention: should the boilers be used to heat systems at low temperature (e.g. radiant panels), a mixer valve is required to avoid
condensation forming.
!DEA AC 23 Plus CS 24 Plus CS 28 Plus CS 32 Plus
Maximum thermal ow rate kW 25.5 26.5 30.1 34.5
Minimum thermal ow rate kW 11.5 11.5 11.5 13.5
Effective nominal output kW 22.9 24.7 28.1 32.3
Minimum effective output kW 9.9 10.1 10.2 12.2
Effective efciency at nominal load (100%) % 89.8 93.05 93.21 93.5
Effective efciency required (100%) % 89.72 92.78 92.90 93.02
Effective efciency at 30% load % 89.43 90.43 90.42 90.42
Effective efciency required (30%) % 87.08 90.18 90.34 90.53
Number of stars (according to 92/42 EEC) no.
Combustion efciencywithnominalload(100%) % 91.36 93.21 94.6 94.57
Combustion efciency with reduced load % 88.5 88.06 89.52 88.76
Heat loss at casing (min.-max.) % 2.0- 1.6 0.17 - 0.16 0.77-1.40 1.07-1.35
(*) Flue gas temperature tf-ta (max.) % 95.5 119.3 96.3 101.4
Flue gas mass ow rate (min.-max) g/s 19.1-21.2 14.21-13.74 15.17-15.35 18.12-16.8
Excess λ air % 140.7 45.15 42.56 35.34
CO
2
% 2.2-4.6 3.0-7.8 2.8-8.0 2.75-8.4
NOx(WeightedvalueaccordingtoEN297/A3orEN483) mg/kWh 189.2 184.16 186.00 164.05
NOx Class 2 2 2 2
Heat loss at chimneywithburneron(min.-max.) % 8.6-11.5 11.94-6.79 5.40-10.48 5.40-11.2
Heat loss at chimney with burner off % 0.657 0.256 0.321 0.280
Available head at the base of the chimney Min. / Max. Pa 2 / 50 2 / 50 2 / 50 2 / 50
(*) Room Temperature = 20°C
!DEA AC 23 Plus CS 24 Plus CS 28 Plus CS 32 Plus
Appliance category II
2H3P
II
2H3P
II
2H3P
II
2H3P
Minimum heat. circuit output (∆t 20 °C) l/min 7.1 7.2 7.3 8.7
Minimum heating circuit pressure bar 0.5 0.5 0.5 0.5
Maximum heating circuit pressure bar 3 3 3 3
Primary circuit content l 3 3 3.5 3.5
Maximum operating temperature in heat. °C 78 78 78 78
Minimum operating temperature in heat. °C 45 45 45 45
Expansion vessel total capacity l 6 6 8 10
Expansion vessel pre-load bar 1 1 1 1
Maximum system capacity (maxtemp.calc.of82°C) l 138 138 184 230
Minimum domestic hot water circuit ow rate l/min. 2.5 2.5 2.5 2.5
Minimum domestic hot water circuit pressure bar 0.5 0.5 0.5 0.5
Maximum domestic hot water circuit pressure bar 6 6 6 6
Domestic hot water specic ow rate (∆t 30 °C) l/min. 11 12 13.5 15.5
Domestic hot water ow rate limiter l/min. 10 10 12 14
Production of D.H.W. in continuous operation with ∆t 45 K
l/min. 7.8 7.4 8.7 10.3
Production of D.H.W. in continuous operation with ∆t 40 K
l/min. 8.8 8.3 9.8 11.6
Production of D.H.W. in continuous operation with ∆t 35 K
l/min. 10.0 9.5 11.1 13.2
Production of D.H.W. in continuous operation with ∆t 30 K
l/min. 11.7 11.0 13.0 15.4
Production of D.H.W. in continuous operation with ∆t 25 K (*)
l/min. 14.1 13.2 15.6 18.5
Temperature adjustable in domestic hot water mode
°C 35-57 35-57 35-57 35-57
Voltage/Frequency electric power supply V-Hz 230/50 230/50 230/50 230/50
Fuse on the power supply A (F) 2 2 2 2
Maximum absorbed output W 85 138 138 150
Protection rating IP X4D X5D X5D X5D
Net weight kg 28.6 30.1 35.2 36.2
Gross weight kg 31.5 33 38.2 39.2
(*) mixed
15
Installation Instructions
ENGLISH
3
INSTALLATION INSTRUCTIONS
ATTENTION!
This boiler is intended solely for
the use for which it was expressly
designed. Any other use is to be
considered improper and therefore
dangerous.
This boiler heats water at a temper-
ature lower than the atmospheric
pressure boiling temperature.
Before connecting the boiler, have pro-
fessionally qualied personnel:
a) Thoroughly wash all the piping of
the system to remove any residues
or impurities which could jeopard-
ise proper operation of the boiler,
even from a hygienic point of view.
b) Check that boiler is set up to operate
with the available type of fuel.
This can be seen written on the
package and on the technical feature
plate;
c) Check that the chimney/ue has an
appropriate draught, without any bot-
tlenecks, and that no exhausts from
other appliances are inserted, unless
the ue has been
implemented to accommodate sev-
eral utilities according to specific
standards and regulations in force.
Only after this check can the tting
between the boiler and chimney/ue
be mounted;
ATTENTION!
If there is dust and/or if there are
aggressive/corrosive vapours
present in the installation room,
the appliance must be protected
suitably and must be able to
operate independently from the air
in the room.
ATTENTION!
Only mount the appliance on a closed
wall, made of non-ammable materi-
al, at, vertical so that the minimum
distances required for installation and
maintenance can be observed.
The boiler must be connected to a cen-
tral heating system and/or domestic hot
water supply network compatible with its
efciency and output.
3.1 - GENERAL WARNINGS
3.2 - INSTALLATION STANDARDS
It must be installed by a professionally qualied
technician, who shall take the responsibility of
observing all local and/or national laws published
in the ofcial journal, as well as the applicable
technical standards.
3.3 -
PREVENTIVE VERIFICATION AND
VERIFICATION AND ADJUSTMENT
OPERATIONS
NOTE!
For further details relating to the
standards, rules and regulations
for safe installation of the thermal
unit, refer to the section "Technical
Information" on the boiler page of
the www.unicalag.it website
NOTE!
Further details in the section
‘Technical Information’ on the boiler
page of the www.unicalag.it website
NOTE!
Further details in the section
‘Technical Information’ on the boiler
page of the www.unicalag.it website
16
The !DEA boiler is supplied completely assembled
in a sturdy cardboard box.
After having removed the appliance from
the packaging, make sure that the supply
is complete and undamaged.
The packaging elements (cardboard
box, straps, plastic bags, etc.) must be
kept out of the reach of children as
they are potential sources of danger.
Unical AG S.p.A. will not be held liable
for damage to persons, animals or ob-
jects due to failure to comply with the
instruction above.
H
P
L
A
B
D
C
As well as the appliance, the packaging contains:
A DOCUMENTATION ENVELOPE
- System booklet
- User operating instructions booklet
- Instruction booklet for the installer and
maintenance engineer
- Warranty
- 2 Spare parts form
- Certicate of conformity
B - Connection predisposition paper template
C - 2 rawlplugs for boiler attachment
D - Flue gas exhaust collector (RS - CS version only)
!DEA P
depth
L
width
H
height
18÷24 kW 290 mm
470 mm 810 mm
28÷32 kW 380 mm
21
3.4 - PACKAGING
17
Installation Instructions
ENGLISH
When choosing the place of the installation of the
boiler, follow the safety instructions below:
- Place the boiler in rooms protected from frost.
- Avoid installation in rooms with a corrosive or very
dusty atmosphere.
- The appliance must only be installed on a vertical
and solid wall which can support its weight.
- The wall must not be made of ammable material.
!DEA CS/RS 18 - CS/RS 24 - CS/RS 28 - CS/RS 32
!DEA CS 24/28/32 Plus
Since the temperature of the wall on which the boil-
er is installed and the temperature of the coaxial
(200)
(200)
exhaust pipe do not exceed, in normal operating
conditions, a room temperature beyond 60 K, it is
not necessary to observe the minimum distances
from ammable walls
For boilers with double intake and exhaust pipes, in
the event of crossing ammable walls, insert insula-
tion between the wall and the ue gas exhaust pipe.
!DEA AC/AR 23
!DEA AC 23 Plus
Maintain a distance at the sides of at least 200 mm
from walls with ammable fabrics (e.g. curtains).
3.5 - POSITIONING THE BOILER
Clearance
18
FOR BOILERS WITH FORCED DRAUGHT
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
C11BS
% slope towards outle = 3%
FOR BOILERS WITH NATURAL DRAUGHT
Ventilation of the rooms
The boiler must be installed in an adequate room in
compliance with the standards in force.
The combustion air is withdrawn directly from
the room where the boiler is installed.
Said room must be ventilated in compliance with the
standards.
To connect the ue gas exhaust pipe, local and na-
tional standards must be observed
In the event the boiler is replaced, ALWAYS re-
place the ue gas pipe as well.
The boiler is type approved for the exhaust congu-
rations listed below:
C12x C12
% Slope towards outlet = 3%
TOTAL LENGTH (LA intake + L Exhaust)
COAXIAL Ø60/100 DOUBLE Ø80
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[m]
A
[m]
UP TO
[m]
0,5 1 4 1 + 1 4 + 4
25
(13A+12S)
COAXIAL Ø80/125 DOUBLE Ø60
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[m]
A
[m]
UP TO
[m]
NA NA NA NA NA NA
Distance between air
inlet pipe and flue gas
exhaust pipe: min 250
mm - max 500
Horizontal exhaust and intake terminals directed
outside via coaxial or double pipes.
C32x C32
TOTAL LENGTH (LA intake + L Exhaust)
COAXIAL Ø60/100 DOUBLE Ø80
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[m]
A
[m]
UP TO
[m]
1 2,5 5 1 + 1 4 + 4
25
(13A+12S)
COAXIAL Ø80/125 DOUBLE Ø60
COLLECTOR COLLECTOR
WITH WITHOUT WITH WITHOUT
FROM
[m]
A
[m]
UP TO
[m]
FROM
[m]
A
[m]
UP TO
[m]
1 2,5 7 NA NA NA
Vertical exhaust and intake terminals directed out-
side via coaxial or double pipes..
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Unical !DEA Installation guide

Category
Fireplaces
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI

in other languages